Siemens 125-3208 Parameter Description Action Setting Default, User Access Level

Page 30

SED2 VFD Electronic Bypass Option Operating Instructions

Parameter

Description

 

 

Action

Setting/

 

 

Default

 

 

 

 

 

 

 

 

 

 

 

P0003

User Access Level

1.

Press

to access parameter

Setting = 3

 

Allows you to access more

Default = 1

 

 

r0000 and to enter the SED2

 

parameters.

 

parameter mode.

 

 

1 = Standard

2.

Press

to advance to

 

 

2 = Extended

 

 

 

parameter P0003.

 

 

3 = Expert

3.

Press

to access the

 

 

 

 

 

 

 

parameter values level.

 

 

 

4.

Press

to advance to 3

 

 

 

 

(expert level).

 

 

 

5.

Press

to confirm and save

 

 

 

 

the P0003 = 3 setting.

 

 

 

 

 

 

 

NOTE:

 

 

 

 

 

Before starting quick commissioning, set P0003 = 3 to ensure all necessary parameters are available during quick commissioning.

P0010

Quick Commissioning

1.

Press

to access parameter

Setting = 1

 

 

 

 

0 = Ready to Run

 

r0000 and to enter the SED2

Default = 0

 

 

parameter mode.

 

 

 

 

 

 

 

 

1 = Quick Commissioning

 

 

 

 

 

 

30 = Factory Setting

2.

Repeatedly press

to

 

 

 

advance to parameter P0010.

 

 

 

3.

Press

to access the

 

 

 

 

parameter values level.

 

 

 

4.

Press

to advance to 1.

 

 

 

5.

Press

to confirm and save

 

 

 

 

the P0010 = 1 setting.

 

 

 

 

 

 

 

 

 

NOTES:

 

 

 

 

 

 

1. P0010 must always be set back to 0 before operating the motor.

 

 

 

2. If P3900 is greater than 0 on completion of commissioning, P0010 is automatically set back to 0.

22

Siemens Building Technologies, Inc.

Image 30
Contents SED2 VFD Electronic Bypass Options Page SED2 VFD Electronic Bypass Option Operating Instructions Page Service Statement Page Table of Contents Application Feature Setup Technical Specifications TroubleshootingManual Organization How to Use this ManualNotation Symbol Meaning Manual NotationsWhere To Send Comments Reference DocumentsSafety Instructions Electronic Bypass Option Overview General DescriptionFuses optional Controller Board Controller Board Inputs and OutputsContactors Keypad FunctionsPushbutton/Indicator DescriptionPushbutton/Indicator Description Output relay on the Controller boardDimensions and Weights Installation InstructionsMechanical Installation Environmental ConditionsBypass Dimensions in Inches Centimeters MountingFrame Sizes D and E Conduit Locations Viewed from Bottom Electrical Installation Bypass Power Circuit Routing of Power and Control Wiring For Frame Sizes a and B Disconnect Overload Ground Lug Switch Disconnect Overload Ground Lug Wire Max Installation Inspection Startup ProceduresSafety Precautions Power-OnSwitch Description Position DIP Switch Settings for E-Bypass FeaturesQuick Commissioning Parameter Description Action Setting Default User Access LevelQuick Commissioning Operation for Europe/N AmericaRated Motor Voltage Rated Motor cosPhi P308, or Rated Motor PowerRated Motor Current Rated Motor Efficiency P0309Rated Motor Frequency Rated Motor SpeedSelection of Command Source Start CommandMotor Overload Factor Speed Command Source Selection of FrequencySetpoint Minimum Motor Frequency Maximum Motor Frequency Ramp-up TimeRamp-down time End Quick CommissioningFlying Start Additional Parameter SettingsFlying Start R0000Motor Current Flying Start Search Rate Flying StartAutomatic Restart Automatic RestartSED2 VFD Electronic Bypass Option Operating Instructions Number of Restart Attempts Time to First RestartVdc Controller Restart Time IncrementPulse Frequency Motor Data Identification Motor Data IdentificationMotor Data Identification Reset to Factory Defaults P0970Required SED2 Parameter Settings Parameter SettingAuto Bypass without Interlock Application Feature SetupOverview DescriptionSettings Example SED2 SettingsInterlock Application Feature Setup Essential Services Wiring Example for InterlockWiring Example for Essential Services Interlock and Auto Bypass on VFD Fault Wiring Example for Interlock and Auto Bypass on VFD FaultDrive Specifications Description Technical SpecificationsSpecifications Description Electronic Bypass SpecificationsDrive Specifications Description SED2 VFD Electronic Bypass Operating InstructonsBasic Sanity Description Test Fault Code/Flashes TroubleshootingPower-on Initialization Failure Unit Fault Condition Basic Sanity Test Fault CodesOverride Jumper FusesFuse Replacement Information VFD0122R2 Troubleshooting Siemens Building Technologies, Inc