Honeywell R0512 manual Attributes, Access Level, Acknowledge Alarm V2.04.xx or higher

Page 15

EXCEL 50/100/500/600/800

ATTRIBUTES

Each datapoint type has associated with it various parameters which allow the user to set, e.g., the user address, the level of access protection, alarm behavior, and other options. These parameters are called attributes. Each attribute performs a specific function related to the datapoint. A complete list of datapoint types and their attributes appears in Table 17 through Table 19. Not all attributes are available for every datapoint type.

Point refreshing (V1.5.x) Four attributes ("Value", "Manual Value", "Operating Mode", and "Alarm Status") will be simultaneously refreshed to an XL-Online operator interface.

NOTE: A complete list of attributes associated with the various datapoint types can be found in the section "List of Datapoint Attributes" on page 38.

Access Level

Four levels of protection The attribute "Access Level" protects datapoints against unauthorized changes on the basis of the password level needed to modify a datapoint. "Access Level" attributes between "1" and "4" are assigned to a point. These attributes correspond to the four password levels found in the XI581 (not with XCL5010, Excel 100C), XI582, and XL-Online operator interfaces and the Excel 50 MMI:

Operator level 1:

Read only.

Operator level 2: Read and make limited changes.

Operator level 3: Read and make changes.

Operator level 4:

Programming.

For example, setting the "Access Level" attribute for the datapoint with the user address "room temp floor 1" to "2" means that all attributes for this datapoint can now only be edited or modified at password level 2 or higher.

Acknowledge Alarm (V2.04.xx or higher)

The attribute "Acknowledge Alarm" allows a controller to acknowledge an alarm for a flexible datapoint of the type "feedback" without changing the operating mode. The controller takes the point out of alarm as soon as a rising edge is detected on the input of the WIA statement writing to the attribute "Acknowledge Alarm".

Fig. 5. The "Acknowledge Alarm" attribute for WIA statement

This attribute is a virtual attribute and can be accessed only by a WIA statement in CARE. It is not part of the datapoint description and therefore cannot be displayed on an MMI or building supervisor.

EN2B-0092GE51 R1111

13

Image 15
Contents Excel 50/100/500/600/800 Excel 50/100/500/600/800 Contents Value Hysteresis Trend Cycle SubtypeValue Write Protection Excel 50/100/500/600/800 Revision Overview ChangeSection Sensor Offset added System Overview Overview Programming Physical Datapoints DatapointsPseudo Datapoints Flexible DatapointsData Points Global DatapointsMapped Datapoints V2.04.xx or higher Access Level Acknowledge Alarm V2.04.xx or higherAttributes Active State prior to Active State ExcelStatus text Alarm Delay Alarm SuppressionAlarm Status prior to Interval Counter Alarm Status Alarm Status V2.04.xx or higherAlarm Type Alarm DefinitionAttributes Delay Time Switching Up Delay Time Switching DownCycle Count Engineering Unit Feedback DelayHigh/Low Alarm/Warning Limits DescriptorsHours Since Serviced Hours RunHours Run Log Hysteresis Alarm HysteresisTrend Hysteresis Example of alarm hysteresisBroadcast Hysteresis Intrinsic Hysteresis for Analog Input SignalsInterval Count Input/Output Status Text V2.04.xx or higherInterval Limit CharacteristicBy plug-in For DI on AI Impedance Configured Activated Or low By DIP Diagram High By @Pull-Up Resistor Handling Last ChangeLED Mode XF823x, XFL823x, and XFx830x modules Maintenance AlarmManual Value Normally Open/Normally Closed V2.04.xx or higher Network Variable V2.04.xx or higherOff Phase Operating ModeMotor Run Time Manual value Remote valueResulting value Remote value Resulting Value Point AlarmsOutput Type SubtypeSafety Position XFx822x, XFx824x, and XFx830x modules Pulse DurationScaling Factor Switching Down Sensor OffsetSuppress Point Trend Logging Switch-On CounterSwitching down Switching down behavior Technical AddressTrend Cycle Value HysteresisFlexible datapoint Number of technical addresses ValueRoom Temp.1.10 Number of technical addresses for flexible datapointsWrite Protection List of Datapoint Attributes Attributes Attributes Daily Program Time ProgramsStructure Individual Time ProgramsAnnual Program Weekly ProgramGenerating a Time Program Special Day ListToday Function Time Programs Alarm Handling Prior to04.x Benefits System AlarmsSystem alarms Alarm Alarm text Cond Cause/reason English Code #Alarm Handling Warm Start With corresponding function of XBS or XL-Online System Alarms Suppression V .04.xx or higher User Program Alarms Alarms Sent across the System BusData Storage Alarm Handling System Bus Test ModeDistributed I/O testing V2.04.xx or higher CommunicationRuntime Synchronization AccessBus Initialization Bus CommunicationInitialization of Distributed I/O Modules New Bus DevicesNetwork-Wide Controller Time Synchronization Point Refreshing PC CommunicationExcel IRC Remote CommunicationRemote Modem Connection Controller Firmware 2.04.xx and Higher Remote Trending dial-upGeneral Controller Firmware 2.03.xx and HigherFor all other controllers equipped with Flash Eproms ExcelCustomize Windows Default Regional and Language Settings HBS Country and Language SettingsMiscelleanous XL40A2MMI Care Country Controllers with Internal Text MMI XL Online CLTG00MMI CentraLine Country and Language SettingsGraphic MMI CLMMI00N2x Tiger Controllers with Hex Dec Char Unicode ISO/IEC 10646-12000 Character Name Latin Small Letter L Latin Small Letter O with Diaeresis Character Settings Eastern Europe Latin Small Letter D Latin Small Letter U with Ring Above Latin Capital Letter L with Acute Character Settings Turkey Miscelleanous Latin Small Letter D Latin Capital Letter I with DOT Above Latin Capital Letter G with Breve Procedure 1. In Windows, click StartSettingsControl panel Miscelleanous Miscelleanous Miscelleanous Miscelleanous Index ModemfaqAutomation and Control Solutions