Honeywell R0512 manual Pulse Duration, Safety Position XFx822x, XFx824x, and XFx830x modules

Page 34

ATTRIBUTES

EXCEL 50/100/500/600/800

As soon as an alarm occurs (e.g. through exceeding a limit value), the attribute "Point in Alarm" is set to "Yes". The attribute is immediately set back to "No" when the limit value returns to normal.

Pulse Duration

The attribute "Pulse Duration" is used for the pulsed subtypes of the digital output (i.e. "Pulse 1") and flexible datapoints of the type "Pulse 2". It defines the duration between coming and going edge of a pulsed signal. The values for this attribute can vary from 1 to 255 seconds; the resolution is 1 second. The default value is 1 second.

NOTE: After a power failure or disconnection of the controller, the “Pulse 1” and “Pulse 2” outputs will resume their last output pulse behavior before the outage.

Safety Position (XFx822x, XFx824x, and XFx830x modules)

The analog output modules XF822x/XFL822x/XFLR822x, the relay output modules XFL824x/XFL824x/XFLR824x and the mixed I/O modules XF830x/XFU830x support the “Safety Position” attribute, which can be set in the CARE datapoint editor.

The modules will put the outputs into the safety position as soon as communication with the Excel 800 CPU is lost.

The XF822x/XF824x modules detect this lost communication once no more polls are received from the Excel 800 CPU for more than one second.

The XFL822x/XFL824x and XF830x/XFU830x modules detect this lost communication once no more polls are received from the Excel 800 CPU within the heartbeat time of the module.

XF822x/XFL822x –”The following attribute options are provided:

“0%” equals 0 Vdc or 2 Vdc (0…11 Vdc or 2…11 Vdc characteristic)

“50%” equals 5 Vdc or 6 Vdc (0…11 Vdc or 2…11 Vdc characteristic)

“100%” equals 10 Vdc

“Remain in last position” (this is the default setting).

XF824x/XFL824x and XF830x/XFU830x –”The following attribute options are provided:

“Off (logical)”

“On (logical)”

“Remain in last position” (this is the default setting).

NOTE: When the XFL822x/XFLR822x and XFL824x/XFLR824x modules are used with non-Excel 800 controllers, the Safety Position can only be set in the LONWORKS NV settings in CARE, and not in the CARE datapoint editor.

Scaling Factor

Input pulses from utility meters (gas, water, heat, etc.) can be connected to the totalizer inputs using the attribute "Scaling Factor". The pulses supplied by the meters are multiplied by the scaling factor and are then ready to be read as pure consumption values. The "Scaling Factor" thus always indicates the value of each pulse received. The adjustable range is 0.0 through 100,000,000.0,

The number of decimal places depends on the selected engineering unit.

Example: A heat meter supplies 10 pulses per kWh "consumed". Accordingly, the scaling factor (= value of a pulse) is 0.1 kWh/pulse.

EN2B-0092GE51 R0512

32

Image 34
Contents Excel 50/100/500/600/800 Excel 50/100/500/600/800 Contents Subtype Value Hysteresis Trend CycleValue Write Protection Excel 50/100/500/600/800 Change Revision OverviewSection Sensor Offset added System Overview Overview Programming Datapoints Physical DatapointsFlexible Datapoints Pseudo DatapointsGlobal Datapoints Data PointsMapped Datapoints V2.04.xx or higher Acknowledge Alarm V2.04.xx or higher Access LevelAttributes Active State Excel Active State prior toStatus text Alarm Suppression Alarm DelayAlarm Status prior to Alarm Definition Alarm Status V2.04.xx or higherAlarm Type Interval Counter Alarm StatusAttributes Delay Time Switching Down Delay Time Switching UpCycle Count Descriptors Feedback DelayHigh/Low Alarm/Warning Limits Engineering UnitHours Run Hours Since ServicedHours Run Log Alarm Hysteresis HysteresisExample of alarm hysteresis Trend HysteresisIntrinsic Hysteresis for Analog Input Signals Broadcast HysteresisInput/Output Status Text V2.04.xx or higher Interval CountCharacteristic Interval LimitLast Change Configured Activated Or low By DIP Diagram High By @Pull-Up Resistor Handling By plug-in For DI on AI ImpedanceMaintenance Alarm LED Mode XF823x, XFL823x, and XFx830x modulesManual Value Network Variable V2.04.xx or higher Normally Open/Normally Closed V2.04.xx or higher Operating Mode Off Phase Motor Run Time Remote value Manual valueResulting value Subtype Point AlarmsOutput Type Remote value Resulting ValuePulse Duration Safety Position XFx822x, XFx824x, and XFx830x modulesScaling Factor Sensor Offset Switching DownSuppress Point Technical Address Switch-On CounterSwitching down Switching down behavior Trend LoggingValue Hysteresis Trend CycleNumber of technical addresses for flexible datapoints ValueRoom Temp.1.10 Flexible datapoint Number of technical addressesWrite Protection List of Datapoint Attributes Attributes Attributes Individual Time Programs Time ProgramsStructure Daily ProgramWeekly Program Annual ProgramSpecial Day List Generating a Time ProgramToday Function Time Programs Prior to Alarm Handling04.x Alarm Alarm text Cond Cause/reason English Code # System AlarmsSystem alarms BenefitsAlarm Handling Warm Start With corresponding function of XBS or XL-Online System Alarms Suppression V .04.xx or higher Alarms Sent across the System Bus User Program AlarmsData Storage Alarm Handling Communication Test ModeDistributed I/O testing V2.04.xx or higher System BusBus Communication AccessBus Initialization Runtime SynchronizationNew Bus Devices Initialization of Distributed I/O ModulesNetwork-Wide Controller Time Synchronization Remote Communication PC CommunicationExcel IRC Point RefreshingRemote Modem Connection Controller Firmware 2.03.xx and Higher Remote Trending dial-upGeneral Controller Firmware 2.04.xx and HigherExcel For all other controllers equipped with Flash EpromsHBS Country and Language Settings Customize Windows Default Regional and Language SettingsMiscelleanous XL40A2MMI Care Country Controllers with Internal Text MMI XL Online CentraLine Country and Language Settings CLTG00MMIGraphic MMI CLMMI00N2x Tiger Controllers with Hex Dec Char Unicode ISO/IEC 10646-12000 Character Name Latin Small Letter L Latin Small Letter O with Diaeresis Character Settings Eastern Europe Latin Small Letter D Latin Small Letter U with Ring Above Latin Capital Letter L with Acute Character Settings Turkey Miscelleanous Latin Small Letter D Latin Capital Letter I with DOT Above Latin Capital Letter G with Breve Procedure 1. In Windows, click StartSettingsControl panel Miscelleanous Miscelleanous Miscelleanous Miscelleanous Modemfaq IndexAutomation and Control Solutions