ALARM HANDLING |
|
| EXCEL 50/100/500/600/800 |
| |
|
|
|
|
| |
Alarm | alarm text | cond. | cause/reason |
| |
no. | English) | code # |
|
|
|
|
| 46 | 1) | No RACL program. |
|
48 | Part applic. miss | 47 | 2) | No parameter file. |
|
48 | 3) | No Z register file. |
| ||
|
| 49 | 4) | No T register file. |
|
|
| 52 | 5) | No datapoint description. |
|
|
| 26 | 1) | Submodule does not exist. |
|
|
| 27 | 2) | Parameter file missing. |
|
|
| 28 | 3) | No M0 module. |
|
49 | RACL environ fault 31 | 4) Invalid SKIP destination. |
345) Info points STARTUP, SHUTDOWN, or EXECUTING_STOPPED are missing or
6) During RACL start datapoint contains errors.
1 | 7) freely programmable application loaded into Excel 50 controller (system alarm | |
parameters set to 0,0,0). | ||
|
50 | INIT div. by zero | 14 | Reason of new start: Division by zero. | |
51 | INIT under OpCode | 15 | Reason of new start: the system software contains an undefined Operation Code. | |
52 | Power failure | 16 | Reason of new start: power failure, data in RAM ok. | |
|
|
|
| |
53 | Link Config Bad | - | Xlink alarm. | |
54 | I/O board missing | 19 | The required configuration contains at least one module which is not included in the | |
hardware configuration. | ||||
|
|
| ||
55 | Unused I/O board | 18 | The hardware configuration contains at least one module that is not needed (can be taken | |
out). | ||||
|
|
| ||
|
|
| 1) Hardware Configuration file (.kfx file) not complete loaded. | |
|
|
| 2) Different modules are plugged under the same address (set using the rotary HEX | |
56 | HW Config. failure | 20 | switch) in the required configuration and in the hardware configuration. | |
|
|
| 3) An application containing | |
|
|
| hardware does not have the 3120E5 Neuron® chip. | |
57 | Wrong version no. | 21 | The version number of the application files and the configuration file are not the same. | |
|
|
|
| |
58 | Totalizer overflow | 5 | Overflow operation hours counter, point value of counters and interval impulse counter. | |
59 | Maintenance alarm | 7 | Course of a service interval for digital points or course or the message/calling interval for | |
counters. Call intervals for counters. | ||||
|
|
| ||
60 | Undef. RACL input | 62 | Undefined RACL errors. | |
|
|
| The loaded application contains too many remote points. An application with more than 46 | |
61 | Too many Globals | 63 | NVs has been rejected for download into an Excel 50 freely programmable controller | |
|
|
| located on a LONWORKS network. | |
62 | 64 | Communication defect/disturbance between Excel 500 and | ||
modem device in controller has gotten a | ||||
|
|
| ||
63 | No Globals | 9 | No remote storage; the remote controller has no storage left for requested remote points. | |
memory | ||||
|
|
| ||
64 | Global pnt missing | 10 | The user address of the remote point was not found in the remote controller. | |
|
|
|
| |
65 | Glob Pnt Occupied | 11 | A remote output to a remote controller is already assigned to another controller. | |
66 | CPU stopped | 12 | The remote controller is in stopped condition. | |
67 | CPU not available | 13 | The remote controller is switched off or does not respond to | |
|
|
|
| |
68 | Init. actuators | 65 | Floating outputs | |
69 | WARM START | 66 | Reason of new start: watchdog. | |
70 | COLD START | 67 | Reason of new start: power failure, data in RAM destroyed. | |
|
|
|
| |
71 | Point in manual | 68 | When falling back to password level 3 there are still points in manual override. | |
|
|
|
| |
72 | Report too large | 69 | Not enough space in the report file for initialization. | |
73 | XI 581 required | 70 | After a download, an entry is demanded in the initializing phase of the ASPECD | |
application. This can happen only with XI581 emulation. | ||||
|
|
| ||
74 | New appli. loaded | 74 | Download of a new application part or entire application. | |
|
|
|
|