Siemens 125-3208 Rated Motor Current, Rated Motor Power, Rated Motor cosPhi P308, or

Page 32

SED2 VFD Electronic Bypass Option Operating Instructions

Parameter

Description

 

Action

Setting/

 

Default

 

 

 

 

 

 

 

 

 

 

 

P0305*

Rated Motor Current

1.

Press

to advance to

Setting =

 

 

Motor

 

0A to 10,000A.

 

parameter P0305.

nameplate

 

Rated motor current (A) from

2.

Press

to access the

Default =

 

motor nameplate.

 

parameter values level.

Varies by

 

 

 

 

 

model

 

 

3.

Press

to advance to

 

 

 

 

nominal current.

 

 

 

4.

Press

to confirm and save

 

 

 

 

the setting.

 

 

 

 

 

 

 

 

P0307*

Rated Motor Power

1.

Press

to advance to

Setting =

 

 

Motor

 

0 kW or hp to 200 kW or hp.

 

parameter P0307.

nameplate

 

Rated motor power (kW or hp)

2.

Press

to access the

Default =

 

from motor nameplate.

 

parameter values level.

Varies by

 

 

 

 

 

model

 

If P0100 =1 (60 Hz, hp, North

3.

Press

to advance to

(hp/voltage

 

dependent)

 

America), then motor power is in

 

 

nominal power.

 

 

hp.

 

 

 

 

4.

Press

to confirm and save

 

 

 

 

the setting.

 

 

 

 

 

 

 

 

P0308*, or

Rated Motor cosPhi (P308), or

1.

Press

to advance to

Setting =

P0309

Rated Motor Efficiency (P0309)

Motor

 

 

 

parameter P0308 or P0309.

nameplate

 

0.000 to 1.00 (P0308) or 0.0 to

 

 

 

P0308 Default

 

99.9 (P0309)

2

Press

to access the

 

 

= 0.00

 

 

 

parameter values level.

 

Rated motor cosPhi or motor

 

 

 

 

 

 

P0309 Default

 

efficiency from motor nameplate.

 

 

 

 

 

3.

Press

to advance to

=

 

If P0100 = 2 and P0307 = kW,

 

nominal cosPhi or motor

Varies by

 

P0308 displays.

 

efficiency.

 

model

 

 

 

 

 

(hp/voltage

 

If P0100 = 1 and P0307 = hp,

4.

Press

to confirm and save

dependent)

 

 

 

P0309 displays.

 

 

 

the setting.

 

 

 

 

 

 

 

 

P0309 = 100% corresponds to

 

 

 

 

 

super conducting.

 

 

 

 

 

NOTE:

 

 

 

 

 

This parameter is available when

 

 

 

 

 

P0003 = 3 and P0010 = 1.

 

 

 

 

 

 

 

 

 

 

* Motor related

parameters.

 

 

 

 

24

Siemens Building Technologies, Inc.

Image 32
Contents SED2 VFD Electronic Bypass Options Page SED2 VFD Electronic Bypass Option Operating Instructions Page Service Statement Page Table of Contents Application Feature Setup Technical Specifications TroubleshootingHow to Use this Manual Notation Symbol MeaningManual Organization Manual NotationsWhere To Send Comments Reference DocumentsSafety Instructions Fuses optional Electronic Bypass Option OverviewGeneral Description Controller Board Controller Board Inputs and OutputsContactors Keypad FunctionsPushbutton/Indicator DescriptionPushbutton/Indicator Description Output relay on the Controller boardInstallation Instructions Mechanical InstallationDimensions and Weights Environmental ConditionsBypass Dimensions in Inches Centimeters MountingFrame Sizes D and E Conduit Locations Viewed from Bottom Electrical Installation Bypass Power Circuit Routing of Power and Control Wiring For Frame Sizes a and B Disconnect Overload Ground Lug Switch Disconnect Overload Ground Lug Wire Max Startup Procedures Safety PrecautionsInstallation Inspection Power-OnSwitch Description Position DIP Switch Settings for E-Bypass FeaturesQuick Commissioning Quick Commissioning Parameter Description Action Setting DefaultUser Access Level Rated Motor Voltage Operation for Europe/NAmerica Rated Motor Power Rated Motor CurrentRated Motor cosPhi P308, or Rated Motor Efficiency P0309Rated Motor Frequency Rated Motor SpeedMotor Overload Factor Selection of Command SourceStart Command Setpoint Speed Command SourceSelection of Frequency Minimum Motor Frequency Maximum Motor Frequency Ramp-up TimeRamp-down time End Quick CommissioningAdditional Parameter Settings Flying StartFlying Start R0000Motor Current Flying Start Search Rate Flying StartAutomatic Restart Automatic RestartSED2 VFD Electronic Bypass Option Operating Instructions Number of Restart Attempts Time to First RestartVdc Controller Restart Time IncrementPulse Frequency Motor Data Identification Motor Data IdentificationMotor Data Identification Reset to Factory Defaults P0970Required SED2 Parameter Settings Parameter SettingApplication Feature Setup OverviewAuto Bypass without Interlock DescriptionSettings Example SED2 SettingsInterlock Application Feature Setup Essential Services Wiring Example for InterlockWiring Example for Essential Services Interlock and Auto Bypass on VFD Fault Wiring Example for Interlock and Auto Bypass on VFD FaultTechnical Specifications Specifications DescriptionDrive Specifications Description Electronic Bypass SpecificationsDrive Specifications Description SED2 VFD Electronic Bypass Operating InstructonsTroubleshooting Power-on Initialization Failure Unit Fault ConditionBasic Sanity Description Test Fault Code/Flashes Basic Sanity Test Fault CodesOverride Jumper FusesFuse Replacement Information VFD0122R2 Troubleshooting Siemens Building Technologies, Inc