EXCEL 50/100/500/600/800

ATTRIBUTES

In the datapoint description, the alarms can be influenced using the functions described below (see also Table 6 on page 17).

Alarm type For each datapoint in the datapoint description, the user can determine whether the signals generated are to be treated as critical or non-critical alarm.

Alarm delay An alarm signal can be delayed by entering an alarm delay time. An alarm signal will be generated only if an alarm continues uninterrupted during the alarm delay time.

Suppress alarm If an alarm signal is not desired from a particular datapoint, this can be fixed in the datapoint description. Thus, all the alarm signals relevant to the particular datapoint and the "Operating Mode" alarm types are suppressed.

Fig. 7. Alarm condition depending on point value and Suppress Alarm status

Fig. 7 shows an example of a changing point value that rises above and falls below the limit Max 2. If Suppress Alarm is not active, then the alarm condition switches between normal to alarm, according to the limit Max 2. If Suppress Alarm is active, then the alarm condition remains normal unless Suppress Alarm is switched off before the point value falls below the limit Max 2. Regardless of the setting of the Alarm suppression flag, an alarm is entered into the controller's history buffer and is also available in the EBI alarm report.

Point alarm It is possible to view all datapoints at the operator interfaces for which the limit value (analog point) or the alarm status (digital point) is currently exceeded.

Driven by a menu, the user address and the accompanying alarm text are displayed on the XI581 (not with XCL5010, Excel 100C) or XI582 operator interfaces or Excel 50 MMI.

On the XL-Online operator interface, a datapoint within the framework of the datapoint description can be seen in all four password levels. If a current alarm is present for the point in question, the attribute “Point in Alarm” produces the display “Yes”, otherwise “No”.

Within the framework of the datapoint description, it is possible, under the attribute “Alarm text”, to enter an alarm text of up to 18 characters in addition to the prepro- grammed text. There are 256 alarm texts in total.

Table 6 presents a summary of various alarm types and attributes.

Table 6. Alarm summary

alarm type/attributes

alarm status

enter alarm

alarm

point in

no. of prepro-

supplementary

delay time

suppression

alarm

grammed texts

text

 

 

Limit Values

selection in DPD*

possible

possible

X

8

possible

Alarm Status

selection in DPD*

possible

possible

X

2

possible

 

 

 

 

 

 

 

Maintenance Alarm

selection in DPD*

-

possible

-

1

-

Totalizer

selection in DPD*

-

possible

-

1

-

Operating Mode

always critical

-

possible

-

2

-

 

 

 

 

 

 

 

System Alarms

always critical

-

-

-

approx. 110

-

17

EN2B-0092GE51 R0512

Image 19
Contents Excel 50/100/500/600/800 Excel 50/100/500/600/800 Contents Value Hysteresis Trend Cycle SubtypeValue Write Protection Excel 50/100/500/600/800 Change Revision OverviewSection Sensor Offset added System Overview Overview Programming Physical Datapoints DatapointsPseudo Datapoints Flexible DatapointsData Points Global DatapointsMapped Datapoints V2.04.xx or higher Acknowledge Alarm V2.04.xx or higher Access LevelAttributes Active State Excel Active State prior toStatus text Alarm Suppression Alarm DelayAlarm Status prior to Interval Counter Alarm Status Alarm Status V2.04.xx or higherAlarm Type Alarm DefinitionAttributes Delay Time Switching Down Delay Time Switching UpCycle Count Engineering Unit Feedback DelayHigh/Low Alarm/Warning Limits DescriptorsHours Run Hours Since ServicedHours Run Log Hysteresis Alarm HysteresisTrend Hysteresis Example of alarm hysteresisBroadcast Hysteresis Intrinsic Hysteresis for Analog Input SignalsInterval Count Input/Output Status Text V2.04.xx or higherInterval Limit CharacteristicBy plug-in For DI on AI Impedance Configured Activated Or low By DIP Diagram High By @Pull-Up Resistor Handling Last ChangeMaintenance Alarm LED Mode XF823x, XFL823x, and XFx830x modulesManual Value Normally Open/Normally Closed V2.04.xx or higher Network Variable V2.04.xx or higherOperating Mode Off PhaseMotor Run Time Remote value Manual valueResulting value Remote value Resulting Value Point AlarmsOutput Type SubtypePulse Duration Safety Position XFx822x, XFx824x, and XFx830x modulesScaling Factor Sensor Offset Switching DownSuppress Point Trend Logging Switch-On CounterSwitching down Switching down behavior Technical AddressTrend Cycle Value HysteresisFlexible datapoint Number of technical addresses ValueRoom Temp.1.10 Number of technical addresses for flexible datapointsWrite Protection List of Datapoint Attributes Attributes Attributes Daily Program Time ProgramsStructure Individual Time ProgramsAnnual Program Weekly ProgramSpecial Day List Generating a Time ProgramToday Function Time Programs Prior to Alarm Handling04.x Benefits System AlarmsSystem alarms Alarm Alarm text Cond Cause/reason English Code #Alarm Handling Warm Start With corresponding function of XBS or XL-Online System Alarms Suppression V .04.xx or higher Alarms Sent across the System Bus User Program AlarmsData Storage Alarm Handling System Bus Test ModeDistributed I/O testing V2.04.xx or higher CommunicationRuntime Synchronization AccessBus Initialization Bus CommunicationNew Bus Devices Initialization of Distributed I/O ModulesNetwork-Wide Controller Time Synchronization Point Refreshing PC CommunicationExcel IRC Remote CommunicationRemote Modem Connection Controller Firmware 2.04.xx and Higher Remote Trending dial-upGeneral Controller Firmware 2.03.xx and HigherFor all other controllers equipped with Flash Eproms ExcelHBS Country and Language Settings Customize Windows Default Regional and Language SettingsMiscelleanous XL40A2MMI Care Country Controllers with Internal Text MMI XL Online CLTG00MMI CentraLine Country and Language SettingsGraphic MMI CLMMI00N2x Tiger Controllers with Hex Dec Char Unicode ISO/IEC 10646-12000 Character Name Latin Small Letter L Latin Small Letter O with Diaeresis Character Settings Eastern Europe Latin Small Letter D Latin Small Letter U with Ring Above Latin Capital Letter L with Acute Character Settings Turkey Miscelleanous Latin Small Letter D Latin Capital Letter I with DOT Above Latin Capital Letter G with Breve Procedure 1. In Windows, click StartSettingsControl panel Miscelleanous Miscelleanous Miscelleanous Miscelleanous Index ModemfaqAutomation and Control Solutions