Honeywell R0512 manual Manual value, Remote value, Resulting value

Page 32

ATTRIBUTES

EXCEL 50/100/500/600/800

Manual During manual operation, the controller uses the manual values, for example, "flow temperature setpoint = 60°C". Outputs adopt the preselected condition, for example, "Heating circuit pump on".

Automatic/Manual Alarm For automatic operation, the attribute "Operating Mode" contains the inputs "Auto" and "Manual". Each switch from automatic to manual operation and back again generates a critical alarm.

Remote (V2.0.x) (not Excel 100C) If manual override controls are present on either the Analog Output (XFL522) or Digital Output (XFL524) modules connected via a LONWORKS network, then the status of these controls (automatic/manual override) is stored in the attribute "Operating Mode". If the manual override controls are set to automatic, the attribute "Operating Mode" can be set to either automatic or manual. If the manual override controls are set to manual override, then the attribute "Operating Mode" can be in the remote mode, only.

Fig. 17 and Fig. 18 demonstrate the relationship between the attribute "Operating Mode", and both the attributes "Value" and "Manual Value" for input and output functions.

Fig. 17. Control flow for input functions

Fig. 18. Control flow for output functions

NOTE: The attribute "Remote" is available only if Manual Override modules are installed on the Distributed I/O output modules. This attribute is therefore not applicable to Excel 50/100/600.

Analog Points Table 13 indicates the analog point signals depending on the attribute "Operating Mode":

Table 13. Analog point signals

 

auto operating

manual operating

remote**

 

mode

mode

operating mode

automatic value*

20%

don’t care

don't care

manual value

don't care

10%

don't care

remote value

don't care

don't care

50%

resulting value

20%

10%

50%

output signal

2 V

1 V

5 V

*Automatic value is either the physical point value (inputs) or the value from the program (outputs)

EN2B-0092GE51 R0512

30

Image 32
Contents Excel 50/100/500/600/800 Excel 50/100/500/600/800 Contents Subtype Value Hysteresis Trend CycleValue Write Protection Excel 50/100/500/600/800 Section Sensor Offset added Revision OverviewChange System Overview Overview Programming Datapoints Physical DatapointsFlexible Datapoints Pseudo DatapointsGlobal Datapoints Data PointsMapped Datapoints V2.04.xx or higher Attributes Access LevelAcknowledge Alarm V2.04.xx or higher Status text Active State prior toActive State Excel Alarm Status prior to Alarm DelayAlarm Suppression Alarm Status V2.04.xx or higher Alarm TypeAlarm Definition Interval Counter Alarm StatusAttributes Cycle Count Delay Time Switching UpDelay Time Switching Down Feedback Delay High/Low Alarm/Warning LimitsDescriptors Engineering UnitHours Run Log Hours Since ServicedHours Run Alarm Hysteresis HysteresisExample of alarm hysteresis Trend HysteresisIntrinsic Hysteresis for Analog Input Signals Broadcast HysteresisInput/Output Status Text V2.04.xx or higher Interval CountCharacteristic Interval LimitConfigured Activated Or low By DIP Diagram High By @ Pull-Up Resistor HandlingLast Change By plug-in For DI on AI Impedance Manual Value LED Mode XF823x, XFL823x, and XFx830x modules Maintenance Alarm Network Variable V2.04.xx or higher Normally Open/Normally Closed V2.04.xx or higherMotor Run Time Off PhaseOperating Mode Resulting value Manual valueRemote value Point Alarms Output TypeSubtype Remote value Resulting ValueScaling Factor Safety Position XFx822x, XFx824x, and XFx830x modulesPulse Duration Suppress Point Switching DownSensor Offset Switch-On Counter Switching down Switching down behaviorTechnical Address Trend LoggingValue Hysteresis Trend CycleValue Room Temp.1.10Number of technical addresses for flexible datapoints Flexible datapoint Number of technical addressesWrite Protection List of Datapoint Attributes Attributes Attributes Time Programs StructureIndividual Time Programs Daily ProgramWeekly Program Annual ProgramToday Function Generating a Time ProgramSpecial Day List Time Programs 04.x Alarm HandlingPrior to System Alarms System alarmsAlarm Alarm text Cond Cause/reason English Code # BenefitsAlarm Handling Warm Start With corresponding function of XBS or XL-Online System Alarms Suppression V .04.xx or higher Data Storage User Program AlarmsAlarms Sent across the System Bus Alarm Handling Test Mode Distributed I/O testing V2.04.xx or higherCommunication System BusAccess Bus InitializationBus Communication Runtime SynchronizationNetwork-Wide Controller Time Synchronization Initialization of Distributed I/O ModulesNew Bus Devices PC Communication Excel IRCRemote Communication Point RefreshingRemote Modem Connection Remote Trending dial-up GeneralController Firmware 2.03.xx and Higher Controller Firmware 2.04.xx and HigherExcel For all other controllers equipped with Flash EpromsMiscelleanous Customize Windows Default Regional and Language SettingsHBS Country and Language Settings XL40A2MMI Care Country Controllers with Internal Text MMI XL Online CentraLine Country and Language Settings CLTG00MMIGraphic MMI CLMMI00N2x Tiger Controllers with Hex Dec Char Unicode ISO/IEC 10646-12000 Character Name Latin Small Letter L Latin Small Letter O with Diaeresis Character Settings Eastern Europe Latin Small Letter D Latin Small Letter U with Ring Above Latin Capital Letter L with Acute Character Settings Turkey Miscelleanous Latin Small Letter D Latin Capital Letter I with DOT Above Latin Capital Letter G with Breve Procedure 1. In Windows, click StartSettingsControl panel Miscelleanous Miscelleanous Miscelleanous Miscelleanous Modemfaq IndexAutomation and Control Solutions