Honeywell R0512 LED Mode XF823x, XFL823x, and XFx830x modules, Maintenance Alarm, Manual Value

Page 29

EXCEL 50/100/500/600/800

ATTRIBUTES

In this way it is possible to determine the last switch-on point of a fan, pump, etc. connected via a digital output.

In the case of analog inputs and pseudo analog points, the last time an alarm limit occurred is stored.

LED Mode (XF823x, XFL823x, and XFx830x modules)

The XF823x Panel Bus Binary Input Module, the XFL823x Lonworks Bus Binary Input Module, and the XF830x / XFU830x modules support the “LED Mode” attribute, which can be set in the CARE datapoint editor. The following attribute options are provided:

“Alarm”

LEDs will be red/green (red = alarm state, not XF830x /

 

 

XFU830x modules)

“Status”

LEDs will be yellow/off (yellow = active state)

NOTE: XF830x / XFU830x modules do not support the Alarm option. Hence, do not assign this attribute to datapoints allocated to one of these modules.

NOTE: When the XFL823x LONWORKS Bus Binary Input Module is used with non-Excel 800 controllers, the LED mode can only be set in the LONWORKS NV settings in CARE, and not in the CARE datapoint editor.

Maintenance Alarm

Specifying a maintenance alarm In the case of those datapoints for which an hours run log has been activated, a time entry can occur within the attribute "Maintenance Alarm" to indicate after how many operational hours an alarm message should be generated. Entering “Zero” results in no alarm message.

Example:

Maintenance should be carried out every 500 hours on the heating circuit pump controlled via a digital output. To achieve this, a time interval duration of 500 hours is entered in the attribute "Maintenance Alarm" for this datapoint. At the same time, activation of the hours run log must also take place in the attribute “Hours Run log” for this datapoint. An alarm message now occurs after 500 hours, to bring to the operator’s attention the necessary pump maintenance.

Manual Value

When the attribute "Operating Mode" is set to "Manual", the operator can enter a manual value or state, and the application program will work with this manual value or state until the operating mode is set back to “Automatic”.

Fig. 15. Example of a sensor input

27

EN2B-0092GE51 R0512

Image 29
Contents Excel 50/100/500/600/800 Excel 50/100/500/600/800 Contents Value Hysteresis Trend Cycle SubtypeValue Write Protection Excel 50/100/500/600/800 Section Sensor Offset added Revision OverviewChange System Overview Overview Programming Physical Datapoints DatapointsPseudo Datapoints Flexible DatapointsData Points Global DatapointsMapped Datapoints V2.04.xx or higher Attributes Access LevelAcknowledge Alarm V2.04.xx or higher Status text Active State prior toActive State Excel Alarm Status prior to Alarm DelayAlarm Suppression Alarm Type Alarm Status V2.04.xx or higherAlarm Definition Interval Counter Alarm StatusAttributes Cycle Count Delay Time Switching UpDelay Time Switching Down High/Low Alarm/Warning Limits Feedback DelayDescriptors Engineering UnitHours Run Log Hours Since ServicedHours Run Hysteresis Alarm HysteresisTrend Hysteresis Example of alarm hysteresisBroadcast Hysteresis Intrinsic Hysteresis for Analog Input SignalsInterval Count Input/Output Status Text V2.04.xx or higherInterval Limit CharacteristicPull-Up Resistor Handling Configured Activated Or low By DIP Diagram High By @Last Change By plug-in For DI on AI ImpedanceManual Value LED Mode XF823x, XFL823x, and XFx830x modulesMaintenance Alarm Normally Open/Normally Closed V2.04.xx or higher Network Variable V2.04.xx or higherMotor Run Time Off PhaseOperating Mode Resulting value Manual valueRemote value Output Type Point AlarmsSubtype Remote value Resulting ValueScaling Factor Safety Position XFx822x, XFx824x, and XFx830x modulesPulse Duration Suppress Point Switching DownSensor Offset Switching down Switching down behavior Switch-On CounterTechnical Address Trend LoggingTrend Cycle Value HysteresisRoom Temp.1.10 ValueNumber of technical addresses for flexible datapoints Flexible datapoint Number of technical addressesWrite Protection List of Datapoint Attributes Attributes Attributes Structure Time ProgramsIndividual Time Programs Daily ProgramAnnual Program Weekly ProgramToday Function Generating a Time ProgramSpecial Day List Time Programs 04.x Alarm HandlingPrior to System alarms System AlarmsAlarm Alarm text Cond Cause/reason English Code # BenefitsAlarm Handling Warm Start With corresponding function of XBS or XL-Online System Alarms Suppression V .04.xx or higher Data Storage User Program AlarmsAlarms Sent across the System Bus Alarm Handling Distributed I/O testing V2.04.xx or higher Test ModeCommunication System BusBus Initialization AccessBus Communication Runtime SynchronizationNetwork-Wide Controller Time Synchronization Initialization of Distributed I/O ModulesNew Bus Devices Excel IRC PC CommunicationRemote Communication Point RefreshingRemote Modem Connection General Remote Trending dial-upController Firmware 2.03.xx and Higher Controller Firmware 2.04.xx and HigherFor all other controllers equipped with Flash Eproms ExcelMiscelleanous Customize Windows Default Regional and Language SettingsHBS Country and Language Settings XL40A2MMI Care Country Controllers with Internal Text MMI XL Online CLTG00MMI CentraLine Country and Language SettingsGraphic MMI CLMMI00N2x Tiger Controllers with Hex Dec Char Unicode ISO/IEC 10646-12000 Character Name Latin Small Letter L Latin Small Letter O with Diaeresis Character Settings Eastern Europe Latin Small Letter D Latin Small Letter U with Ring Above Latin Capital Letter L with Acute Character Settings Turkey Miscelleanous Latin Small Letter D Latin Capital Letter I with DOT Above Latin Capital Letter G with Breve Procedure 1. In Windows, click StartSettingsControl panel Miscelleanous Miscelleanous Miscelleanous Miscelleanous Index ModemfaqAutomation and Control Solutions