Honeywell R0512 manual Alarm Hysteresis

Page 23

EXCEL 50/100/500/600/800

ATTRIBUTES

maintained” will be 120 hours. By comparing the attributes "Maintenance Alarm" and "Last Maintained", the user can see that the next maintenance period will be after an additional 380 hours have elapsed. If the maintenance alarm is reached, and the maintenance work has been performed, the counter can be reset manually. The counter can also be reset manually before reaching the maintenance alarm if, for instance, the maintenance has been performed earlier. If the counter is not reset, on expiration of the maintenance alarm, e.g. after 500 hours, the elapsed hours run continues to be incremented, and an additional alarm will be generated when 1000 hours running has been reached.

Hysteresis

The following hysteresis attributes allow the user to control the triggering conditions based on a changing parameter under which actions are taken, such as alarm signaling, writing values to buffers, etc. A hysteresis can be used, e.g., to prevent an alarm from being generated unless the value being monitored changes by more than a given value. This eliminates unnecessary alarm generation and reduces bus communication traffic.

Alarm Hysteresis

Alarm hysteresis (V1.5.x) In the case of analog inputs and pseudo analog points, the attribute "Alarm Hysteresis" is available. It provides variable hysteresis that can be implemented, e.g., in order to reduce the cost of communicating with a remote front-end. The hysteresis value is set from an MMI and can have a value anywhere in the range defined by [10-ato (Max1 - Min1)] where “a” is the number of decimal places set in the attribute "Engineering Unit". The minimum value for the hysteresis is 10-a. Alarms are generated under the following conditions:

Max 1 Alarm (generated if MAX 1 is exceeded)

Max 2 Alarm (generated if MAX 2 is exceeded)

Max 2 Normal (generated if the value falls below MAX 2-Hysteresis)

Max 1 Normal (generated if the value falls below MAX 1-Hysteresis)

Min 1 Alarm (generated if the value falls below MIN 1)

Min 2 Alarm (generated if the value falls below MIN 2)

Min 2 Normal (generated if the value MIN 2+Hysteresis is exceeded)

Min 1 Normal (generated if the value MIN 1+Hysteresis is exceeded)

The CARE default value (i.e. 1% of actual value and no less than 0.2) for this attribute is 0. Access to "Alarm Hysteresis" is also possible via RIA/WIA.

NOTE: The number of decimal places can be changed only using CARE.

NOTE: Attempting to enter a hysteresis value that is less than the allowed minimum will result in the attribute being assigned the minimum value as defined above.

Example:

In this example, the number of decimal places in the attribute "Engineering Unit" has been chosen to have a value of 2. Fig. 11 shows an example datapoint value as a function of time that increases and decreases over the range from Max 1 to Min 1.

21

EN2B-0092GE51 R0512

Image 23
Contents Excel 50/100/500/600/800 Excel 50/100/500/600/800 Contents Value Hysteresis Trend Cycle SubtypeValue Write Protection Excel 50/100/500/600/800 Section Sensor Offset added Revision OverviewChange System Overview Overview Programming Physical Datapoints DatapointsPseudo Datapoints Flexible DatapointsData Points Global DatapointsMapped Datapoints V2.04.xx or higher Attributes Access LevelAcknowledge Alarm V2.04.xx or higher Status text Active State prior toActive State Excel Alarm Status prior to Alarm DelayAlarm Suppression Interval Counter Alarm Status Alarm Status V2.04.xx or higherAlarm Type Alarm DefinitionAttributes Cycle Count Delay Time Switching UpDelay Time Switching Down Engineering Unit Feedback DelayHigh/Low Alarm/Warning Limits DescriptorsHours Run Log Hours Since ServicedHours Run Hysteresis Alarm HysteresisTrend Hysteresis Example of alarm hysteresisBroadcast Hysteresis Intrinsic Hysteresis for Analog Input SignalsInterval Count Input/Output Status Text V2.04.xx or higherInterval Limit CharacteristicBy plug-in For DI on AI Impedance Configured Activated Or low By DIP Diagram High By @Pull-Up Resistor Handling Last ChangeManual Value LED Mode XF823x, XFL823x, and XFx830x modulesMaintenance Alarm Normally Open/Normally Closed V2.04.xx or higher Network Variable V2.04.xx or higherMotor Run Time Off PhaseOperating Mode Resulting value Manual valueRemote value Remote value Resulting Value Point AlarmsOutput Type SubtypeScaling Factor Safety Position XFx822x, XFx824x, and XFx830x modulesPulse Duration Suppress Point Switching DownSensor Offset Trend Logging Switch-On CounterSwitching down Switching down behavior Technical AddressTrend Cycle Value HysteresisFlexible datapoint Number of technical addresses ValueRoom Temp.1.10 Number of technical addresses for flexible datapointsWrite Protection List of Datapoint Attributes Attributes Attributes Daily Program Time ProgramsStructure Individual Time ProgramsAnnual Program Weekly ProgramToday Function Generating a Time ProgramSpecial Day List Time Programs 04.x Alarm HandlingPrior to Benefits System AlarmsSystem alarms Alarm Alarm text Cond Cause/reason English Code #Alarm Handling Warm Start With corresponding function of XBS or XL-Online System Alarms Suppression V .04.xx or higher Data Storage User Program AlarmsAlarms Sent across the System Bus Alarm Handling System Bus Test ModeDistributed I/O testing V2.04.xx or higher CommunicationRuntime Synchronization AccessBus Initialization Bus CommunicationNetwork-Wide Controller Time Synchronization Initialization of Distributed I/O ModulesNew Bus Devices Point Refreshing PC CommunicationExcel IRC Remote CommunicationRemote Modem Connection Controller Firmware 2.04.xx and Higher Remote Trending dial-upGeneral Controller Firmware 2.03.xx and HigherFor all other controllers equipped with Flash Eproms ExcelMiscelleanous Customize Windows Default Regional and Language SettingsHBS Country and Language Settings XL40A2MMI Care Country Controllers with Internal Text MMI XL Online CLTG00MMI CentraLine Country and Language SettingsGraphic MMI CLMMI00N2x Tiger Controllers with Hex Dec Char Unicode ISO/IEC 10646-12000 Character Name Latin Small Letter L Latin Small Letter O with Diaeresis Character Settings Eastern Europe Latin Small Letter D Latin Small Letter U with Ring Above Latin Capital Letter L with Acute Character Settings Turkey Miscelleanous Latin Small Letter D Latin Capital Letter I with DOT Above Latin Capital Letter G with Breve Procedure 1. In Windows, click StartSettingsControl panel Miscelleanous Miscelleanous Miscelleanous Miscelleanous Index ModemfaqAutomation and Control Solutions