TIME PROGRAMS

Entries in the annual program must therefore be made only if a daily program differing from the one selected is to be used. An undefined daily program to be inserted in the annual program can be defined in the daily program.

Special Day List

One special day list exists per time program. It makes a number of holidays and special days available to which a daily program can be assigned. This daily pro- gram will then apply to this holiday or special day every year. The date of floating holidays is calculated automatically by the Excel 500. If no daily program is entered on certain holidays, the special day list is not taken into account on this day.

The following holidays and special days are contained in the list:

New Year's Day (1st of January)

Epiphany (6th of January)

Monday before Ash Wednesday

Shrove Tuesday

Ash Wednesday

Good Friday

Easter Sunday

Easter Monday

Labor Day (1st of May)

Ascension Day

Whit Sunday

Whit Monday

Corpus Christi

Assumption Day (15th of August)

Day of German Unity (3rd of October)

Reformation Day (31st of October)

All Saint's Day (1st of November)

Day of Prayer and Repentance

1st to 4th Sundays in Advent

Christmas Eve (24th of December)

Christmas Day (25th of December)

Boxing Day (26th of December)

New Year's Eve (31st of December)

First Saturday in the month (Germany)

If a daily program that has not yet been defined should be entered in the special day list, it must first be defined in the "Daily program" section of the time program.

NOTE: To activate the special day list, you must set the special day status to

ON.

The "TODAY" Function

Using the "TODAY" function, it is possible to perform on/off changes to setpoint values or control states without having to access the annual program or to define a new daily program. New setpoint values or control states and the period of validity (i.e. start and end) for a specific user address are defined. These changes are carried out at operator level 2 of the XI581 (not with XCL5010, Excel 100C), XI582, and XL-Online operator interfaces or the Excel 50 MMI. The start time must be within 24 hours from the entry time. The end time must be within 24 hours from the start time. The duration of the change can thus amount to a maximum of 24 hours. The entry is deleted automatically after the end time point is exceeded.

Generating a Time Program

A new time program is defined at operator level 4 (programming level) of XL-Online or on the Excel CARE engineering system. The new time program is given a name

43

EN2B-0092GE51 R0512

Image 45
Contents Excel 50/100/500/600/800 Excel 50/100/500/600/800 Contents Value Hysteresis Trend Cycle SubtypeValue Write Protection Excel 50/100/500/600/800 Revision Overview ChangeSection Sensor Offset added System Overview Overview Programming Physical Datapoints DatapointsPseudo Datapoints Flexible DatapointsData Points Global DatapointsMapped Datapoints V2.04.xx or higher Access Level Acknowledge Alarm V2.04.xx or higherAttributes Active State prior to Active State ExcelStatus text Alarm Delay Alarm SuppressionAlarm Status prior to Alarm Type Alarm Status V2.04.xx or higherAlarm Definition Interval Counter Alarm StatusAttributes Delay Time Switching Up Delay Time Switching DownCycle Count High/Low Alarm/Warning Limits Feedback DelayDescriptors Engineering UnitHours Since Serviced Hours RunHours Run Log Hysteresis Alarm HysteresisTrend Hysteresis Example of alarm hysteresisBroadcast Hysteresis Intrinsic Hysteresis for Analog Input SignalsInterval Count Input/Output Status Text V2.04.xx or higherInterval Limit CharacteristicPull-Up Resistor Handling Configured Activated Or low By DIP Diagram High By @Last Change By plug-in For DI on AI ImpedanceLED Mode XF823x, XFL823x, and XFx830x modules Maintenance AlarmManual Value Normally Open/Normally Closed V2.04.xx or higher Network Variable V2.04.xx or higherOff Phase Operating ModeMotor Run Time Manual value Remote valueResulting value Output Type Point AlarmsSubtype Remote value Resulting ValueSafety Position XFx822x, XFx824x, and XFx830x modules Pulse DurationScaling Factor Switching Down Sensor OffsetSuppress Point Switching down Switching down behavior Switch-On CounterTechnical Address Trend LoggingTrend Cycle Value HysteresisRoom Temp.1.10 ValueNumber of technical addresses for flexible datapoints Flexible datapoint Number of technical addressesWrite Protection List of Datapoint Attributes Attributes Attributes Structure Time ProgramsIndividual Time Programs Daily ProgramAnnual Program Weekly ProgramGenerating a Time Program Special Day ListToday Function Time Programs Alarm Handling Prior to04.x System alarms System AlarmsAlarm Alarm text Cond Cause/reason English Code # BenefitsAlarm Handling Warm Start With corresponding function of XBS or XL-Online System Alarms Suppression V .04.xx or higher User Program Alarms Alarms Sent across the System BusData Storage Alarm Handling Distributed I/O testing V2.04.xx or higher Test ModeCommunication System BusBus Initialization AccessBus Communication Runtime SynchronizationInitialization of Distributed I/O Modules New Bus DevicesNetwork-Wide Controller Time Synchronization Excel IRC PC CommunicationRemote Communication Point RefreshingRemote Modem Connection General Remote Trending dial-upController Firmware 2.03.xx and Higher Controller Firmware 2.04.xx and HigherFor all other controllers equipped with Flash Eproms ExcelCustomize Windows Default Regional and Language Settings HBS Country and Language SettingsMiscelleanous XL40A2MMI Care Country Controllers with Internal Text MMI XL Online CLTG00MMI CentraLine Country and Language SettingsGraphic MMI CLMMI00N2x Tiger Controllers with Hex Dec Char Unicode ISO/IEC 10646-12000 Character Name Latin Small Letter L Latin Small Letter O with Diaeresis Character Settings Eastern Europe Latin Small Letter D Latin Small Letter U with Ring Above Latin Capital Letter L with Acute Character Settings Turkey Miscelleanous Latin Small Letter D Latin Capital Letter I with DOT Above Latin Capital Letter G with Breve Procedure 1. In Windows, click StartSettingsControl panel Miscelleanous Miscelleanous Miscelleanous Miscelleanous Index ModemfaqAutomation and Control Solutions