Quinny 65040-AB manual Back-up Mode until all faults have been corrected

Page 64

Section VIII - Power$ync IIOperation

A potentially serious condition could exist if the main motor starter does not respond to the controller’s signal to disengage. The cooling fan motor will not stop as long as the main motor is running so that cooling can be maintained in the event that the starter does not respond to a signal to perform a normal shutdown. If the starter does not respond to a signal to disengage in an emergency, an unsafe condition may result. The Power$ync IIcontroller will flash all the LED safety and warning lights to draw attention to this situation, should it occur. It will also display one of the following messages, depending on the unit configuration:

NOTICE! ********* NOTICE!

COMPRESSOR MAIN CONTACTOR

IS NOT DISENGAGING

PULL MAIN DISCONNECT

NOTICE!

REMOTE STARTER

IS NOT DISENGAGING

PULL MAIN DISCONNECT

Pull the main disconnect to cut the power to the compressor. Determine the reason that the starter is not responding, correct the problem and repeat the start-up procedure. As with other faults, loose wiring should be the first item checked. If all wiring to and from the relay board is tight and wiring to the starter auxiliary contacts is tight, a faulty starter may be the problem. Determine the original cause for the shutdown. If the unit was being stopped because there was no air demand, it can be restarted after the starter problem is corrected. If the unit was being stopped due to a detected fault, correct the fault before continuing operation. Do not attempt to run the compressor

in Back-up Mode until all faults have been corrected.

In addition to the sensor check at power-up, the

Power$ync IIcontroller continually checks sensors for faults. If the controller receives a signal that is outside its expected range or fails to receive a signal, one of the following messages will be displayed depending on the sensor affected:

NOTICE!

COMPRESSOR HAS SHUT DOWN

DISCHARGE RTD FAULTY OR DISCONNECTED

REFER TO YOUR SERVICE MANUAL

NOTICE!

COMPRESSOR HAS SHUT DOWN

STG 2 OUT RTD FAULTY OR DISCONNECTED

REFER TO YOUR SERVICE MANUAL

NOTICE!

COMPRESSOR HAS SHUT DOWN

STG 2 IN RTD FAULTY OR DISCONNECTED

REFER TO YOUR SERVICE MANUAL

NOTICE!

COMPRESSOR HAS SHUT DOWN

STG 1 OUT RTD FAULTY OR DISCONNECTED

REFER TO YOUR SERVICE MANUAL

NOTICE!

COMPRESSOR HAS SHUT DOWN

PACKAGE PRESSURE SENSOR FAULTY REFER TO YOUR SERVICE MANUAL

NOTICE!

COMPRESSOR HAS SHUT DOWN

STG 2 OUT PRESSURE SENSOR FAULTY

REFER TO YOUR SERVICE MANUAL

NOTICE!

COMPRESSOR HAS SHUT DOWN FLUID PRESSURE SENSOR FAULTY REFER TO YOUR SERVICE MANUAL

NOTICE!

COMPRESSOR HAS SHUT DOWN

STG 1 OUT PRESSURE SENSOR FAULTY

REFER TO YOUR SERVICE MANUAL

There are two probable causes for these displays: a disconnected wire or a failed sensor or transducer. Disconnect the main power supply to the compressor and check the connection at the temperature probe and at the controller. If a loose connection is found, correct the problem and repeat the start-up procedure. If all connections are tight, the problem is a failed sensor or transducer. If a spare part is available, replace and repeat the start-up process. If no spare part is available, contact a service representative. The compressor can be operated in Back-up Mode.

62

Quincy Compressor® - QSD™

 

 

Image 64
Contents QSD Series Page Table of Contents Section V Maintenance or Service Preparation Standard Warranty Dimensional Data air-cooled Dimensional Data water-cooled Safety Precautions Section I GeneralSafety Alert Symbols Spare Parts Ordering InformationSection II Description General Description Compression Cycle and Air FlowCooling System Lubricating Fluid SystemMoisture Separator Water-cooledCapacity Control System Electrical System Back-up Control Shutdown ConditionsIndicators Safety SensorsMain Power on Light High Discharge Air Temperature LightsSection II Description Section III Installation Moving the Unit to the Installation SiteReceiving LocationPiping Connections Manual Shutoff Valve Piping Fit-upElectrical GuardsWater Flow Water QualityFluid Level Fan RotationSection IV Operating Procedures Prior to StartingStarting the Compressor Stopping the Compressor Normal OperationPressure Readings Temperature Readings Water-cooledStopping the Compressor Emergency Section V Preparing for Maintenance or Service This page Intentionally Left Blank Fluid Specifications SafetySection VI Servicing Air Filter Fluid LifePreparation for New Seal Installation Input Shaft SealSeal Installation Airend Sealing SystemSection VII Service Adjustments Pressure SwitchPressure Switch Back-up Operating Mode Adjusting Pressure SwitchThis page Intentionally Left Blank Section Viii Power$ync II Operation Introduction to Power$yncBack-up Mode Operation Do not switch modes with power on the compressorMultiple Machine Operational Mode Auto Dual Time DelaySingle Machine Operational Modes Continuous RunPressure Settings Network Load Delay TimeNetwork Installation Connecting Cable to the Power$ync II Circuit BoardRocker Switch Settings Network Setup Network Voltage Tests on Power$ync II SystemsUP/DOWN DEADBAND, F1 EDIT, Enter Return Power-up Displays Start-upSection Viii Power$ync II Operation Compressor in Back-up Mode U19 Memory Failure Contact Your Service RepresentativeU19 Data Checksum Error Press F2 to Update Deadband Data Error Press F1 to ClearU19 Data not Initialized Press F2 to Initialize Filter Needs Servicing Please Replace AS Soon AS Possible Start-up Displays Operational DisplaysAdditional Sensors Compressor is StartingCompressor is Unloaded Compressor is Unloaded Minutes Left to ShutdownProgrammed Shutdown Compressor Settings and Maintenance Displays Mode and Pressure DisplaysCompressor Mode of Operation Auto Dual Timed Stop Press F1 Press F2Read Pressure Settings pages 34-35 before Press F1 to change the load and unload pressuresPlease Wait Network Configuration in Progress Machine ID SetupMachine ID for this Compressor Press Enter to Accept Value Before setting or changing a sequence, read Sequence Network DataUP/DOWN POSITION, F1 EDIT, Enter Return UP/DOWN Machine ID, Enter ReturnDAY Monday SEQ Abcd Network Configuration MenuDAY Monday SEQ To clear a particular sequence from the memory, press F1 Filter Service Hourmeters Reset Service HourmetersCompressor Hourmeter Menu Compressor Hourmeters Intake Filter HoursPress F1 to Reset Fluid Filter Hours Press Enter to Return Fluid Filter Hours Reset to Press Enter to ReturnPress F1 to Reset Fluid Hours Press Enter to Return Fluid Hours Reset to Press Enter to ReturnCompressor Maintenance Menu Compressor Control Test Time Menu To View Current TimeTo SET Time and Date Time and Date Menu Current Time on this ControlHorsepower Compressor Control Test Menu Unload Valve Test Press F1Unload Press Fluid PressUnit Configuration Date Modem Baud Rate SetupCompressor Diagnostic Menu View Shutdown LOG Network DiagnosticSection Viii Power$ync II Operation ETOL00 FTOL00 Network Connection Data Confidence Modem INITIALIZATION** Init Indicator is lit, the indicator will remain litF1 to EDIT/ENTER to Accept Value Compressor has Shut Down Emergency Stop Button WAS Pressed Sequence Data Error Press F1 to Clear Schedule Data Error Compressor has Shut Down Take Corrective Action Back-up Mode until all faults have been corrected Inlet Temp Fluid Pressure STG 1 OUT Temp STG 2 in Temp Shutdown Log Messages Emergency Stop PressedMotor Overload STG 2 Discharge RTD Failure Control log has no entries at that point Section IX Troubleshooting Probable Causes Corrective Action Failure to StartSection IX Troubleshooting Unscheduled ShutdownProbable Causes Corrective Action Unscheduled Shutdown Frequent Air Cleaner Clogging High Discharge Air TemperatureProbable Causes Corrective Action Low Air Delivery Frequent Fluid Filter CloggingCompressor does not Unload when there is no Air Demand Too Rapid Cycling Between Load and Unload Pressure Relief Valve Exhausting Excessive Fluid in Buffing Air Vent BowlsWater in Buffing Air Vent Bowls Excessive Fluid in Gearbox Vent BowlLow Delivery Pressure High Interstage PressureErroneous Displays Microprocessor Will Not Display MessagesSection X- Maintenance Schedule Interval ActionDaily Operating Record Quincy Compressor QSD Quincy Compressor QSD