Modular Units — For units with multiple main air- conditioning sections, connect the high voltage compressor power wiring to the line side of the high voltage terminal block in the second section’s high voltage electrical box. This wiring is located in the upper portion of the compressor compartment.
Connect the low voltage wiring, located in the compressor compartment, between the two air conditioning sections using the quick connects provided.
For the supply fan motor, connect the
For units with multiple fans, connect the control power wiring with the quick connects provided at the fan compart- ment junction.
CONTROL WIRING (CV Only) — A standard commercial thermostat controls constant volume units. These units turn compressors on or off in response to zone temperature. The 50BV units provide 2 stages of cooling.
C Transformer
OReversing Valve (heat pumps only)
Y1 1st Stage Compressor Contactor
Y2 2nd Stage Compressor Contactor R Transformer
G Indoor Fan Contactor
Select an appropriate commercial thermostat that has 2 stag- es of cooling control. If the unit is a heat pump, make sure the thermostat is capable of heat pump control. Any of the Debonair® series commercial thermostats will meet the re- quirements, and are available in a variety of attractive styles, in programmable and
Install the thermostat in the space where the temperature is being controlled, according to the instructions provided with the thermostat.
WARNING
Before wiring the thermostat to the unit, make sure that main power to the unit has been disconnected. Failure to heed this warning could result in personal injury.
To wire the thermostat:
1.Connect the ‘C’ terminal from the 50BV unit to the ‘C’ terminal on the thermostat.
2.Wire the ‘Y1’ and ‘Y2’ terminals from the 50BV unit to the ‘Y1’ and ‘Y2’ terminals, respectively, at the thermostat.
3.Make a connection between the ‘G’ terminal on the unit and the ‘G’ terminal on the thermostat.
4.Attach a wire from the ‘R’ terminal at the unit to the ‘R’ terminal at the thermostat.
5.50BVQ and 50BVV ONLY: If the unit is a heat pump, connect a final wire from terminal ‘O’ on the heat pump unit to the ‘W1/O/B’ terminal at the thermostat. Configure the thermostat for heat pump operation using the installation instructions provided with the thermostat. Set the reversing valve polarity of the thermostat to ‘O’.
See Fig. 24 for typical thermostat wiring.
THERMOSTAT |
|
|
B |
| |
O |
| TYPICAL |
Y2 R W1 Y1 G | C | |
|
| UNIT |
|
| C |
| 24 VAC COMMON | O |
| FAN RELAY | |
|
| |
| COMPRESSOR RELAY | Y1 |
|
| Y2 |
| HEAT PUMP |
|
| 24 VAC RETURN | R |
| 2nd STAGE COMPRESSOR RELAY | G |
|
|
Fig. 24 — Typical Wiring 18 to 30 Ton Units
(Two-Stage Cooling Units)
These units can be controlled using a standard commercial,
For
Finally, verify that transformer phasing is consistent between Modules A and B.
REMOTE CONDENSER FAN CONTACTOR WIR- ING — For units up to 30 tons, one remote condenser is required. Install a
For 40 to 60 ton units, 2 remote condensers are required. Be sure to make piping connections so that compressors 1 and 2 are connected to condenser 1, and compressors 3 and 4 are connect- ed to condenser 2. Use an additional set of NO (normally open) contacts on PR1 to energize FC1 on condenser 1, and a set of NO contacts on PR2 to energize FC1 on condenser 2.
CONTROL WIRING (VAV Only) — The VAV units are de- signed to operate either with a building management system or stand alone (local control).
Carrier Comfort Network® Control Wiring — The CC6400 Control Module connects to the Carrier Comfort Network (CCN) bus in a daisy chain arrangement. Negative pins on each component must be connected to respective negative pins and likewise positive pins on each component must be connected to respective positive pins. The controller signal pins must be wired to the signal ground pins. Wiring connections for CCN must be made at the
At any baud rate (9600, 19200, 38400 baud), the number of controllers is limited to 239 devices maximum. Bus length may not exceed 4000 ft, with no more than 60 total devices on any
NOTE: Carrier device default is 9600 baud.
The CCN communication bus wiring is field supplied and field installed. It consists of shielded