ATTRIBUTES

 

EXCEL 50/100/500/600/800

 

The following four limit value attributes exist:

 

Low Warning Limit

 

Low Alarm Limit

 

High Warning Limit

 

High Alarm Limit

 

Exceeding the limit values generates an alarm.

Example:

Monitoring supply air temperature limits (see Fig. 10).

Fig. 10. Monitoring supply air temperature limits

Hours Run

Display of elapsed hours The attribute "Hours Run" returns the total number of hours during which any of the stages is in the ON position. However, if more than one stage is in the ON position, the "Hours Run" count is not added up, but rather counted only once. Display of the elapsed hours run with activated hours run logging (see also "Hours Run Log" on page 20).

NOTE: If the attribute "Active State" of the point is 0, then the OFF position is also counted.

Hours Run Log

Hours run log An hours run log can be carried out for digital datapoints (physical and pseudo) and for flexible datapoints, e.g. logging the hours run by a heating circuit pump. This requires the decision: hours run log = Yes/No to be made in the attribute "Hours Run Log". The accumulated hours run are displayed in the attribute “Hours Run”. Hours run are logged with a sample rate of 1 minute.

Hours Since Serviced

Display hours run since last maintenance The elapsed hours run since the last maintenance work are totaled in the attribute "Last Maintained". If, for example, the maintenance alarm is 500 hours, and a pump has already been running for 120 hours, then the entry in the attribute “Last

EN2B-0092GE51 R0512

20

Image 22
Contents Excel 50/100/500/600/800 Excel 50/100/500/600/800 Contents Subtype Value Hysteresis Trend CycleValue Write Protection Excel 50/100/500/600/800 Change Revision OverviewSection Sensor Offset added System Overview Overview Programming Datapoints Physical DatapointsFlexible Datapoints Pseudo DatapointsGlobal Datapoints Data PointsMapped Datapoints V2.04.xx or higher Acknowledge Alarm V2.04.xx or higher Access LevelAttributes Active State Excel Active State prior toStatus text Alarm Suppression Alarm DelayAlarm Status prior to Alarm Definition Alarm Status V2.04.xx or higherAlarm Type Interval Counter Alarm Status Attributes Delay Time Switching Down Delay Time Switching UpCycle Count Descriptors Feedback DelayHigh/Low Alarm/Warning Limits Engineering UnitHours Run Hours Since ServicedHours Run Log Alarm Hysteresis HysteresisExample of alarm hysteresis Trend HysteresisIntrinsic Hysteresis for Analog Input Signals Broadcast HysteresisInput/Output Status Text V2.04.xx or higher Interval CountCharacteristic Interval LimitLast Change Configured Activated Or low By DIP Diagram High By @Pull-Up Resistor Handling By plug-in For DI on AI ImpedanceMaintenance Alarm LED Mode XF823x, XFL823x, and XFx830x modulesManual Value Network Variable V2.04.xx or higher Normally Open/Normally Closed V2.04.xx or higherOperating Mode Off PhaseMotor Run Time Remote value Manual valueResulting value Subtype Point AlarmsOutput Type Remote value Resulting ValuePulse Duration Safety Position XFx822x, XFx824x, and XFx830x modulesScaling Factor Sensor Offset Switching DownSuppress Point Technical Address Switch-On CounterSwitching down Switching down behavior Trend LoggingValue Hysteresis Trend CycleNumber of technical addresses for flexible datapoints ValueRoom Temp.1.10 Flexible datapoint Number of technical addressesWrite Protection List of Datapoint Attributes Attributes Attributes Individual Time Programs Time ProgramsStructure Daily ProgramWeekly Program Annual ProgramSpecial Day List Generating a Time ProgramToday Function Time Programs Prior to Alarm Handling04.x Alarm Alarm text Cond Cause/reason English Code # System AlarmsSystem alarms BenefitsAlarm Handling Warm Start With corresponding function of XBS or XL-Online System Alarms Suppression V .04.xx or higher Alarms Sent across the System Bus User Program AlarmsData Storage Alarm Handling Communication Test ModeDistributed I/O testing V2.04.xx or higher System BusBus Communication AccessBus Initialization Runtime SynchronizationNew Bus Devices Initialization of Distributed I/O ModulesNetwork-Wide Controller Time Synchronization Remote Communication PC CommunicationExcel IRC Point RefreshingRemote Modem Connection Controller Firmware 2.03.xx and Higher Remote Trending dial-upGeneral Controller Firmware 2.04.xx and HigherExcel For all other controllers equipped with Flash EpromsHBS Country and Language Settings Customize Windows Default Regional and Language SettingsMiscelleanous XL40A2MMI Care Country Controllers with Internal Text MMI XL Online CentraLine Country and Language Settings CLTG00MMIGraphic MMI CLMMI00N2x Tiger Controllers with Hex Dec Char Unicode ISO/IEC 10646-12000 Character Name Latin Small Letter L Latin Small Letter O with Diaeresis Character Settings Eastern Europe Latin Small Letter D Latin Small Letter U with Ring Above Latin Capital Letter L with Acute Character Settings Turkey Miscelleanous Latin Small Letter D Latin Capital Letter I with DOT Above Latin Capital Letter G with Breve Procedure 1. In Windows, click StartSettingsControl panel Miscelleanous Miscelleanous Miscelleanous Miscelleanous Modemfaq IndexAutomation and Control Solutions