Quinny 65040-AB manual Inlet Temp

Page 65

Section VIII - Power$ync IIOperation

The Power$ync IIcontroller also performs continuing checks on itself while the compressor is in operation. If it detects a fault, it will display one of the following two messages:

NOTICE!

COMPRESSOR HAS SHUT DOWN

**NOTICE** COMMUNICATION FAILURE

REFER TO YOUR SERVICE MANUAL

The Power$ync IIcontroller continually checks its communication pathways between boards, even when no pertinent information is being passed. This is done to confirm that all communication pathways are functioning and ready to accept and process signals. If the controller fails to receive the proper response to its attempt to confirm that the communication pathways are functioning properly, it will try two more times and then shut the compressor down. Call your local service representative to correct this problem. The compressor can be operated in Back-up Mode.

PKG. DISCH TEMP_______

COMPRESSOR HAS SHUT DOWN

**NOTICE** HIGH DISCHARGE TEMPERATURE

TAKE CORRECTIVE ACTION

This display indicates that the controller has detected a high temperature condition at the temperature probe installed in the discharge line from the package to the plant air. This could be the result of a mechanical failure or it could be the result of low coolant flow. This is a serious condition. Do not attempt to restart the compressor until the cause of the shutdown has been determined and corrected. The compressor will not restart as long as the high temperature condition exists. Call your service representative if you cannot determine and correct the cause of the shutdown.

Power$ync IIis connected to and monitors the state of the motor starter and overload. Should the controller detect a fault condition or detect that a component is not responding to commands, it will illuminate the appropriate LED on the schematic and display one of the following messages:

2 INLET TEMP ______

COMPRESSOR HAS SHUT DOWN NOTICE! HIGH STAGE 2 INLET TEMP TAKE CORRECTIVE ACTION

2 DISCH TEMP ______

COMPRESSOR HAS SHUT DOWN

NOTICE! HIGH STAGE 2 DISCH TEMP

TAKE CORRECTIVE ACTION

1 DISCH TEMP ______

COMPRESSOR HAS SHUT DOWN

NOTICE! HIGH STAGE 1 DISCH TEMP

TAKE CORRECTIVE ACTION

High temperature shutdowns could be caused by high ambient temperatures. Verify that the ambient temperature is within the operating limits of the compressor. A failed or broken vent fan could also cause high temperatures. For water-cooled units, the water temperature or flow might be outside the operating limits of the compressor or the cooler might need cleaning. For air-cooled units, the air flow might be blocked, the fan or fan motor may have failed, the thermal mixing valve may have failed or the cooler may need cleaning. High Stage 2 discharge temperature can be caused by a high delta-pressure across stage 2. This could be caused by a blowdown valve failure.

FLUID PRESSURE ______

COMPRESSOR HAS SHUT DOWN

NOTICE! LOW FLUID PRESSURE

TAKE CORRECTIVE ACTION

Low fluid pressure may be caused by a failed fluid pump or regulating valve.

Quincy Compressor® - QSD™

63

 

 

Image 65
Contents QSD Series Page Table of Contents Section V Maintenance or Service Preparation Standard Warranty Dimensional Data air-cooled Dimensional Data water-cooled Section I General Safety PrecautionsSpare Parts Ordering Information Safety Alert SymbolsSection II Description Compression Cycle and Air Flow General DescriptionLubricating Fluid System Cooling SystemMoisture Separator Water-cooledCapacity Control System Electrical System Shutdown Conditions Back-up ControlSafety Sensors IndicatorsMain Power on Light High Discharge Air Temperature LightsSection II Description Moving the Unit to the Installation Site Section III InstallationReceiving LocationPiping Connections Piping Fit-up Manual Shutoff ValveGuards ElectricalWater Quality Water FlowFan Rotation Fluid LevelPrior to Starting Section IV Operating ProceduresStarting the Compressor Stopping the Compressor Normal OperationStopping the Compressor Emergency Temperature Readings Water-cooledPressure Readings Section V Preparing for Maintenance or Service This page Intentionally Left Blank Section VI Servicing SafetyFluid Specifications Fluid Life Air FilterInput Shaft Seal Preparation for New Seal InstallationAirend Sealing System Seal InstallationPressure Switch Section VII Service AdjustmentsPressure Switch Back-up Operating Mode Adjusting Pressure SwitchThis page Intentionally Left Blank Introduction to Power$ync Section Viii Power$ync II OperationBack-up Mode Operation Do not switch modes with power on the compressorAuto Dual Time Delay Multiple Machine Operational ModeSingle Machine Operational Modes Continuous RunNetwork Load Delay Time Pressure SettingsConnecting Cable to the Power$ync II Circuit Board Network InstallationRocker Switch Settings UP/DOWN DEADBAND, F1 EDIT, Enter Return Network Voltage Tests on Power$ync II SystemsNetwork Setup Start-up Power-up DisplaysSection Viii Power$ync II Operation U19 Memory Failure Contact Your Service Representative Compressor in Back-up ModeU19 Data not Initialized Press F2 to Initialize Deadband Data Error Press F1 to ClearU19 Data Checksum Error Press F2 to Update Filter Needs Servicing Please Replace AS Soon AS Possible Operational Displays Start-up DisplaysAdditional Sensors Compressor is StartingProgrammed Shutdown Compressor is Unloaded Minutes Left to ShutdownCompressor is Unloaded Mode and Pressure Displays Compressor Settings and Maintenance DisplaysCompressor Mode of Operation Auto Dual Timed Stop Press F1 Press F2Press F1 to change the load and unload pressures Read Pressure Settings pages 34-35 beforeMachine ID for this Compressor Press Enter to Accept Value Machine ID SetupPlease Wait Network Configuration in Progress Sequence Network Data Before setting or changing a sequence, readUP/DOWN POSITION, F1 EDIT, Enter Return UP/DOWN Machine ID, Enter ReturnDAY Monday SEQ Network Configuration MenuDAY Monday SEQ Abcd To clear a particular sequence from the memory, press F1 Reset Service Hourmeters Filter Service HourmetersCompressor Hourmeter Menu Compressor Hourmeters Intake Filter HoursFluid Filter Hours Reset to Press Enter to Return Press F1 to Reset Fluid Filter Hours Press Enter to ReturnPress F1 to Reset Fluid Hours Press Enter to Return Fluid Hours Reset to Press Enter to ReturnTime Menu To View Current Time Compressor Maintenance Menu Compressor Control TestTo SET Time and Date Time and Date Menu Current Time on this ControlCompressor Control Test Menu Unload Valve Test Press F1 HorsepowerUnload Press Fluid PressModem Baud Rate Setup Unit Configuration DateCompressor Diagnostic Menu View Shutdown LOG Network DiagnosticSection Viii Power$ync II Operation ETOL00 FTOL00 Network Connection Data Confidence F1 to EDIT/ENTER to Accept Value Indicator is lit, the indicator will remain litModem INITIALIZATION** Init Compressor has Shut Down Emergency Stop Button WAS Pressed Sequence Data Error Press F1 to Clear Schedule Data Error Compressor has Shut Down Take Corrective Action Back-up Mode until all faults have been corrected Inlet Temp Fluid Pressure STG 1 OUT Temp STG 2 in Temp Emergency Stop Pressed Shutdown Log MessagesMotor Overload STG 2 Discharge RTD Failure Control log has no entries at that point Probable Causes Corrective Action Failure to Start Section IX TroubleshootingUnscheduled Shutdown Section IX TroubleshootingProbable Causes Corrective Action Unscheduled Shutdown High Discharge Air Temperature Frequent Air Cleaner CloggingProbable Causes Corrective Action Low Air Delivery Frequent Fluid Filter CloggingCompressor does not Unload when there is no Air Demand Too Rapid Cycling Between Load and Unload Excessive Fluid in Buffing Air Vent Bowls Pressure Relief Valve ExhaustingWater in Buffing Air Vent Bowls Excessive Fluid in Gearbox Vent BowlHigh Interstage Pressure Low Delivery PressureMicroprocessor Will Not Display Messages Erroneous DisplaysInterval Action Section X- Maintenance ScheduleDaily Operating Record Quincy Compressor QSD Quincy Compressor QSD