TIME PROGRAMS

EXCEL 50/100/500/600/800

and assigned a user address. This process thus defines which user addresses are to be referenced by the time program.

Up to 20 time programs can be defined for each Excel 500. The time programs are extremely flexible. The switching points for a section of the system or building are usually combined in one time program. It is also possible to combine all datapoints in one time program.

The following steps can also be carried out at operator level 2 (read and limited changes) of the XI581 (not with XCL5010, Excel 100C), XI582, and XL-Online operator interfaces and the XL50-MMI.

1)Daily programs are generated and given a name.

2)User addresses with a switching time and setpoint value or control state are entered in the daily program.

3)A daily program is assigned to each weekday in the weekly program section after the daily programs have been generated.

4)This weekly program is automatically copied for each week in the annual program.

The generation of an executable time program is now complete.

If, on a certain day in the annual program, a daily program differing from the one specified in the weekly program is to be used, this new daily program can be entered directly in the annual program. The defined weekly program is not modified and continues to be used on those days which have not been modified, in any way, in the annual program.

Any changes to be made to switching times, setpoint values, or control states must be carried out in the daily programs.

The special day list is available. It contains a number of holidays; a different daily program can be assigned to each holiday. Once assigned to a holiday, the daily program will apply on this holiday every year. That is valid for holidays with fixed date (for example New Year’s Day or Christmas Eve) as well as for floating holidays (Ascension Day, Good Friday). The dates of floating holidays will be calculated automatically by Excel 500. If there are no entries, then the existing daily program of the annual program remains valid on that holiday.

EN2B-0092GE51 R0512

44

Image 46
Contents Excel 50/100/500/600/800 Excel 50/100/500/600/800 Contents Subtype Value Hysteresis Trend CycleValue Write Protection Excel 50/100/500/600/800 Change Revision OverviewSection Sensor Offset added System Overview Overview Programming Datapoints Physical DatapointsFlexible Datapoints Pseudo DatapointsGlobal Datapoints Data PointsMapped Datapoints V2.04.xx or higher Acknowledge Alarm V2.04.xx or higher Access LevelAttributes Active State Excel Active State prior toStatus text Alarm Suppression Alarm DelayAlarm Status prior to Alarm Definition Alarm Status V2.04.xx or higherAlarm Type Interval Counter Alarm StatusAttributes Delay Time Switching Down Delay Time Switching UpCycle Count Descriptors Feedback DelayHigh/Low Alarm/Warning Limits Engineering UnitHours Run Hours Since ServicedHours Run Log Alarm Hysteresis HysteresisExample of alarm hysteresis Trend HysteresisIntrinsic Hysteresis for Analog Input Signals Broadcast HysteresisInput/Output Status Text V2.04.xx or higher Interval CountCharacteristic Interval LimitLast Change Configured Activated Or low By DIP Diagram High By @Pull-Up Resistor Handling By plug-in For DI on AI ImpedanceMaintenance Alarm LED Mode XF823x, XFL823x, and XFx830x modulesManual Value Network Variable V2.04.xx or higher Normally Open/Normally Closed V2.04.xx or higherOperating Mode Off PhaseMotor Run Time Remote value Manual valueResulting value Subtype Point AlarmsOutput Type Remote value Resulting ValuePulse Duration Safety Position XFx822x, XFx824x, and XFx830x modulesScaling Factor Sensor Offset Switching DownSuppress Point Technical Address Switch-On CounterSwitching down Switching down behavior Trend LoggingValue Hysteresis Trend CycleNumber of technical addresses for flexible datapoints ValueRoom Temp.1.10 Flexible datapoint Number of technical addressesWrite Protection List of Datapoint Attributes Attributes Attributes Individual Time Programs Time ProgramsStructure Daily ProgramWeekly Program Annual ProgramSpecial Day List Generating a Time ProgramToday Function Time Programs Prior to Alarm Handling04.x Alarm Alarm text Cond Cause/reason English Code # System AlarmsSystem alarms BenefitsAlarm Handling Warm Start With corresponding function of XBS or XL-Online System Alarms Suppression V .04.xx or higher Alarms Sent across the System Bus User Program AlarmsData Storage Alarm Handling Communication Test ModeDistributed I/O testing V2.04.xx or higher System BusBus Communication AccessBus Initialization Runtime SynchronizationNew Bus Devices Initialization of Distributed I/O ModulesNetwork-Wide Controller Time Synchronization Remote Communication PC CommunicationExcel IRC Point RefreshingRemote Modem Connection Controller Firmware 2.03.xx and Higher Remote Trending dial-upGeneral Controller Firmware 2.04.xx and HigherExcel For all other controllers equipped with Flash EpromsHBS Country and Language Settings Customize Windows Default Regional and Language SettingsMiscelleanous XL40A2MMI Care Country Controllers with Internal Text MMI XL Online CentraLine Country and Language Settings CLTG00MMIGraphic MMI CLMMI00N2x Tiger Controllers with Hex Dec Char Unicode ISO/IEC 10646-12000 Character Name Latin Small Letter L Latin Small Letter O with Diaeresis Character Settings Eastern Europe Latin Small Letter D Latin Small Letter U with Ring Above Latin Capital Letter L with Acute Character Settings Turkey Miscelleanous Latin Small Letter D Latin Capital Letter I with DOT Above Latin Capital Letter G with Breve Procedure 1. In Windows, click StartSettingsControl panel Miscelleanous Miscelleanous Miscelleanous Miscelleanous Modemfaq IndexAutomation and Control Solutions