Page 31

EXCEL 50/100/500/600/800

ATTRIBUTES

Motor Run Time

Time to open / time to close For actuators controlled via a three-position output, two values (time to open / time to close) can be entered in the attribute “Motor Run Time”. This attribute defines the time required by the actuator to change from the “Open” to the “Closed” state, and vice versa.

If no value is entered for the “Time to Closed” motor run time, then the “Time to Open” motor run time is assumed automatically. In the case of the motor run-on time, when reversing directions, 1% of the “Time to Open” motor run time is added to the calculated time.

The three-position output relay energizes when the calculated run time reaches 500 ms. The stated run time always amounts to 500 ms or a multiple thereof. A calculated run time of, for instance, 1215 ms results in an actual run time of 1000 ms.

CAUTION

Regarding motor run time, the behavior of controllers with OS < 2.06.05 engineered using CARE 4 differs significantly from controllers with OS

2.06.05and higher engineered using CARE 7 and higher. See also section “Controller OS 2.06 usage and functionality in CARE 4 and CARE – XL500 7.01.02” in Excel CARE – User Guide (EN2B-0182GE51).

Off Phase

Fig. 16. Off phase

The attribute "Off Phase" is used in conjunction with flexible datapoints of the type "feedback". It defines the duration of the OFF phase on switching down. It is of relevance only if the attribute “Switching Down” is set to 0, i.e. if OFF phases are selected on switching down.

Range:

0 to 255s

Default value: 10s

Resolution: 1s

The OFF phase has to be defined for devices with large inertia, such as fans.

Operating Mode

The attribute "Operating Mode" enables the user to switch between manual and automatic operation.

Automatic Under automatic operation, the controller processes the values at the inputs, for instance from temperature sensors. For outputs, under automatic operation, the status shown by the user/time switch program is adopted, e.g., "Heating circuit pump off".

29

EN2B-0092GE51 R0512

Image 31
Contents Excel 50/100/500/600/800 Excel 50/100/500/600/800 Contents Value Hysteresis Trend Cycle SubtypeValue Write Protection Excel 50/100/500/600/800 Change Revision OverviewSection Sensor Offset added System Overview Overview Programming Physical Datapoints DatapointsPseudo Datapoints Flexible DatapointsData Points Global DatapointsMapped Datapoints V2.04.xx or higher Acknowledge Alarm V2.04.xx or higher Access LevelAttributes Active State Excel Active State prior toStatus text Alarm Suppression Alarm DelayAlarm Status prior to Interval Counter Alarm Status Alarm Status V2.04.xx or higherAlarm Type Alarm DefinitionAttributes Delay Time Switching Down Delay Time Switching UpCycle Count Engineering Unit Feedback DelayHigh/Low Alarm/Warning Limits DescriptorsHours Run Hours Since ServicedHours Run Log Hysteresis Alarm HysteresisTrend Hysteresis Example of alarm hysteresisBroadcast Hysteresis Intrinsic Hysteresis for Analog Input SignalsInterval Count Input/Output Status Text V2.04.xx or higherInterval Limit CharacteristicBy plug-in For DI on AI Impedance Configured Activated Or low By DIP Diagram High By @Pull-Up Resistor Handling Last ChangeMaintenance Alarm LED Mode XF823x, XFL823x, and XFx830x modulesManual Value Normally Open/Normally Closed V2.04.xx or higher Network Variable V2.04.xx or higherOperating Mode Off PhaseMotor Run Time Remote value Manual valueResulting value Remote value Resulting Value Point AlarmsOutput Type SubtypePulse Duration Safety Position XFx822x, XFx824x, and XFx830x modulesScaling Factor Sensor Offset Switching DownSuppress Point Trend Logging Switch-On CounterSwitching down Switching down behavior Technical AddressTrend Cycle Value HysteresisFlexible datapoint Number of technical addresses ValueRoom Temp.1.10 Number of technical addresses for flexible datapointsWrite Protection List of Datapoint Attributes Attributes Attributes Daily Program Time ProgramsStructure Individual Time ProgramsAnnual Program Weekly ProgramSpecial Day List Generating a Time ProgramToday Function Time Programs Prior to Alarm Handling04.x Benefits System AlarmsSystem alarms Alarm Alarm text Cond Cause/reason English Code #Alarm Handling Warm Start With corresponding function of XBS or XL-Online System Alarms Suppression V .04.xx or higher Alarms Sent across the System Bus User Program AlarmsData Storage Alarm Handling System Bus Test ModeDistributed I/O testing V2.04.xx or higher CommunicationRuntime Synchronization AccessBus Initialization Bus CommunicationNew Bus Devices Initialization of Distributed I/O ModulesNetwork-Wide Controller Time Synchronization Point Refreshing PC CommunicationExcel IRC Remote CommunicationRemote Modem Connection Controller Firmware 2.04.xx and Higher Remote Trending dial-upGeneral Controller Firmware 2.03.xx and HigherFor all other controllers equipped with Flash Eproms ExcelHBS Country and Language Settings Customize Windows Default Regional and Language SettingsMiscelleanous XL40A2MMI Care Country Controllers with Internal Text MMI XL Online CLTG00MMI CentraLine Country and Language SettingsGraphic MMI CLMMI00N2x Tiger Controllers with Hex Dec Char Unicode ISO/IEC 10646-12000 Character Name Latin Small Letter L Latin Small Letter O with Diaeresis Character Settings Eastern Europe Latin Small Letter D Latin Small Letter U with Ring Above Latin Capital Letter L with Acute Character Settings Turkey Miscelleanous Latin Small Letter D Latin Capital Letter I with DOT Above Latin Capital Letter G with Breve Procedure 1. In Windows, click StartSettingsControl panel Miscelleanous Miscelleanous Miscelleanous Miscelleanous Index ModemfaqAutomation and Control Solutions