Quinny 65040-AB manual Section IV Operating Procedures, Prior to Starting, Starting the Compressor

Page 24

Section IV - Operating Procedures

Prior to Starting

Starting the Compressor

Stopping the Compressor - Normal Operation

Stopping the Compressor - Emergency

Prior to Starting

!CAUTION

Provisions should be made to have the instruction manual readily available to the operator and maintenance personnel. If the manual becomes illegible or lost, have it replaced immediately. The instruction manual should be read periodically to prevent a serious accident.

Before starting the unit, review Sections II and III of this manual and be certain that all installation requirements have been met and that the purpose and use of each of the controls and all warnings are thoroughly understood. Adhere to the following checklist before placing the compressor into operation:

Remove all loose items and tools from around the compressor.

Check fluid level in the gearbox.

Check the fan and fan mounting for tightness.

Manually rotate the compressor through enough revolutions to be certain there is no mechanical interference.

Ensure that all pressure relief valves are in place and properly sized.

Make sure all panels and guards are in place and securely mounted.

Check fuses, circuit breakers and thermal overloads for proper size.

After all the above conditions have been satisfied close the main power disconnect switch, jog the starter switch button to check the rotation of the compressor

Install the coupling guard.

Check the fan rotation (air should push outward through the enclosure).

Check inlet and discharge water piping for proper connections, adequate supply and open drain.

NOTE

When freezing temperatures are expected before the next start-up, drain all cooling water as follows:

Drain inlet and outlet water lines at the cabinet connections.

Remove drain plugs from fluid cooler and stage one water jacket tube.

Inject compressed air at 15-20 psig into the system to remove the remaining coolant.

Starting the Compressor

Secure all enclosure panels on compressor.

Select the mode of operation and start the compressor.

Watch for excessive vibration, unusual noises, or air/ fluid leaks. If anything unusual develops, stop the compressor immediately and correct the condition.

Control settings have been adjusted at the factory; however, they should be checked during start-up and readjusted, if necessary. Some applications may require a slightly different setting than those provided by the factory (never increase pressure settings beyond factory specifications). Refer to Section VII - Service Adjustments.

Observe compressor operation closely for the first hour of operation and frequently for the next seven hours. Stop and correct any noted problems.

NOTE

If the unit fails to start consult Section IX - Troubleshooting. Do not adjust the unload pressure more than 5 PSIG beyond the full load pressure rating of the machine.

Stopping the Compressor - Normal Operation

Press the shutdown button on the keypad below the main display.

NOTE

It is always a good practice to close the service valve when the compressor is not being used. It will prevent the system’s air pressure from leaking back into the compressor if the check valve leaks or fails.

22

Quincy Compressor® - QSD™

 

 

Image 24
Contents QSD Series Page Table of Contents Section V Maintenance or Service Preparation Standard Warranty Dimensional Data air-cooled Dimensional Data water-cooled Safety Precautions Section I GeneralSafety Alert Symbols Spare Parts Ordering InformationSection II Description General Description Compression Cycle and Air FlowCooling System Lubricating Fluid SystemMoisture Separator Water-cooledCapacity Control System Electrical System Back-up Control Shutdown ConditionsIndicators Safety SensorsMain Power on Light High Discharge Air Temperature LightsSection II Description Section III Installation Moving the Unit to the Installation SiteReceiving LocationPiping Connections Manual Shutoff Valve Piping Fit-upElectrical GuardsWater Flow Water QualityFluid Level Fan RotationSection IV Operating Procedures Prior to StartingStarting the Compressor Stopping the Compressor Normal OperationTemperature Readings Water-cooled Pressure ReadingsStopping the Compressor Emergency Section V Preparing for Maintenance or Service This page Intentionally Left Blank Safety Fluid SpecificationsSection VI Servicing Air Filter Fluid LifePreparation for New Seal Installation Input Shaft SealSeal Installation Airend Sealing SystemSection VII Service Adjustments Pressure SwitchPressure Switch Back-up Operating Mode Adjusting Pressure SwitchThis page Intentionally Left Blank Section Viii Power$ync II Operation Introduction to Power$yncBack-up Mode Operation Do not switch modes with power on the compressorMultiple Machine Operational Mode Auto Dual Time DelaySingle Machine Operational Modes Continuous RunPressure Settings Network Load Delay TimeNetwork Installation Connecting Cable to the Power$ync II Circuit BoardRocker Switch Settings Network Voltage Tests on Power$ync II Systems Network SetupUP/DOWN DEADBAND, F1 EDIT, Enter Return Power-up Displays Start-upSection Viii Power$ync II Operation Compressor in Back-up Mode U19 Memory Failure Contact Your Service RepresentativeDeadband Data Error Press F1 to Clear U19 Data Checksum Error Press F2 to UpdateU19 Data not Initialized Press F2 to Initialize Filter Needs Servicing Please Replace AS Soon AS Possible Start-up Displays Operational DisplaysAdditional Sensors Compressor is StartingCompressor is Unloaded Minutes Left to Shutdown Compressor is UnloadedProgrammed Shutdown Compressor Settings and Maintenance Displays Mode and Pressure DisplaysCompressor Mode of Operation Auto Dual Timed Stop Press F1 Press F2Read Pressure Settings pages 34-35 before Press F1 to change the load and unload pressuresMachine ID Setup Please Wait Network Configuration in ProgressMachine ID for this Compressor Press Enter to Accept Value Before setting or changing a sequence, read Sequence Network DataUP/DOWN POSITION, F1 EDIT, Enter Return UP/DOWN Machine ID, Enter ReturnNetwork Configuration Menu DAY Monday SEQ AbcdDAY Monday SEQ To clear a particular sequence from the memory, press F1 Filter Service Hourmeters Reset Service HourmetersCompressor Hourmeter Menu Compressor Hourmeters Intake Filter HoursPress F1 to Reset Fluid Filter Hours Press Enter to Return Fluid Filter Hours Reset to Press Enter to ReturnPress F1 to Reset Fluid Hours Press Enter to Return Fluid Hours Reset to Press Enter to ReturnCompressor Maintenance Menu Compressor Control Test Time Menu To View Current TimeTo SET Time and Date Time and Date Menu Current Time on this ControlHorsepower Compressor Control Test Menu Unload Valve Test Press F1Unload Press Fluid PressUnit Configuration Date Modem Baud Rate SetupCompressor Diagnostic Menu View Shutdown LOG Network DiagnosticSection Viii Power$ync II Operation ETOL00 FTOL00 Network Connection Data Confidence Indicator is lit, the indicator will remain lit Modem INITIALIZATION** InitF1 to EDIT/ENTER to Accept Value Compressor has Shut Down Emergency Stop Button WAS Pressed Sequence Data Error Press F1 to Clear Schedule Data Error Compressor has Shut Down Take Corrective Action Back-up Mode until all faults have been corrected Inlet Temp Fluid Pressure STG 1 OUT Temp STG 2 in Temp Shutdown Log Messages Emergency Stop PressedMotor Overload STG 2 Discharge RTD Failure Control log has no entries at that point Section IX Troubleshooting Probable Causes Corrective Action Failure to StartSection IX Troubleshooting Unscheduled ShutdownProbable Causes Corrective Action Unscheduled Shutdown Frequent Air Cleaner Clogging High Discharge Air TemperatureProbable Causes Corrective Action Low Air Delivery Frequent Fluid Filter CloggingCompressor does not Unload when there is no Air Demand Too Rapid Cycling Between Load and Unload Pressure Relief Valve Exhausting Excessive Fluid in Buffing Air Vent BowlsWater in Buffing Air Vent Bowls Excessive Fluid in Gearbox Vent BowlLow Delivery Pressure High Interstage PressureErroneous Displays Microprocessor Will Not Display MessagesSection X- Maintenance Schedule Interval ActionDaily Operating Record Quincy Compressor QSD Quincy Compressor QSD