Startup Procedures
Additional Parameter Settings
NOTE: If Display Selection for r0000, parameter P0005 = 21 (actual frequency), then the BOP display alternately shows setpoint values and the actual value (0 Hz).
Flying Start
Parameter |
| Description |
|
| Action | Setting/ |
|
|
| Default | |||
|
|
|
|
|
| |
|
|
|
|
|
| |
P1200 | Flying Start | 1. | Press | to enter the SED2 | Minimum = 0 | |
|
|
|
| |||
| Starts SED2 into a spinning |
| parameter mode and to display | Default = 0 | ||
|
| r0000. |
| |||
| motor by rapidly changing the |
|
|
| ||
|
|
|
|
| ||
| output frequency of the SED2 |
|
|
| Maximum = 6 | |
| until the actual motor speed is | 2. | Press | to advance to |
| |
| found. Then, the motor runs up | Suggested = 2 | ||||
|
| parameter P1200. | ||||
| to setpoint using the normal |
| ||||
|
|
|
|
| ||
| ramp time. |
|
|
|
| |
| 0 | = Flying start disabled. | 3. | Press | to access the |
|
|
| parameter values level. |
| |||
| 1 | = Flying start is always active, |
|
|
|
|
| start in direction of setpoint. |
|
|
|
| |
| 2 | = Flying start is active, if power | 4. | Press | to advance to |
|
| on, fault, OFF2, start in direction |
| desired setting. |
| ||
| of setpoint. |
|
|
|
| |
| 3 | = Flying start is active if fault, | 5. | Press | to confirm and save |
|
| OFF2, start in direction of |
| ||||
| setpoint. |
| the setting. |
| ||
| 4 | = Flying start is always active, |
|
|
|
|
| only in direction of setpoint. |
|
|
|
| |
| 5 | = Flying start is active if power |
|
|
|
|
| on, fault, OFF2, only in direction |
|
|
|
| |
| of setpoint. |
|
|
|
| |
| 6 | = Flying start is active if fault, |
|
|
|
|
| OFF2, only in direction of |
|
|
|
| |
| setpoint. |
|
|
|
| |
|
|
|
|
|
|
|
NOTES:
1. Flying start is useful for motors with high inertia loads.
2. Settings 1 through 3 search in both directions. Settings 4 through 6 search only in the direction of the setpoint.
3. Flying start must be used in cases where the motor may still be turning (such as after a brief input power break) or can be driven by the load. Otherwise, overcurrent trips occur.
4. If the SED2 faults on F0002 (overvoltage) on a start command, flying start may have to be optimized by reducing the values in P1203 and P1202.
Siemens Building Technologies, Inc. | 31 |