EXCEL 50/100/500/600/800 | ALARM HANDLING |
| |||
|
|
|
| ||
Alarm | alarm text | cond. | cause/reason | ||
no. | English) | code # |
|
| |
14 | Return to normal | 79 | Alarm condition control for DI, PD points. | ||
15 | Hware clock failed | 61 | Error while initializing the system clock. | ||
|
|
|
| ||
16 | Battery low | 17 | Battery voltage too low or battery not existent. | ||
17 | Battery status OK | 87 | Battery voltage back to normal again (alarm occurs only after alarm message "Battery | ||
low"). | |||||
|
|
| |||
18 | Wrong Module ID | 71 | An invalid module ID is read (error on internal I/O or defect module or the module has an | ||
|
|
| |||
19 | Too Many DO | 60 | Too many modules of the same type (XF521, XF522, ...). | ||
Module | |||||
|
|
|
| ||
20 | Contr. w/o Flash | 81 | Error occurred when burning the Flash EPROM. | ||
|
|
|
| ||
21 | FLASH Mem Full | 82 | Not enough Flash memory space to save application. | ||
|
|
|
| ||
22 | Link Point Alarm | - | Xlink alarm. | ||
23 | Link Comm Down | - | Xlink alarm. | ||
24 | No characteristic | 57 | The application part "Characteristics" is defect. | ||
|
|
|
|
| |
25 | RCL Submod | - | RACL | ||
missing | |||||
|
|
|
| ||
26 | Download SSI Now | - | Xlink alarm. | ||
27 | Download CPU | - | Xlink alarm. | ||
Now | |||||
|
|
|
| ||
28 | RACL inconsistent | 29 | Incompatible version numbers of RACL program and RACL parameter files and/or | ||
datapoint description. | |||||
|
|
| |||
29 | Nested | 30 | RACL program contains errors (MCAL from submodule). | ||
submodules! | |||||
|
|
|
| ||
30 | alarm message | - | Alarm not used. | ||
158 | |||||
|
|
|
| ||
31 | RACL undef. | 32 | RACL program contains errors (undefined Operation code). | ||
OpCode | |||||
|
|
|
| ||
32 | RACL program | 33 | RACL program contains errors (Checksum changed). | ||
fault | |||||
|
|
|
| ||
|
|
| 1) During RACL run, datapoint contains errors or point is locked. | ||
33 | Unknown datapoint | 34 | 2) An unrecognized (missing) characteristic in the datapoint editor has been used. | ||
|
|
| Check if the default file set of the controller is different from the set used in CARE. | ||
34 | SSI Points Active |
| Xlink alarm. | ||
|
|
|
| ||
35 | Invalid operation | 36 | |||
statements LN with input value 1.0 ). | |||||
|
|
| |||
36 | RACL overflow | 37 | Arithmetic overflow at RACL performance "+infinite". | ||
37 | RACL neg. | 38 | Arithmetic underflow at RACL performance | ||
overflow | |||||
|
|
|
| ||
38 | RACL inval. | 39 | RACL program contains errors (invalid Operation Code). | ||
OpCode | |||||
|
|
|
| ||
39 | 40 | Access to | |||
40 | Invalid | 41 | Too many statements (exits) in one column. | ||
|
|
|
| ||
41 | Invalid | 42 | Attempt to use | ||
42 | Invalid | 43 | Attempt to use | ||
43 | Invalid | 44 | Attempt to use | ||
|
|
|
| ||
44 | SSI Interface Up | - | Xlink alarm. | ||
45 | No parameter file | - | RACL parameter file missing. | ||
46 | No Z file | - | RACL Z register file missing. | ||
|
|
|
| ||
47 | No T file | - | RACL time register file missing. |
47 |