ATTRIBUTES | EXCEL 50/100/500/600/800 |
Active State (prior to V2.04.x)
The attribute "Active State" defines when a digital input/output is active.
NOTE: The "Active State" attribute does not reflect the current condition of a digital datapoint.
NOTE: This is not applicable to digital inputs in applications designed for con- trollers using V2.04.xx firmware or higher. In such applications, this attribute is fixed at 1, and the new attribute "Normally Open/Normally Closed" (NO/NC) is active (see section "Normally Open/Normally Closed (V2.04.xx or higher)" on page 28 for more details).
The following values are possible:
•0 = digital input/output is active when a "logical 0 signal" is present
•1 = digital input/output is active when a "logical 1 signal" is present
Table 3 indicates the active state for various conditions of the XF523 and XFL523 modules.
Table 3. Active state for the digital input of XF523 and XFL523 modules
|
|
|
|
|
| digital input |
|
|
|
| ||
contact status |
|
| open |
|
|
|
| closed |
| |||
CARE definition |
| NC |
| NO | NC |
| NO |
| ||||
(NC/NO system diagram) |
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
| |
definition - in |
|
|
|
|
|
|
|
|
|
|
|
|
Editor attribute "Active State" | 1 |
| 0 | 1 |
| 0 | 1 |
| 0 | 1 |
| 0 |
(change Active/Passive State |
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
| |
text) |
|
|
|
|
|
|
|
|
|
|
|
|
CARE interpretation | 1 |
| 1 | 0 |
| 0 | 0 |
| 0 | 1 |
| 1 |
(control table) |
|
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
|
| |
display at operator interface | OFF/ |
| ON/ | OFF/ |
| ON/ | ON/ |
| OFF/ | ON/ |
| OFF/ |
trouble: |
| operating | trouble: |
| operating | operating |
| trouble: | operating |
| trouble: | |
(status text) |
|
|
|
| ||||||||
| alarm |
| RTN* | alarm |
| RTN* | RTN* |
| alarm | RTN* |
| alarm |
| * | RTN = Return | To Normal |
|
|
|
|
|
|
| ||
| NOTE: XFL523 Module is applicable only for V2.0.xx software. |
|
Active State (Excel 800)
The attribute "Active State" defines when a digital input/output is active. 1 means, that a digital input/output is active when a "logical 1 signal" is present
NOTE: "Active State" = 0 is not allowed/possible.
NOTE: The "Active State" attribute does not reflect the current condition of a digital datapoint.
Table 4. Active State for the digital input of XF823 and XFL823 modules
|
|
|
|
|
| digital input |
|
|
| ||
contact status |
|
| open |
|
|
| closed | ||||
CARE definition | NC |
| NO |
| NC |
| NO | ||||
(NC/NO system diagram) |
|
|
| ||||||||
|
|
|
|
|
|
|
|
|
|
| |
definition - in |
|
|
|
|
|
|
|
|
|
|
|
Editor attribute "Active State" | 1 |
|
| 1 |
|
| 1 |
|
| 1 |
|
(change Active/Passive State |
|
|
|
|
|
|
| ||||
|
|
|
|
|
|
|
|
|
|
| |
text) |
|
|
|
|
|
|
|
|
|
|
|
14 |