Honeywell R0512 manual User Program Alarms, Data Storage, Alarms Sent across the System Bus

Page 53

EXCEL 50/100/500/600/800

 

ALARM HANDLING

 

Table 21. Avoiding alarm datapoint showers

 

 

 

 

 

 

 

 

Reason for fault

Module alarm

Point alarm

 

Care 3.x applications

defective module or power failure

"I/O board missing" (54)

"hardware failure" (109)

 

"I/O board present" (103)

"hardware OK" (110)

 

for controller

 

 

 

 

sensor break / short-circuit or

 

"hardware failure" (109)

 

firmware V. 2.04.xx

 

 

 

missing NV update from bound NV

 

"hardware OK" (110)

 

Care 4.x applications

defective module or power failure

"I/O board missing" (54)

"board missing" (130)

 

"I/O board present" (103)

"board present" (131)

 

for controller

 

 

 

 

sensor break / short-circuit or

 

"hardware failure" (109)

 

firmware V. 2.04.xx

 

 

 

missing NV update from bound NV

 

"hardware OK" (110)

 

Care 4.x applications

defective module or power failure

Due to open LON, module

"board missing" (130)

 

alarms are no longer possible!

"board present" (131)

 

for controller

 

 

 

 

sensor break / short-circuit or

 

"hardware failure" (109)

 

firmware V. 2.06.xx

 

 

 

missing NV update from bound NV

 

"hardware OK" (110)

 

Procedure Engineer CARE 4.x applications for controller firmware version 2.04.xx, and then suppress the datapoint system alarms 109 and 110 by placing the @ character at the first position of the corresponding alarm text.

User Program Alarms

It is possible to generate alarm signals at any point in the user program by using a special program command.

The alarm text can be individually created and may contain up to 18 characters.

Data Storage

Each alarm is stored in the alarm memory that can hold up to 99 alarms. Alarm sig- nals in the alarm memory contain neither an indication of the nature of the alarm signals in the alarm (critical/non-critical) nor an acknowledgment of the alarm on the operator interface.

The alarm memory entry contains user address, alarm text, date, and time. If the memory capacity is exceeded, new alarm signals are accepted, such that the last 99 alarms always remain in the alarm memory.

The alarm memory can be viewed on the XI581 (not with XCL5010, Excel 100C), XI582 and XL-Online operator interfaces and the Excel 50 MMI.

Alarms Sent across the System Bus

Alarm recovery Once the capacity of the temporary alarm buffer for system alarms is reached (max. 99 alarms for firmware 2.03.xx or lower, and max. 50 alarms for firmware 2.04.x), then any additional alarms cause the datapoint to be labeled "in alarm" and given a description of the type of alarm that has occurred. Labeling is carried out only for the last occurring alarm for that datapoint.

When a C-bus connection to a front-end has been established, then all alarm messages of the temporary system alarm buffer are sent to the front-end. After- wards, alarms for datapoints that are labeled “in alarm” are sent directly to the C- bus (except those that are in alarm suppression).

If the controller’s alarm history buffer still contains information related to such an alarm, then this information is sent to the front-end. Otherwise, only the alarm type (without data or time) is sent. In this case, the datapoints appear at the front-end with an asterisk indicating that the data and time shown do not correspond to the generation of the alarm.

Refresh list deletion (V1.5.x) If an XBS or XL-Online is disconnected from the bus/controller, then the refresh list is deleted after a period of 2 minutes. This allows point values to be updated that

51

EN2B-0092GE51 R0512

Image 53
Contents Excel 50/100/500/600/800 Excel 50/100/500/600/800 Contents Value Hysteresis Trend Cycle SubtypeValue Write Protection Excel 50/100/500/600/800 Section Sensor Offset added Revision OverviewChange System Overview Overview Programming Physical Datapoints DatapointsPseudo Datapoints Flexible DatapointsData Points Global DatapointsMapped Datapoints V2.04.xx or higher Attributes Access LevelAcknowledge Alarm V2.04.xx or higher Status text Active State prior toActive State Excel Alarm Status prior to Alarm DelayAlarm Suppression Alarm Type Alarm Status V2.04.xx or higherAlarm Definition Interval Counter Alarm StatusAttributes Cycle Count Delay Time Switching UpDelay Time Switching Down High/Low Alarm/Warning Limits Feedback DelayDescriptors Engineering UnitHours Run Log Hours Since ServicedHours Run Hysteresis Alarm HysteresisTrend Hysteresis Example of alarm hysteresisBroadcast Hysteresis Intrinsic Hysteresis for Analog Input SignalsInterval Count Input/Output Status Text V2.04.xx or higherInterval Limit CharacteristicPull-Up Resistor Handling Configured Activated Or low By DIP Diagram High By @Last Change By plug-in For DI on AI ImpedanceManual Value LED Mode XF823x, XFL823x, and XFx830x modulesMaintenance Alarm Normally Open/Normally Closed V2.04.xx or higher Network Variable V2.04.xx or higherMotor Run Time Off PhaseOperating Mode Resulting value Manual valueRemote value Output Type Point AlarmsSubtype Remote value Resulting ValueScaling Factor Safety Position XFx822x, XFx824x, and XFx830x modulesPulse Duration Suppress Point Switching DownSensor Offset Switching down Switching down behavior Switch-On CounterTechnical Address Trend LoggingTrend Cycle Value HysteresisRoom Temp.1.10 ValueNumber of technical addresses for flexible datapoints Flexible datapoint Number of technical addressesWrite Protection List of Datapoint Attributes Attributes Attributes Structure Time ProgramsIndividual Time Programs Daily ProgramAnnual Program Weekly ProgramToday Function Generating a Time ProgramSpecial Day List Time Programs 04.x Alarm HandlingPrior to System alarms System AlarmsAlarm Alarm text Cond Cause/reason English Code # BenefitsAlarm Handling Warm Start With corresponding function of XBS or XL-Online System Alarms Suppression V .04.xx or higher Data Storage User Program AlarmsAlarms Sent across the System Bus Alarm Handling Distributed I/O testing V2.04.xx or higher Test ModeCommunication System BusBus Initialization AccessBus Communication Runtime SynchronizationNetwork-Wide Controller Time Synchronization Initialization of Distributed I/O ModulesNew Bus Devices Excel IRC PC CommunicationRemote Communication Point RefreshingRemote Modem Connection General Remote Trending dial-upController Firmware 2.03.xx and Higher Controller Firmware 2.04.xx and HigherFor all other controllers equipped with Flash Eproms ExcelMiscelleanous Customize Windows Default Regional and Language SettingsHBS Country and Language Settings XL40A2MMI Care Country Controllers with Internal Text MMI XL Online CLTG00MMI CentraLine Country and Language SettingsGraphic MMI CLMMI00N2x Tiger Controllers with Hex Dec Char Unicode ISO/IEC 10646-12000 Character Name Latin Small Letter L Latin Small Letter O with Diaeresis Character Settings Eastern Europe Latin Small Letter D Latin Small Letter U with Ring Above Latin Capital Letter L with Acute Character Settings Turkey Miscelleanous Latin Small Letter D Latin Capital Letter I with DOT Above Latin Capital Letter G with Breve Procedure 1. In Windows, click StartSettingsControl panel Miscelleanous Miscelleanous Miscelleanous Miscelleanous Index ModemfaqAutomation and Control Solutions