Honeywell R0512 manual Excel 50/100/500/600/800

Page 1

Excel 50/100/500/600/800

CONTROLLERS

HONEYWELL EXCEL 5000 OPEN SYSTEM

SOFTWARE DESCRIPTION

® U.S. Registered Trademark

EN2B-0092GE51 R0512

Copyright © 2012 Honeywell Inc. • All rights reserved

 

Image 1
Contents Excel 50/100/500/600/800 Excel 50/100/500/600/800 Contents Value Hysteresis Trend Cycle SubtypeValue Write Protection Excel 50/100/500/600/800 Change Revision OverviewSection Sensor Offset added System Overview Overview Programming Physical Datapoints DatapointsPseudo Datapoints Flexible DatapointsData Points Global DatapointsMapped Datapoints V2.04.xx or higher Acknowledge Alarm V2.04.xx or higher Access LevelAttributes Active State Excel Active State prior toStatus text Alarm Suppression Alarm DelayAlarm Status prior to Alarm Type Alarm Status V2.04.xx or higherAlarm Definition Interval Counter Alarm StatusAttributes Delay Time Switching Down Delay Time Switching UpCycle Count High/Low Alarm/Warning Limits Feedback DelayDescriptors Engineering UnitHours Run Hours Since ServicedHours Run Log Hysteresis Alarm HysteresisTrend Hysteresis Example of alarm hysteresisBroadcast Hysteresis Intrinsic Hysteresis for Analog Input SignalsInterval Count Input/Output Status Text V2.04.xx or higherInterval Limit CharacteristicPull-Up Resistor Handling Configured Activated Or low By DIP Diagram High By @Last Change By plug-in For DI on AI ImpedanceMaintenance Alarm LED Mode XF823x, XFL823x, and XFx830x modulesManual Value Normally Open/Normally Closed V2.04.xx or higher Network Variable V2.04.xx or higherOperating Mode Off PhaseMotor Run Time Remote value Manual valueResulting value Output Type Point AlarmsSubtype Remote value Resulting ValuePulse Duration Safety Position XFx822x, XFx824x, and XFx830x modulesScaling Factor Sensor Offset Switching DownSuppress Point Switching down Switching down behavior Switch-On CounterTechnical Address Trend LoggingTrend Cycle Value HysteresisRoom Temp.1.10 ValueNumber of technical addresses for flexible datapoints Flexible datapoint Number of technical addressesWrite Protection List of Datapoint Attributes Attributes Attributes Structure Time ProgramsIndividual Time Programs Daily ProgramAnnual Program Weekly ProgramSpecial Day List Generating a Time ProgramToday Function Time Programs Prior to Alarm Handling04.x System alarms System AlarmsAlarm Alarm text Cond Cause/reason English Code # BenefitsAlarm Handling Warm Start With corresponding function of XBS or XL-Online System Alarms Suppression V .04.xx or higher Alarms Sent across the System Bus User Program AlarmsData Storage Alarm Handling Distributed I/O testing V2.04.xx or higher Test ModeCommunication System BusBus Initialization AccessBus Communication Runtime SynchronizationNew Bus Devices Initialization of Distributed I/O ModulesNetwork-Wide Controller Time Synchronization Excel IRC PC CommunicationRemote Communication Point RefreshingRemote Modem Connection General Remote Trending dial-upController Firmware 2.03.xx and Higher Controller Firmware 2.04.xx and HigherFor all other controllers equipped with Flash Eproms ExcelHBS Country and Language Settings Customize Windows Default Regional and Language SettingsMiscelleanous XL40A2MMI Care Country Controllers with Internal Text MMI XL Online CLTG00MMI CentraLine Country and Language SettingsGraphic MMI CLMMI00N2x Tiger Controllers with Hex Dec Char Unicode ISO/IEC 10646-12000 Character Name Latin Small Letter L Latin Small Letter O with Diaeresis Character Settings Eastern Europe Latin Small Letter D Latin Small Letter U with Ring Above Latin Capital Letter L with Acute Character Settings Turkey Miscelleanous Latin Small Letter D Latin Capital Letter I with DOT Above Latin Capital Letter G with Breve Procedure 1. In Windows, click StartSettingsControl panel Miscelleanous Miscelleanous Miscelleanous Miscelleanous Index ModemfaqAutomation and Control Solutions