Carrier 50BV020-064 specifications Service, Maintenance

Page 49
SERVICE

SERVICE

MAINTENANCE CAUTION

Improper phase sequence will cause scroll compressor failure due to reverse rotation.

Signs of miswire are:

Excessive noise

Reverse rotation of 3 phase indoor fan

Rapid temperature rise on suction tube

No pressure differential

Correct immediately. Shut off power at disconnect and switch any 2 power leads at unit terminal block or pigtails.

Compressor Rotation — To determine whether or not the compressor is rotating in the proper direction:

1.Connect service gages to suction and discharge pressure fittings.

2.Energize the compressor.

The suction pressure should drop and the discharge pres- sure should rise, as is normal on any start-up. If the suc- tion pressure does not drop and the discharge pressure does not rise to normal levels:

3.Turn off power to the unit and tag disconnect.

4.Reverse any 2 of the unit power leads.

Reapply power to the unit. The suction and discharge pressure levels should now move to their normal start-up levels.

Also, check that the fan is rotating in the proper direction.

NOTE: When the compressor is rotating in the wrong direc- tion, the unit makes an elevated level of noise and does not provide cooling.

Fan Motor Replacement — If required, replace the fan motor with an equal or better type and efficiency motor with equal horsepower. The motor must be rated for a VFD or inverter application. Do not change the horsepower unless there is a system design requirement change and VFD size analysis.

CHECK/CHANGE VFD OUTPUT CURRENT LIMIT — The VFD provides additional fan motor protection by limiting the output current to a programmed value. This value has been factory set according to the factory-installed motor and VFD sizing options.

If the VFD and/or motor is replaced, the VFD setup mode parameter "tHr1" should be reprogrammed to the following calculated values for optimum motor protection and operating range:

For VFD size about equal to motor:

tHr1 = 100*motor nameplate Amps / VFD rated output Amps

MAINTENANCE

Cleaning Unit Exterior — Unit exterior panels should be wiped down using a damp soft cloth or sponge with a mix- ture of warm water and a mild detergent.

Coil Cleaning — Hot water, steam, and direct expansion coils must be cleaned at least once a year to maintain peak per- formance. Dirty coils can contribute to decreased heating or cooling capacity and efficiency, increased operating costs, and compressor problems on direct expansion systems. Dirt, grease, and other oils can also reduce the wettability of the coil surfaces, which can result in moisture blow-off from cooling coils and resulting water leakage problems. If the grime on the surface of the coils becomes wet, which commonly occurs with

cooling coils, microbial growth (mold) can result, causing foul odors and health related indoor air quality problems.

Coils can become dirty over a period of time, especially if air filter maintenance is neglected. Coils should be in- spected regularly and cleaned when necessary. Clean coils with a vacuum cleaner, fresh water, compressed air, or a bristle brush (not wire). Do not use high-pressure water or air. Damage to fins may result. Backflush coil to remove de- bris. Commercial coil cleaners may also be used to help re- move grease and dirt. Steam cleaning is NOT recommend- ed. After cleaning, use a fin comb of the correct fin spacing when straightening mashed or bent coil fins.

Units installed in corrosive environments should be cleaned as part of a planned maintenance schedule. In this type of application, all accumulations of dirt should be cleaned off the coil.

Inspection — Check coil baffles for tight fit to prevent air from bypassing the coil. Check panels for air leakage, particu- larly those sealing the fan and coil compartments. Check for loose electrical connections, compressor oil levels, proper re- frigerant charge, and refrigerant piping leaks. Before start-up, be sure all optional service valves are open.

Air Filters — The 50BV single-piece units come with 1-in. filters. The standard 1-in. filters provide lower pressure drop and longer filter service intervals. The 50BV modular units come with 4-in. filters.

Inspect air filters every 30 days and replace filters as necessary.

Replacement filters should have a minimum efficiency rat- ing of MERV 6 per ASHRAE rating procedures and be rated for up to 625 fpm velocity. Job requirements or local codes may specify higher minimum ratings.

Condensate Drains — Clean the drain line and unit drain pan at the start of each cooling season. Check flow by pouring water into the drain.

Water-Cooled Condensers — Water-cooled condens- ers may require cleaning of the scale (water deposits) due to improperly maintained closed-loop water systems. Sludge build-up may need to be cleaned in an open tower system due to inducted contaminants.

Local water conditions may cause excessive fouling or pit- ting of tubes. Condenser tubes should be cleaned at least once a year, or more often if the water is contaminated.

Proper water treatment can minimize tube fouling and pitting. If such conditions are anticipated, water treatment analysis is recommended. Refer to the System Design Manual, Part 5, for general water conditioning information.

Manual background CAUTION

Follow all safety codes. Wear safety glasses and rubber gloves when using inhibited hydrochloric acid solution. Observe and follow acid manufacturer’s instructions.

Isolate the supply and return water connections when re- moving piping to the condenser.

Clean condensers with an inhibited hydrochloric acid solu- tion. The acid can stain hands and clothing, attack concrete, and, without inhibitor, can attack steel. Cover surroundings to guard against splashing. Vapors from vent pipe are not harmful, but take care to prevent liquid from being carried over by the gases.

Warm solution acts faster, but cold solution is just as effec- tive if applied for a longer period.

49

Image 49
Contents CONTENTS Installation, Start-Upand Service InstructionsSAFETY CONSIDERATIONS GENERAL MAJOR SYSTEM COMPONENTS Constant Volume CV UnitsStep 1 - Complete Pre-InstallationChecks INSTALLATIONTable 2 - Modular Unit Shipping Table a50-7257efFig. 2 - 50BVC,J,Q020-034Dimensions Fig. 3 - 50BVE,K020-034Dimensions a50-8201 Fig. 4 - 50BVT,V,W034 High-BoyDimensionsFig. 5 - 50BVT,V,W034 Low-BoyDimensions Fig. 6 - 50BVT,V,W044-064 High-BoyDimensions Fig. 7 - 50BVT,V,W044-064 Low-BoyDimensions Fig. 8 - 50BVU,X034 High-BoyDimensions Fig. 9 - 50BVU,X034 Low-BoyDimensions Fig. 10 - 50BVU,X044-064 High-BoyDimensions Fig. 11 - 50BVU,X044-064 Low-BoyDimensions a50-7306ef NOTES 1.Dimensions in inches mma50-7307ef NOTES 1.Dimensions in inches mma50-8235 Shipping Weights lbSize 034 Units Size 044-064Units Table 3A - Physical Data - 50BVC,E,J,K,Q Table 3B - Physical Data - 50BVT,U,V,W,X Multiple Fan Units Fig. 15 - Typical Fan Discharge Connections forFig. 16 - Duct Static Pressure Probe a50-7138efP/N 39EK20462 a50-7267efStep 4 - Make Piping Connections Fig. 19 - DHS Limit Switch P/Na50-8253 Fig. 18 - DHS Pressure Limit Location50BVC,J,Q Units Table 5A - Condenser Pressure DropTable 5B - Condenser Pressure Drop 50BVT,V,W Units50BVC,E,J,K,Q Units Table 6A - Hot Water Pressure DropTable 6B - Hot Water Pressure Drop 50BVT,U,V,W,X UnitsTable 7B - Economizer Pressure Drop Curve Step 5 - Complete Electrical Connectionsft wg, 50BVT,U,V,W,X Units a50-7270efTable 9A - Electrical Data - 50BVC,E,J,K,Q Table 9B - Electrical Data - 50BVT,U,V,W,X a50-7272ef Fig. 24 - Typical Wiring 18 to 30 Ton UnitsTwo-StageCooling Units Table 10 - Recommended Cables a50-7273efa50-7164tf Fig. 26 - Field Terminal Blocka50-7275ef Installation Unit Discharge LocationFig. 27 - Modular Unit VAV Control Panel a39-1867tTable 11 - Thermistor Resistance vs Temperature START-UPValues for Supply-AirTemperature Sensor 10 Kilo- ohmTable 13 - Fan Performance - 50BVC,E,Q020 CV Unit Start-UpTable 14 - Fan Performance - 50BVC,E,Q024 Table 15 - Fan Performance - 50BVC,E,Q028 Table 16 - Fan Performance - 50BVC,E,Q034 Table 17 - Fan Performance - 50BVT,U,V034 Table 17 - Fan Performance - 50BVT,U,V034 cont Table 18 - Fan Performance - 50BVT,U,V044 Table 19 - Fan Performance - 50BVT,U,V054 Table 19 - Fan Performance - 50BVT,U,V054 cont Table 20 - Fan Performance - 50BVT,U,V064 Table 20 - Fan Performance - 50BVT,U,V064 cont VAV Unit Start-Up 02-06-04 OMNIZONE VPACFig. 32 - LID a50-7425efFig. 33 - 50BV VFD Display The LID display will show Year Table 22 - Controller Hardware Points Table 21 - Controller Set PointsTable 23 - Software Points Table 24 - Configuration Parameters Unoccupied space or return air temperature demand MAINTENANCE SERVICEFig. 34 - Gravity Flow Method a50-186tfa50-187tf Fig. 35 - Forced Circulation MethodTROUBLESHOOTING Evaporator Fan Performance AdjustmentCharging the System a50-7135tfPOSSIBLE CAUSE PROBLEMPROBLEM Table 28 - Unit TroubleshootingCORRECTION PROCEDURE POSSIBLE CAUSETable 30 - Forcing an Input or Output Table 29 - CV Units LED Diagnostic CodesTable 31 - Clearing a Forced Input or Output Page Page Page Page UNIT WIRING FIELD WIRINGPage WIRE LEGEND FIELD WIRINGa50-7282ef TRANS-1PCB2 J1 FIELD WIRINGUNIT WIRING FIELD WIRINGPCB1 PCB1 FIELD WIRINGLEGEND AND NOTES FOR FIG Catalog No Copyright 2008 Carrier CorporationForm 50BV-3SI 10-08I. PRELIMINARY INFORMATION START-UPCHECKLISTII. PRE-START-UP CONTROLSIII.START-UP