Carrier 50BV020-064 specifications A - Electrical Data - 50BVC,E,J,K,Q

Page 25
Table 9A — Electrical Data — 50BVC,E,J,K,Q

For an unbalanced 3-phase supply voltage, use the follow- ing formula to determine the percent of voltage imbalance:

Percent Voltage Imbalance

=100 x max voltage deviation from average voltage average voltage

Example: Supply voltage is 460-3-60.

AB = 452 V

BC = 464 V

AC = 455 V

Average Voltage = 452 + 464 + 455 3

= 1371 3

= 457

Determine maximum deviation from average voltage:

(AB) 457 – 452 = 5 V

(BC) 464 – 457 = 7 V

(AC) 457 – 455 = 2 V Maximum deviation is 7 V.

Determine percent of voltage imbalance:

% Voltage Imbalance = 100 x 7 = 1.53% 457

This amount of phase imbalance is satisfactory as it is be- low the maximum allowable 2%.

IMPORTANT: If supply voltage phase imbalance is more than 2%, contact the local electric utility com- pany immediately.

POWER WIRING — Properly sized fuses or HACR (Heat- ing, Air Conditioning and Refrigeration) circuit breakers must be installed for branch circuit protection, according to the national and applicable local codes. See unit nameplate and Tables 9A and 9B for maximum overcurrent protection size.

These units are provided with single point, main power supply terminal blocks. Refer to Fig. 2-14 for conduit connec- tion locations. Connect the power leads as indicated on the unit wiring diagrams (found in the Troubleshooting section) and be certain to connect the ground lead to the ground lug in the unit high voltage electrical box. Refer to Tables 9A and 9B for unit electrical data.

Table 9A — Electrical Data — 50BVC,E,J,K,Q

 

 

NOMINAL

VOLTAGE

 

COMPRESSOR

 

INDOOR FAN MOTOR

POWER

DISCONNECT

UNIT SIZE

RANGE

No. 1

No. 2

SUPPLY

SIZE

VOLTAGE

 

 

 

50BVC,E,J,K,Q

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(3 Ph, 60 Hz)

Min

Max

RLA

 

LRA

RLA

 

LRA

Qty

HP

FLA

MCA

MOCP

FLA

 

 

 

 

 

 

 

 

 

(ea)

(ea)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

1.5

5.0

84.0

110

75.8

 

 

208/230

187

253

32.9

 

195

32.9

 

195

2

2

6.4

86.8

110

78.6

 

 

 

 

3

9.0

92.0

110

83.8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

12.2

98.4

110

90.2

 

 

 

 

 

 

 

 

 

 

 

 

1.5

2.5

42.1

50

38.0

 

020

460

414

506

16.5

 

95

16.5

 

95

2

2

3.2

43.5

50

39.4

 

 

 

3

4.5

46.1

50

42.0

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

6.1

49.3

50

45.2

 

 

 

 

 

 

 

 

 

 

 

 

1.5

2.0

34.6

45

31.2

 

 

575

518

633

13.6

 

80

13.6

 

80

2

2

2.0

34.6

45

31.2

 

 

 

 

3

3.6

37.8

45

34.4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

5.4

41.4

45

38.0

 

 

 

 

 

 

 

 

 

 

 

 

2

6.4

88.4

120

80.0

 

 

208/230

187

253

33.6

 

225

33.6

 

225

2

3

9.0

93.6

120

85.2

 

 

 

 

 

 

 

 

 

 

 

 

5

12.2

100.0

120

91.6

 

 

 

 

 

 

 

 

 

 

 

 

2

3.2

48.3

60

43.6

 

024

460

414

506

18.6

 

114

18.6

 

114

2

3

4.5

50.85

60

46.2

 

 

 

 

 

 

 

 

 

 

 

 

5

6.1

54.05

60

49.4

 

 

 

 

 

 

 

 

 

 

 

 

2

2.0

34.6

45

31.2

 

 

575

518

633

13.6

 

80

13.6

 

80

2

3

3.6

37.8

45

34.4

 

 

 

 

 

 

 

 

 

 

 

 

5

5.4

41.4

45

38.0

 

 

208/230

187

253

53.6

 

245

53.6

 

245

2

3

9.0

138.6

190

125.2

 

 

 

 

5

12.2

145.0

190

131.6

 

 

 

 

 

 

 

 

 

 

 

 

 

028

460

414

506

20.7

 

125

20.7

 

125

2

3

4.5

55.6

70

50.4

 

 

 

5

6.1

58.8

70

53.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

575

518

633

16.4

 

100

16.4

 

100

2

3

3.6

44.1

60

40.0

 

 

 

 

5

5.4

47.7

60

43.6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

208/230

187

253

59.1

 

425

59.1

 

425

2

5

12.2

157.4

200

142.6

 

034

460

414

506

26.4

 

187

26.4

 

187

2

5

6.1

71.6

90

65.0

 

 

575

518

633

20.5

 

148

20.5

 

148

2

5

5.4

56.9

70

51.8

 

LEGEND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FLA

Full Load Amps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

HP

Horsepower

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LRA

Locked Rotor Amps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MCA

Minimum Circuit Amps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

MOCP — Maximum Overcurrent Protection

 

 

 

 

 

 

 

 

 

 

 

 

RLA

Rated Load Amps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

25

Image 25
Contents CONTENTS Installation, Start-Upand Service InstructionsSAFETY CONSIDERATIONS GENERAL MAJOR SYSTEM COMPONENTS Constant Volume CV UnitsStep 1 - Complete Pre-InstallationChecks INSTALLATIONTable 2 - Modular Unit Shipping Table a50-7257efFig. 2 - 50BVC,J,Q020-034Dimensions Fig. 3 - 50BVE,K020-034Dimensions a50-8201 Fig. 4 - 50BVT,V,W034 High-BoyDimensionsFig. 5 - 50BVT,V,W034 Low-BoyDimensions Fig. 6 - 50BVT,V,W044-064 High-BoyDimensions Fig. 7 - 50BVT,V,W044-064 Low-BoyDimensions Fig. 8 - 50BVU,X034 High-BoyDimensions Fig. 9 - 50BVU,X034 Low-BoyDimensions Fig. 10 - 50BVU,X044-064 High-BoyDimensions Fig. 11 - 50BVU,X044-064 Low-BoyDimensions a50-7306ef NOTES 1.Dimensions in inches mma50-7307ef NOTES 1.Dimensions in inches mma50-8235 Shipping Weights lbSize 034 Units Size 044-064Units Table 3A - Physical Data - 50BVC,E,J,K,Q Table 3B - Physical Data - 50BVT,U,V,W,X Multiple Fan Units Fig. 15 - Typical Fan Discharge Connections forFig. 16 - Duct Static Pressure Probe a50-7138efP/N 39EK20462 a50-7267efStep 4 - Make Piping Connections Fig. 19 - DHS Limit Switch P/Na50-8253 Fig. 18 - DHS Pressure Limit Location50BVC,J,Q Units Table 5A - Condenser Pressure DropTable 5B - Condenser Pressure Drop 50BVT,V,W Units50BVC,E,J,K,Q Units Table 6A - Hot Water Pressure DropTable 6B - Hot Water Pressure Drop 50BVT,U,V,W,X UnitsTable 7B - Economizer Pressure Drop Curve Step 5 - Complete Electrical Connectionsft wg, 50BVT,U,V,W,X Units a50-7270efTable 9A - Electrical Data - 50BVC,E,J,K,Q Table 9B - Electrical Data - 50BVT,U,V,W,X a50-7272ef Fig. 24 - Typical Wiring 18 to 30 Ton UnitsTwo-StageCooling Units Table 10 - Recommended Cables a50-7273efa50-7164tf Fig. 26 - Field Terminal Blocka50-7275ef Installation Unit Discharge LocationFig. 27 - Modular Unit VAV Control Panel a39-1867tTable 11 - Thermistor Resistance vs Temperature START-UPValues for Supply-AirTemperature Sensor 10 Kilo- ohmTable 13 - Fan Performance - 50BVC,E,Q020 CV Unit Start-UpTable 14 - Fan Performance - 50BVC,E,Q024 Table 15 - Fan Performance - 50BVC,E,Q028 Table 16 - Fan Performance - 50BVC,E,Q034 Table 17 - Fan Performance - 50BVT,U,V034 Table 17 - Fan Performance - 50BVT,U,V034 cont Table 18 - Fan Performance - 50BVT,U,V044 Table 19 - Fan Performance - 50BVT,U,V054 Table 19 - Fan Performance - 50BVT,U,V054 cont Table 20 - Fan Performance - 50BVT,U,V064 Table 20 - Fan Performance - 50BVT,U,V064 cont VAV Unit Start-Up 02-06-04 OMNIZONE VPACFig. 32 - LID a50-7425efFig. 33 - 50BV VFD Display The LID display will show Year Table 22 - Controller Hardware Points Table 21 - Controller Set PointsTable 23 - Software Points Table 24 - Configuration Parameters Unoccupied space or return air temperature demand MAINTENANCE SERVICEFig. 34 - Gravity Flow Method a50-186tfa50-187tf Fig. 35 - Forced Circulation MethodTROUBLESHOOTING Evaporator Fan Performance AdjustmentCharging the System a50-7135tfPOSSIBLE CAUSE PROBLEMPROBLEM Table 28 - Unit TroubleshootingCORRECTION PROCEDURE POSSIBLE CAUSETable 30 - Forcing an Input or Output Table 29 - CV Units LED Diagnostic CodesTable 31 - Clearing a Forced Input or Output Page Page Page Page UNIT WIRING FIELD WIRINGPage WIRE LEGEND FIELD WIRINGa50-7282ef TRANS-1PCB2 J1 FIELD WIRINGUNIT WIRING FIELD WIRINGPCB1 PCB1 FIELD WIRINGLEGEND AND NOTES FOR FIG Catalog No Copyright 2008 Carrier CorporationForm 50BV-3SI 10-08I. PRELIMINARY INFORMATION START-UPCHECKLISTII. PRE-START-UP CONTROLSIII.START-UP