Honeywell R0512 manual Switch-On Counter, Technical Address, Trend Logging

Page 36

ATTRIBUTESEXCEL 50/100/500/600/800

whether the off-phase is selected between the single stages, e.g., for ventilators, or whether the next lower stage is selected directly, e.g., for electrical air heaters.

Switching down

Switching down behavior

0

3, OFF, 2, OFF, 1, OFF

1

3, 2, 1

Switch-On Counter

Record switching frequency The attribute "Switch-On Counter" gives information about the switching frequency of digital datapoints. The change of state from 0 to 1 is counted in each case.

Technical Address

Technical address An Excel 500/600 controller consists of 16 Distributed input/output modules with a total of 128 physical inputs and outputs. The Excel 100C provides 36 physical I/Os (see Excel 100C Installation Instructions, form no. EN1R-0144GE51, for technical addresses). Where a system requires additional inputs and outputs, several con- trollers can be connected together. Controllers then communicate with one another via the system bus.

Each physical datapoint within the system must have an address that identifies the point uniquely. The technical address contains information about the controller number, the I/O module number, and also the input/output number in this module (see Fig. 19).

020401

Mapped points (V2.04.xx or higher)

Input/output number

Module number (set via address switch on each I/O module) Controller number (set via MMI)

Fig. 19. Example of a technical address

Thus, the address 02.04.01 uniquely identifies the first input/output in the fourth module of the second controller in your system.

NOTE: The Excel 50 controller does not have I/O modules, but its technical addresses follow the same pattern, with module numbers referring to internal I/O boards. For details, see the Excel 50 Installation Instructions.

Datapoints that are mapped only to LONWORKS network variables are not assigned to any I/O board. In this case, the board number (module number) of the technical address is zero.

Trend Logging

Up to 20 datapoints (all datapoint types, except for global datapoints) in each controller can be trend logged simultaneously. This means changes in the input or output value can be stored with the user address, value (or status), date, and time for 20 different datapoints. This is achieved by selecting the attribute "Trend Logging" to YES in the datapoint description.

For analog values (see Fig. 20), the value, e.g., 20 °C / 68 °F, is displayed in addition to the user address, date, and time. For digital values (see Fig. 21), the status text, e.g., "On", is displayed in addition to the user address, date, and time.

EN2B-0092GE51 R0512

34

Image 36
Contents Excel 50/100/500/600/800 Excel 50/100/500/600/800 Contents Subtype Value Hysteresis Trend CycleValue Write Protection Excel 50/100/500/600/800 Revision Overview ChangeSection Sensor Offset added System Overview Overview Programming Datapoints Physical DatapointsFlexible Datapoints Pseudo DatapointsGlobal Datapoints Data PointsMapped Datapoints V2.04.xx or higher Access Level Acknowledge Alarm V2.04.xx or higherAttributes Active State prior to Active State ExcelStatus text Alarm Delay Alarm SuppressionAlarm Status prior to Alarm Status V2.04.xx or higher Alarm TypeAlarm Definition Interval Counter Alarm StatusAttributes Delay Time Switching Up Delay Time Switching DownCycle Count Feedback Delay High/Low Alarm/Warning LimitsDescriptors Engineering UnitHours Since Serviced Hours RunHours Run Log Alarm Hysteresis HysteresisExample of alarm hysteresis Trend HysteresisIntrinsic Hysteresis for Analog Input Signals Broadcast HysteresisInput/Output Status Text V2.04.xx or higher Interval CountCharacteristic Interval LimitConfigured Activated Or low By DIP Diagram High By @ Pull-Up Resistor HandlingLast Change By plug-in For DI on AI ImpedanceLED Mode XF823x, XFL823x, and XFx830x modules Maintenance AlarmManual Value Network Variable V2.04.xx or higher Normally Open/Normally Closed V2.04.xx or higherOff Phase Operating ModeMotor Run Time Manual value Remote valueResulting value Point Alarms Output Type Subtype Remote value Resulting ValueSafety Position XFx822x, XFx824x, and XFx830x modules Pulse DurationScaling Factor Switching Down Sensor OffsetSuppress Point Switch-On Counter Switching down Switching down behaviorTechnical Address Trend LoggingValue Hysteresis Trend CycleValue Room Temp.1.10Number of technical addresses for flexible datapoints Flexible datapoint Number of technical addressesWrite Protection List of Datapoint Attributes Attributes Attributes Time Programs StructureIndividual Time Programs Daily ProgramWeekly Program Annual ProgramGenerating a Time Program Special Day ListToday Function Time Programs Alarm Handling Prior to04.x System Alarms System alarmsAlarm Alarm text Cond Cause/reason English Code # BenefitsAlarm Handling Warm Start With corresponding function of XBS or XL-Online System Alarms Suppression V .04.xx or higher User Program Alarms Alarms Sent across the System BusData Storage Alarm Handling Test Mode Distributed I/O testing V2.04.xx or higherCommunication System BusAccess Bus InitializationBus Communication Runtime SynchronizationInitialization of Distributed I/O Modules New Bus DevicesNetwork-Wide Controller Time Synchronization PC Communication Excel IRCRemote Communication Point RefreshingRemote Modem Connection Remote Trending dial-up GeneralController Firmware 2.03.xx and Higher Controller Firmware 2.04.xx and HigherExcel For all other controllers equipped with Flash EpromsCustomize Windows Default Regional and Language Settings HBS Country and Language SettingsMiscelleanous XL40A2MMI Care Country Controllers with Internal Text MMI XL Online CentraLine Country and Language Settings CLTG00MMIGraphic MMI CLMMI00N2x Tiger Controllers with Hex Dec Char Unicode ISO/IEC 10646-12000 Character Name Latin Small Letter L Latin Small Letter O with Diaeresis Character Settings Eastern Europe Latin Small Letter D Latin Small Letter U with Ring Above Latin Capital Letter L with Acute Character Settings Turkey Miscelleanous Latin Small Letter D Latin Capital Letter I with DOT Above Latin Capital Letter G with Breve Procedure 1. In Windows, click StartSettingsControl panel Miscelleanous Miscelleanous Miscelleanous Miscelleanous Modemfaq IndexAutomation and Control Solutions