Honeywell R0512 manual Warm Start

Page 50

ALARM HANDLING

 

 

EXCEL 50/100/500/600/800

 

 

 

 

 

 

Alarm

alarm text

cond.

cause/reason

 

no.

English)

code #

 

 

 

 

 

46

1)

No RACL program.

 

48

Part applic. miss

47

2)

No parameter file.

 

48

3)

No Z register file.

 

 

 

49

4)

No T register file.

 

 

 

52

5)

No datapoint description.

 

 

 

26

1)

Submodule does not exist.

 

 

 

27

2)

Parameter file missing.

 

 

 

28

3)

No M0 module.

 

49

RACL environ fault 31

4) Invalid SKIP destination.

345) Info points STARTUP, SHUTDOWN, or EXECUTING_STOPPED are missing or

6) During RACL start datapoint contains errors.

1

7) freely programmable application loaded into Excel 50 controller (system alarm

parameters set to 0,0,0).

 

50

INIT div. by zero

14

Reason of new start: Division by zero.

51

INIT under OpCode

15

Reason of new start: the system software contains an undefined Operation Code.

52

Power failure

16

Reason of new start: power failure, data in RAM ok.

 

 

 

 

53

Link Config Bad

-

Xlink alarm.

54

I/O board missing

19

The required configuration contains at least one module which is not included in the

hardware configuration.

 

 

 

55

Unused I/O board

18

The hardware configuration contains at least one module that is not needed (can be taken

out).

 

 

 

 

 

 

1) Hardware Configuration file (.kfx file) not complete loaded.

 

 

 

2) Different modules are plugged under the same address (set using the rotary HEX

56

HW Config. failure

20

switch) in the required configuration and in the hardware configuration.

 

 

 

3) An application containing NV-mapping is rejected by the target controller because the

 

 

 

hardware does not have the 3120E5 Neuron® chip.

57

Wrong version no.

21

The version number of the application files and the configuration file are not the same.

 

 

 

 

58

Totalizer overflow

5

Overflow operation hours counter, point value of counters and interval impulse counter.

59

Maintenance alarm

7

Course of a service interval for digital points or course or the message/calling interval for

counters. Call intervals for counters.

 

 

 

60

Undef. RACL input

62

Undefined RACL errors.

 

 

 

The loaded application contains too many remote points. An application with more than 46

61

Too many Globals

63

NVs has been rejected for download into an Excel 50 freely programmable controller

 

 

 

located on a LONWORKS network.

62

C-Bus error

64

Communication defect/disturbance between Excel 500 and C-Bus submodule. Logical

modem device in controller has gotten a C-Bus # already in use for a C-Bus controller.

 

 

 

63

No Globals

9

No remote storage; the remote controller has no storage left for requested remote points.

memory

 

 

 

64

Global pnt missing

10

The user address of the remote point was not found in the remote controller.

 

 

 

 

65

Glob Pnt Occupied

11

A remote output to a remote controller is already assigned to another controller.

66

CPU stopped

12

The remote controller is in stopped condition.

67

CPU not available

13

The remote controller is switched off or does not respond to C-Bus communication.

 

 

 

 

68

Init. actuators

65

Floating outputs (3-position outputs) are synchronized.

69

WARM START

66

Reason of new start: watchdog.

70

COLD START

67

Reason of new start: power failure, data in RAM destroyed.

 

 

 

 

71

Point in manual

68

When falling back to password level 3 there are still points in manual override.

 

 

 

 

72

Report too large

69

Not enough space in the report file for initialization.

73

XI 581 required

70

After a download, an entry is demanded in the initializing phase of the ASPECD

application. This can happen only with XI581 emulation.

 

 

 

74

New appli. loaded

74

Download of a new application part or entire application.

 

 

 

 

EN2B-0092GE51 R0512

48

Image 50
Contents Excel 50/100/500/600/800 Excel 50/100/500/600/800 Contents Subtype Value Hysteresis Trend CycleValue Write Protection Excel 50/100/500/600/800 Section Sensor Offset added Revision OverviewChange System Overview Overview Programming Datapoints Physical DatapointsFlexible Datapoints Pseudo DatapointsGlobal Datapoints Data PointsMapped Datapoints V2.04.xx or higher Attributes Access LevelAcknowledge Alarm V2.04.xx or higher Status text Active State prior toActive State Excel Alarm Status prior to Alarm DelayAlarm Suppression Alarm Definition Alarm Status V2.04.xx or higherAlarm Type Interval Counter Alarm StatusAttributes Cycle Count Delay Time Switching UpDelay Time Switching Down Descriptors Feedback DelayHigh/Low Alarm/Warning Limits Engineering UnitHours Run Log Hours Since ServicedHours Run Alarm Hysteresis HysteresisExample of alarm hysteresis Trend HysteresisIntrinsic Hysteresis for Analog Input Signals Broadcast HysteresisInput/Output Status Text V2.04.xx or higher Interval CountCharacteristic Interval LimitLast Change Configured Activated Or low By DIP Diagram High By @Pull-Up Resistor Handling By plug-in For DI on AI ImpedanceManual Value LED Mode XF823x, XFL823x, and XFx830x modulesMaintenance Alarm Network Variable V2.04.xx or higher Normally Open/Normally Closed V2.04.xx or higherMotor Run Time Off PhaseOperating Mode Resulting value Manual valueRemote value Subtype Point AlarmsOutput Type Remote value Resulting ValueScaling Factor Safety Position XFx822x, XFx824x, and XFx830x modulesPulse Duration Suppress Point Switching DownSensor Offset Technical Address Switch-On CounterSwitching down Switching down behavior Trend LoggingValue Hysteresis Trend CycleNumber of technical addresses for flexible datapoints ValueRoom Temp.1.10 Flexible datapoint Number of technical addressesWrite Protection List of Datapoint Attributes Attributes Attributes Individual Time Programs Time ProgramsStructure Daily ProgramWeekly Program Annual ProgramToday Function Generating a Time ProgramSpecial Day List Time Programs 04.x Alarm HandlingPrior to Alarm Alarm text Cond Cause/reason English Code # System AlarmsSystem alarms BenefitsAlarm Handling Warm Start With corresponding function of XBS or XL-Online System Alarms Suppression V .04.xx or higher Data Storage User Program AlarmsAlarms Sent across the System Bus Alarm Handling Communication Test ModeDistributed I/O testing V2.04.xx or higher System BusBus Communication AccessBus Initialization Runtime SynchronizationNetwork-Wide Controller Time Synchronization Initialization of Distributed I/O ModulesNew Bus Devices Remote Communication PC CommunicationExcel IRC Point RefreshingRemote Modem Connection Controller Firmware 2.03.xx and Higher Remote Trending dial-upGeneral Controller Firmware 2.04.xx and HigherExcel For all other controllers equipped with Flash EpromsMiscelleanous Customize Windows Default Regional and Language SettingsHBS Country and Language Settings XL40A2MMI Care Country Controllers with Internal Text MMI XL Online CentraLine Country and Language Settings CLTG00MMIGraphic MMI CLMMI00N2x Tiger Controllers with Hex Dec Char Unicode ISO/IEC 10646-12000 Character Name Latin Small Letter L Latin Small Letter O with Diaeresis Character Settings Eastern Europe Latin Small Letter D Latin Small Letter U with Ring Above Latin Capital Letter L with Acute Character Settings Turkey Miscelleanous Latin Small Letter D Latin Capital Letter I with DOT Above Latin Capital Letter G with Breve Procedure 1. In Windows, click StartSettingsControl panel Miscelleanous Miscelleanous Miscelleanous Miscelleanous Modemfaq IndexAutomation and Control Solutions