EXCEL 50/100/500/600/800

ATTRIBUTES

possible that not every value is displayed when high frequency values with high scaling factors are received.

Resetting the interval count Resetting takes place either manually via an operating unit, by reaching the “Interval Limit” value, or by reaching the “totalized” constant, which is 2 to the power of 31.

Totalizer overflow When the “Interval Limit” or the “totalized” constant is reached, a “Totalizer Overflow” system alarm is created.

Interval Limit

The attribute “Interval Limit” is that value of the "Interval Count" attribute which, when reached, will generate a “Totalizer Overflow” alarm. The highest possible value for the attribute "Interval Count" is 99,999,999.

Electrical energy example A message should be generated after the “consumption” of 5 MWh of electrical power. The input in the attribute “Interval Limit” must therefore be 5 MWh. Once the interval count reaches its reporting level of 5 MWh, then a report is generated, the interval count is reset to “Zero”, and a new totalizing period is started.

I/O Characteristic

The attribute "I/O Characteristic" enables the user to display special input and out- put characteristics (see Fig. 13) for analog inputs/outputs. Special characteristics permit, for instance, the adaptation of Excel 50/100/500/600/800 to many different sensor types. Ten individual input/output characteristics are available per

Excel 50/100/500/600/800 controller.

Each special characteristic is assigned a name that can be recalled from the attribute "I/O Characteristic". Thus, the desired characteristic can be assigned to the selected datapoint.

Fig. 13. Example of a special output characteristic

Creation of characteristics is carried out at programming level. Up to a maximum of four reference points can be specified per characteristic. Up to ten different characteristics can be defined for each controller.

For XFL and XFC I/O modules, user-defined characteristics are supported from CARE 5.0 and controller firmware 2.06.05 onwards.

CAUTION

Regarding I/O characteristic, the behavior of controllers with OS < 2.06.05 engineered using CARE 4 differs significantly from controllers with OS

2.06.05and higher engineered using CARE 7 and higher. See also section “Controller OS 2.06 usage and functionality in CARE 4 and CARE – XL500 7.01.02” in Excel CARE – User Guide (EN2B-0182GE51).

25

EN2B-0092GE51 R0512

Image 27
Contents Excel 50/100/500/600/800 Excel 50/100/500/600/800 Contents Value Hysteresis Trend Cycle SubtypeValue Write Protection Excel 50/100/500/600/800 Revision Overview ChangeSection Sensor Offset added System Overview Overview Programming Physical Datapoints DatapointsPseudo Datapoints Flexible DatapointsData Points Global DatapointsMapped Datapoints V2.04.xx or higher Access Level Acknowledge Alarm V2.04.xx or higherAttributes Active State prior to Active State ExcelStatus text Alarm Delay Alarm SuppressionAlarm Status prior to Interval Counter Alarm Status Alarm Status V2.04.xx or higherAlarm Type Alarm DefinitionAttributes Delay Time Switching Up Delay Time Switching DownCycle Count Engineering Unit Feedback DelayHigh/Low Alarm/Warning Limits DescriptorsHours Since Serviced Hours RunHours Run Log Hysteresis Alarm Hysteresis Trend Hysteresis Example of alarm hysteresisBroadcast Hysteresis Intrinsic Hysteresis for Analog Input SignalsInterval Count Input/Output Status Text V2.04.xx or higherInterval Limit CharacteristicBy plug-in For DI on AI Impedance Configured Activated Or low By DIP Diagram High By @Pull-Up Resistor Handling Last ChangeLED Mode XF823x, XFL823x, and XFx830x modules Maintenance AlarmManual Value Normally Open/Normally Closed V2.04.xx or higher Network Variable V2.04.xx or higherOff Phase Operating ModeMotor Run Time Manual value Remote valueResulting value Remote value Resulting Value Point AlarmsOutput Type SubtypeSafety Position XFx822x, XFx824x, and XFx830x modules Pulse DurationScaling Factor Switching Down Sensor OffsetSuppress Point Trend Logging Switch-On CounterSwitching down Switching down behavior Technical AddressTrend Cycle Value HysteresisFlexible datapoint Number of technical addresses ValueRoom Temp.1.10 Number of technical addresses for flexible datapointsWrite Protection List of Datapoint Attributes Attributes Attributes Daily Program Time ProgramsStructure Individual Time ProgramsAnnual Program Weekly ProgramGenerating a Time Program Special Day ListToday Function Time Programs Alarm Handling Prior to04.x Benefits System AlarmsSystem alarms Alarm Alarm text Cond Cause/reason English Code #Alarm Handling Warm Start With corresponding function of XBS or XL-Online System Alarms Suppression V .04.xx or higher User Program Alarms Alarms Sent across the System BusData Storage Alarm Handling System Bus Test ModeDistributed I/O testing V2.04.xx or higher CommunicationRuntime Synchronization AccessBus Initialization Bus CommunicationInitialization of Distributed I/O Modules New Bus DevicesNetwork-Wide Controller Time Synchronization Point Refreshing PC CommunicationExcel IRC Remote CommunicationRemote Modem Connection Controller Firmware 2.04.xx and Higher Remote Trending dial-upGeneral Controller Firmware 2.03.xx and HigherFor all other controllers equipped with Flash Eproms ExcelCustomize Windows Default Regional and Language Settings HBS Country and Language SettingsMiscelleanous XL40A2MMI Care Country Controllers with Internal Text MMI XL Online CLTG00MMI CentraLine Country and Language SettingsGraphic MMI CLMMI00N2x Tiger Controllers with Hex Dec Char Unicode ISO/IEC 10646-12000 Character Name Latin Small Letter L Latin Small Letter O with Diaeresis Character Settings Eastern Europe Latin Small Letter D Latin Small Letter U with Ring Above Latin Capital Letter L with Acute Character Settings Turkey Miscelleanous Latin Small Letter D Latin Capital Letter I with DOT Above Latin Capital Letter G with Breve Procedure 1. In Windows, click StartSettingsControl panel Miscelleanous Miscelleanous Miscelleanous Miscelleanous Index ModemfaqAutomation and Control Solutions