Siemens 125-3208 Installation Instructions, Environmental Conditions, Mechanical Installation

Page 17

Installation Instructions

Installation Instructions

Environmental Conditions

Install the Electronic Bypass Option in a heated, indoor controlled environment that is free of moisture and conductive contaminants such as condensation and dust. The air entering the unit for ventilation/cooling must be clean and free from corrosive gases.

The ambient temperature must be between 14°F and 104°F (-10°C to 40°C) and the relative humidity must be 0% to 95% noncondensing. Do not mount unit in direct sunlight.

Mechanical Installation

Inspection

1.As you unpack the Electronic Bypass Option, check for shipping damage. In the event of damage, contact the transport company.

2.Locate the Electronic Bypass Option nameplate and confirm that the unit is configured to the installation requirements.

3.Verify the delivery is complete. If not, contact the supplier.

Dimensions and Weights

Figure 5 shows overall and mounting dimensions for the Electronic Bypass Option. Figures 6 through 8 show conduit locations.

Approximate weights are as follows.

 

 

 

 

 

 

 

Bypass

Weight lb (kg)

 

Frame Size

 

 

 

 

A

45

(20)

 

B

55

(25)

 

C

75

(34)

 

D

150 (68)

 

E

180 (82)

 

F

470

(213)

NOTE: Exact weight will be affected by actual horsepower/voltage and selected power options.

Siemens Building Technologies, Inc.

9

Image 17
Contents SED2 VFD Electronic Bypass Options Page SED2 VFD Electronic Bypass Option Operating Instructions Page Service Statement Page Table of Contents Technical Specifications Troubleshooting Application Feature SetupNotation Symbol Meaning How to Use this ManualManual Organization Manual NotationsReference Documents Where To Send CommentsSafety Instructions Fuses optional Electronic Bypass Option OverviewGeneral Description Controller Board Inputs and Outputs Controller BoardKeypad Functions ContactorsDescription Pushbutton/IndicatorOutput relay on the Controller board Pushbutton/Indicator DescriptionMechanical Installation Installation InstructionsDimensions and Weights Environmental ConditionsMounting Bypass Dimensions in Inches CentimetersFrame Sizes D and E Conduit Locations Viewed from Bottom Electrical Installation Bypass Power Circuit Routing of Power and Control Wiring For Frame Sizes a and B Disconnect Overload Ground Lug Switch Disconnect Overload Ground Lug Wire Max Safety Precautions Startup ProceduresInstallation Inspection Power-OnDIP Switch Settings for E-Bypass Features Switch Description PositionQuick Commissioning Quick Commissioning Parameter Description Action Setting DefaultUser Access Level Rated Motor Voltage Operation for Europe/NAmerica Rated Motor Current Rated Motor PowerRated Motor cosPhi P308, or Rated Motor Efficiency P0309Rated Motor Speed Rated Motor FrequencyMotor Overload Factor Selection of Command SourceStart Command Setpoint Speed Command SourceSelection of Frequency Minimum Motor Frequency Ramp-up Time Maximum Motor FrequencyEnd Quick Commissioning Ramp-down timeFlying Start Additional Parameter SettingsFlying Start R0000Search Rate Flying Start Motor Current Flying StartAutomatic Restart Automatic RestartSED2 VFD Electronic Bypass Option Operating Instructions Time to First Restart Number of Restart AttemptsRestart Time Increment Vdc ControllerPulse Frequency Motor Data Identification Motor Data IdentificationMotor Data Identification P0970 Reset to Factory DefaultsParameter Setting Required SED2 Parameter SettingsOverview Application Feature SetupAuto Bypass without Interlock DescriptionExample SED2 Settings SettingsInterlock Application Feature Setup Wiring Example for Interlock Essential ServicesWiring Example for Essential Services Wiring Example for Interlock and Auto Bypass on VFD Fault Interlock and Auto Bypass on VFD FaultSpecifications Description Technical SpecificationsDrive Specifications Description Electronic Bypass SpecificationsSED2 VFD Electronic Bypass Operating Instructons Drive Specifications DescriptionPower-on Initialization Failure Unit Fault Condition TroubleshootingBasic Sanity Description Test Fault Code/Flashes Basic Sanity Test Fault CodesFuses Override JumperFuse Replacement Information VFD0122R2 Troubleshooting Siemens Building Technologies, Inc