Siemens 125-3208 operating instructions SED2 VFD Electronic Bypass Operating Instructons

Page 58

SED2 VFD Electronic Bypass Operating Instructons

 

Table 6. SED2 Specifications (Continued).

Drive Specifications

Description

Auxiliary supply 24V

Glavanically separated, unregulated auxiliary supply (18V to 32V) 100 mA

Overload capacity

110% for 60 seconds

Control method

Linear, parabolic and programmable V/f; and flux current control low-power

 

mode

PWM frequency

4k Hz to 16k Hz (adjustable in 2k Hz increments)

Fixed frequencies

15 programmable

Skip frequency bands

4 programmable

 

 

Setpoint resolution

0.01 Hz digital, 0.01 Hz serial, 10 bit analog

Digital inputs

6: fully programmable and scalable isolated digital inputs, switchable

(sink/source)

 

Analog inputs

2: 0 to 10 Vdc, 0/4 to 20 mA, can also be configured as digital inputs or

 

Ni 1000 input

Relay outputs

2: configurable 30 Vdc/5A (resistive), 250 Vac 2A (inductive)

 

 

Analog outputs

2: programmable (0/4 to 20 mA)

 

 

Serial interface

RS-485 Transmission rate: Up to 38.4k Baud

 

Protocols: Siemens, P1 and Johnson, N2;

Protection level

IP20: NEMA Type 1 with protective shield and gland plate installed

 

IP54: NEMA Type 12 (400V and 500V series only)

 

Temperature ranges

Operating: 14°F to 104°F (–10°C to 40°C)

Storage: –40°F to 158°F (–40°C to 70°C)

 

Humidity

95% rh, non-condensing

Operational altitudes

Up to 3280 ft (1000m) above sea level without de-rating

 

 

Protection features

Under-voltage, Over-voltage, Overload, Ground fault, Short circuit, Stall

 

prevention, Locked motor, Motor overtemperature l2t PTC, Over-temperature,

 

Parameter PIN protection

Standards

UL, cUL

NOTE: SED2 Compliance with EN61000-3-12:

From September 1st, 2005 all electrical apparatus covered by the EMC directive will have to comply with EN61000-3-12 “Limits for harmonic currents produced by equipment connected to public low voltage systems with input currents > 16A and =< 75 A per phase”.

Siemens variable speed drives of the product range SED2 (Micromaster 436) fulfil the requirements of the EN 61000-3-12 (without the need for external line reactors) regarding the THD values of Table 3 under the pre condition of Rsce > 190. The required PWHD values will not be achieved. Due to this fact it is recommended to apply for connection approval at the local electricity board.

The local electricity board will evaluate among many other data the content of the 5th harmonic current and the Line Power Factor "Lambda”, which is the ratio of active power and apparent power.

Siemens frequency inverters are optimized in design and operation characteristics regarding energy efficiency and less interference with line supplies.

50

Siemens Building Technologies, Inc.

Image 58
Contents SED2 VFD Electronic Bypass Options Page SED2 VFD Electronic Bypass Option Operating Instructions Page Service Statement Page Table of Contents Application Feature Setup Technical Specifications TroubleshootingManual Organization How to Use this ManualNotation Symbol Meaning Manual NotationsWhere To Send Comments Reference DocumentsSafety Instructions General Description Electronic Bypass Option OverviewFuses optional Controller Board Controller Board Inputs and OutputsContactors Keypad FunctionsPushbutton/Indicator DescriptionPushbutton/Indicator Description Output relay on the Controller boardDimensions and Weights Installation InstructionsMechanical Installation Environmental ConditionsBypass Dimensions in Inches Centimeters MountingFrame Sizes D and E Conduit Locations Viewed from Bottom Electrical Installation Bypass Power Circuit Routing of Power and Control Wiring For Frame Sizes a and B Disconnect Overload Ground Lug Switch Disconnect Overload Ground Lug Wire Max Installation Inspection Startup ProceduresSafety Precautions Power-OnSwitch Description Position DIP Switch Settings for E-Bypass FeaturesQuick Commissioning User Access Level Parameter Description Action Setting DefaultQuick Commissioning America Operation for Europe/NRated Motor Voltage Rated Motor cosPhi P308, or Rated Motor PowerRated Motor Current Rated Motor Efficiency P0309Rated Motor Frequency Rated Motor SpeedStart Command Selection of Command SourceMotor Overload Factor Selection of Frequency Speed Command SourceSetpoint Minimum Motor Frequency Maximum Motor Frequency Ramp-up TimeRamp-down time End Quick CommissioningFlying Start Additional Parameter SettingsFlying Start R0000Motor Current Flying Start Search Rate Flying StartAutomatic Restart Automatic RestartSED2 VFD Electronic Bypass Option Operating Instructions Number of Restart Attempts Time to First RestartVdc Controller Restart Time IncrementPulse Frequency Motor Data Identification Motor Data IdentificationMotor Data Identification Reset to Factory Defaults P0970Required SED2 Parameter Settings Parameter SettingAuto Bypass without Interlock Application Feature SetupOverview DescriptionSettings Example SED2 SettingsInterlock Application Feature Setup Essential Services Wiring Example for InterlockWiring Example for Essential Services Interlock and Auto Bypass on VFD Fault Wiring Example for Interlock and Auto Bypass on VFD FaultDrive Specifications Description Technical SpecificationsSpecifications Description Electronic Bypass SpecificationsDrive Specifications Description SED2 VFD Electronic Bypass Operating InstructonsBasic Sanity Description Test Fault Code/Flashes TroubleshootingPower-on Initialization Failure Unit Fault Condition Basic Sanity Test Fault CodesOverride Jumper FusesFuse Replacement Information VFD0122R2 Troubleshooting Siemens Building Technologies, Inc