Honeywell R0512 manual Sensor Offset, Suppress Point, Switching Down

Page 35

EXCEL 50/100/500/600/800

ATTRIBUTES

Pseudo totalizers: In the event that you have selected the datapoint type "pseudo totalizer inputs," you must set the attribute "Scaling Factor" to "1"; otherwise, the number of pseudo totalizer inputs will not be counted.

Sensor Offset

The attribute “Sensor Offset” is designed for the compensation of the resistance of the sensor wiring for low-resistance sensors, like Pt 100, Pt 1000, Balco 500.

The voltage offset due to the wire resistance is approximately constant, the attribute “Sensor Offset” functionality has therefore been designed to compensate constant voltage offsets at the analog input.

Function principle The principle is that the attribute “Sensor Offset” can be defined at a selected tem- perature, e.g., 1 °C at 20 °C. The Excel controller processes this temperature offset into a voltage offset, e.g., -0.11 V, and applies this very voltage offset for correcting (offsetting) all voltages measured.

In order to display a temperature, the controller processes the resulting voltage back into a temperature. This principle and the processing (including mathematical rounding) from “°C” into “volt” and back into “°C” leads to slightly inconstant offsets across the temperature range.

Example for a selected “Sensor Offset” of 1°C:

Measured Temperature

Corrected Temperature

20°C

19°C

-10°C

-8,4°C

For XFL and XFC I/O modules, "Sensor Offset" functionality is supported from

CARE 5.0 and controller firmware 2.06.05 onwards.

CAUTION

Regarding sensor offset, the behavior of controllers with OS < 2.06.05 engineered using CARE 4 differs significantly from controllers with OS 2.06.05 and higher engineered using CARE 7 and higher.

For example, for XL50 internal AI and XL500 internal AI (XF521/527 modules), the sensor offset is subtracted from the datapoint value.

For XL50 and XL800 controllers using XF821 modules, the sensor offset is added to the datapoint value.

See also section “Sensor Offset Handling” in Excel CARE – User Guide (EN2B-0182GE51).

Suppress Point

The attribute "Suppress Point" means that datapoints are no longer processed and checked. As a result, no alarms are generated for suppressed points. Where you have flexible datapoints, this attribute acts upon all basic types of physical datapoints.

IMPORTANT

Never suppress a datapoint used via your application program. This causes system failure.

Switching Down

The attribute "Switching Down" is used in conjunction with flexible datapoints of the type "feedback". On switching down from one stage to another, it determines

33

EN2B-0092GE51 R0512

Image 35
Contents Excel 50/100/500/600/800 Excel 50/100/500/600/800 Contents Value Hysteresis Trend Cycle SubtypeValue Write Protection Excel 50/100/500/600/800 Section Sensor Offset added Revision OverviewChange System Overview Overview Programming Physical Datapoints DatapointsPseudo Datapoints Flexible DatapointsData Points Global DatapointsMapped Datapoints V2.04.xx or higher Attributes Access LevelAcknowledge Alarm V2.04.xx or higher Status text Active State prior toActive State Excel Alarm Status prior to Alarm DelayAlarm Suppression Interval Counter Alarm Status Alarm Status V2.04.xx or higherAlarm Type Alarm DefinitionAttributes Cycle Count Delay Time Switching UpDelay Time Switching Down Engineering Unit Feedback DelayHigh/Low Alarm/Warning Limits DescriptorsHours Run Log Hours Since ServicedHours Run Hysteresis Alarm HysteresisTrend Hysteresis Example of alarm hysteresisBroadcast Hysteresis Intrinsic Hysteresis for Analog Input SignalsInterval Count Input/Output Status Text V2.04.xx or higherInterval Limit CharacteristicBy plug-in For DI on AI Impedance Configured Activated Or low By DIP Diagram High By @Pull-Up Resistor Handling Last ChangeManual Value LED Mode XF823x, XFL823x, and XFx830x modulesMaintenance Alarm Normally Open/Normally Closed V2.04.xx or higher Network Variable V2.04.xx or higherMotor Run Time Off PhaseOperating Mode Resulting value Manual value Remote value Remote value Resulting Value Point AlarmsOutput Type SubtypeScaling Factor Safety Position XFx822x, XFx824x, and XFx830x modulesPulse Duration Suppress Point Switching DownSensor Offset Trend Logging Switch-On CounterSwitching down Switching down behavior Technical AddressTrend Cycle Value HysteresisFlexible datapoint Number of technical addresses ValueRoom Temp.1.10 Number of technical addresses for flexible datapointsWrite Protection List of Datapoint Attributes Attributes Attributes Daily Program Time ProgramsStructure Individual Time ProgramsAnnual Program Weekly ProgramToday Function Generating a Time ProgramSpecial Day List Time Programs 04.x Alarm HandlingPrior to Benefits System AlarmsSystem alarms Alarm Alarm text Cond Cause/reason English Code #Alarm Handling Warm Start With corresponding function of XBS or XL-Online System Alarms Suppression V .04.xx or higher Data Storage User Program AlarmsAlarms Sent across the System Bus Alarm Handling System Bus Test ModeDistributed I/O testing V2.04.xx or higher CommunicationRuntime Synchronization AccessBus Initialization Bus CommunicationNetwork-Wide Controller Time Synchronization Initialization of Distributed I/O ModulesNew Bus Devices Point Refreshing PC CommunicationExcel IRC Remote CommunicationRemote Modem Connection Controller Firmware 2.04.xx and Higher Remote Trending dial-upGeneral Controller Firmware 2.03.xx and HigherFor all other controllers equipped with Flash Eproms ExcelMiscelleanous Customize Windows Default Regional and Language SettingsHBS Country and Language Settings XL40A2MMI Care Country Controllers with Internal Text MMI XL Online CLTG00MMI CentraLine Country and Language SettingsGraphic MMI CLMMI00N2x Tiger Controllers with Hex Dec Char Unicode ISO/IEC 10646-12000 Character Name Latin Small Letter L Latin Small Letter O with Diaeresis Character Settings Eastern Europe Latin Small Letter D Latin Small Letter U with Ring Above Latin Capital Letter L with Acute Character Settings Turkey Miscelleanous Latin Small Letter D Latin Capital Letter I with DOT Above Latin Capital Letter G with Breve Procedure 1. In Windows, click StartSettingsControl panel Miscelleanous Miscelleanous Miscelleanous Miscelleanous Index ModemfaqAutomation and Control Solutions