Siemens 125-3208 operating instructions Rated Motor Frequency, Rated Motor Speed

Page 33

Startup Procedures

Parameter

Description

 

 

Action

Setting/

 

 

Default

 

 

 

 

 

 

 

 

 

 

 

P0310*

Rated Motor Frequency

1.

Press

to advance to

Setting =

 

 

Motor

 

 

 

parameter P0310.

 

12 Hz to 650 Hz

 

nameplate 60

 

 

 

 

 

Hz

 

Rated motor frequency (Hz) from

2.

Press

to access the

Default =

 

motor nameplate.

 

parameter values level.

 

 

 

 

 

50 Hz/60 Hz

 

Pole pair number is recalculated

3.

Press

to advance to

Default is

 

automatically if the parameter is

 

changed.

 

nominal frequency (60 Hz).

dependent on

 

 

 

 

 

the setting of

 

 

 

 

 

the motor

 

 

4.

Press

to confirm and save

frequency and

 

 

 

the setting.

unit of

 

 

 

 

 

measurement

 

 

 

 

 

DIP switches.

 

 

 

 

 

 

P0311*

Rated Motor Speed

1.

Press

to advance to

Setting =

 

 

Motor

 

 

 

parameter P0311.

 

0 to 40,000 1/min

 

nameplate

 

Rated motor speed (rpm) from

2.

Press

to access the

Default =

 

motor nameplate.

 

parameter values level.

Varies by

 

 

 

 

 

model

 

A setting of 0 causes an internal

3

Press

to advance to

 

 

calculation of this value.

 

 

 

 

nominal motor speed.

 

 

Vector control and V/f control

 

 

 

 

 

with speed controller require this

4.

Press

to confirm and save

 

 

value.

 

 

 

the setting.

 

 

 

 

 

 

Slip compensation in V/f control

 

 

 

 

 

requires this value for correct

 

 

 

 

 

operation.

 

 

 

 

 

Pole pair number is recalculated

 

 

 

 

 

automatically if the parameter is

 

 

 

 

 

changed.

 

 

 

 

 

 

 

 

 

 

* Motor related

parameters.

 

 

 

 

Siemens Building Technologies, Inc.

25

Image 33
Contents SED2 VFD Electronic Bypass Options Page SED2 VFD Electronic Bypass Option Operating Instructions Page Service Statement Page Table of Contents Technical Specifications Troubleshooting Application Feature SetupNotation Symbol Meaning How to Use this ManualManual Organization Manual NotationsReference Documents Where To Send CommentsSafety Instructions Electronic Bypass Option Overview General DescriptionFuses optional Controller Board Inputs and Outputs Controller BoardKeypad Functions ContactorsDescription Pushbutton/IndicatorOutput relay on the Controller board Pushbutton/Indicator DescriptionMechanical Installation Installation InstructionsDimensions and Weights Environmental ConditionsMounting Bypass Dimensions in Inches CentimetersFrame Sizes D and E Conduit Locations Viewed from Bottom Electrical Installation Bypass Power Circuit Routing of Power and Control Wiring For Frame Sizes a and B Disconnect Overload Ground Lug Switch Disconnect Overload Ground Lug Wire Max Safety Precautions Startup ProceduresInstallation Inspection Power-OnDIP Switch Settings for E-Bypass Features Switch Description PositionQuick Commissioning Parameter Description Action Setting Default User Access LevelQuick Commissioning Operation for Europe/N AmericaRated Motor Voltage Rated Motor Current Rated Motor PowerRated Motor cosPhi P308, or Rated Motor Efficiency P0309Rated Motor Speed Rated Motor FrequencySelection of Command Source Start CommandMotor Overload Factor Speed Command Source Selection of FrequencySetpoint Minimum Motor Frequency Ramp-up Time Maximum Motor FrequencyEnd Quick Commissioning Ramp-down timeFlying Start Additional Parameter SettingsFlying Start R0000Search Rate Flying Start Motor Current Flying StartAutomatic Restart Automatic RestartSED2 VFD Electronic Bypass Option Operating Instructions Time to First Restart Number of Restart AttemptsRestart Time Increment Vdc ControllerPulse Frequency Motor Data Identification Motor Data IdentificationMotor Data Identification P0970 Reset to Factory DefaultsParameter Setting Required SED2 Parameter SettingsOverview Application Feature SetupAuto Bypass without Interlock DescriptionExample SED2 Settings SettingsInterlock Application Feature Setup Wiring Example for Interlock Essential ServicesWiring Example for Essential Services Wiring Example for Interlock and Auto Bypass on VFD Fault Interlock and Auto Bypass on VFD FaultSpecifications Description Technical SpecificationsDrive Specifications Description Electronic Bypass SpecificationsSED2 VFD Electronic Bypass Operating Instructons Drive Specifications DescriptionPower-on Initialization Failure Unit Fault Condition TroubleshootingBasic Sanity Description Test Fault Code/Flashes Basic Sanity Test Fault CodesFuses Override JumperFuse Replacement Information VFD0122R2 Troubleshooting Siemens Building Technologies, Inc