Startup Procedures
Parameter | Description |
|
| Action | Setting/ |
|
| Default | |||
|
|
|
|
| |
|
|
|
|
|
|
P0100 | Operation for Europe/N. | 1. | Press | to advance to | Setting = 1 |
| America |
| |||
| 0 = 50 Hz, kW (Europe) |
| parameter P0100. | Default = 0 or | |
|
|
|
| 1 | |
| factory default | 2 | Press | to access the | (Default is |
| 1 = 60 Hz, hp |
| parameter values level. | ||
|
|
|
| determined by | |
| (North America) | 3. | Press | to advance to 1. | the setting of |
|
| the motor | |||
| 2 = 60 Hz, kW |
|
|
| frequency and |
| (North America) | 4. | Press | to confirm and save | unit of |
|
| measurement | |||
|
|
| the P0100 = 1 setting. | ||
| The setting of Motor Frequency |
| DIP switches.) | ||
|
|
|
| ||
| and Unit of Measurement DIP |
|
|
|
|
| switch 2 overrides P0100 |
|
|
|
|
| settings 0 and 1. |
|
|
|
|
|
|
|
|
|
|
NOTES:
1. Stop the SED2 (that is, disable all pulses) before changing this parameter.
2. Changing P0100 resets all rated motor parameters as well as other parameters that depend on the rated motor parameters (such as P0340, Calculation of motor Parameters).
P0304* | Rated Motor Voltage | 1. | Press | to advance to | Setting = |
|
| Motor | |||
| 10V to 2000V. |
| parameter P0304. | nameplate | |
| Rated motor voltage (V) from | 2. | Press | to access the | Default = |
| motor nameplate. |
| parameter values level. | Varies by | |
|
|
|
|
| model |
|
| 3. | Press | to advance to |
|
|
|
| nominal voltage. |
| |
|
| 4. | Press | to confirm and save |
|
|
|
| the setting. |
|
|
|
|
|
|
|
|
* Motor related | parameters. |
|
|
|
|
Siemens Building Technologies, Inc. | 23 |