Siemens 125-3208 operating instructions Additional Parameter Settings, Flying Start, R0000

Page 39

Startup Procedures

Additional Parameter Settings

NOTE: If Display Selection for r0000, parameter P0005 = 21 (actual frequency), then the BOP display alternately shows setpoint values and the actual value (0 Hz).

Flying Start

Parameter

 

Description

 

 

Action

Setting/

 

 

 

Default

 

 

 

 

 

 

 

 

 

 

 

 

P1200

Flying Start

1.

Press

to enter the SED2

Minimum = 0

 

 

 

 

 

Starts SED2 into a spinning

 

parameter mode and to display

Default = 0

 

 

r0000.

 

 

motor by rapidly changing the

 

 

 

 

 

 

 

 

 

output frequency of the SED2

 

 

 

Maximum = 6

 

until the actual motor speed is

2.

Press

to advance to

 

 

found. Then, the motor runs up

Suggested = 2

 

 

parameter P1200.

 

to setpoint using the normal

 

 

 

 

 

 

 

ramp time.

 

 

 

 

 

0

= Flying start disabled.

3.

Press

to access the

 

 

 

parameter values level.

 

 

1

= Flying start is always active,

 

 

 

 

 

start in direction of setpoint.

 

 

 

 

 

2

= Flying start is active, if power

4.

Press

to advance to

 

 

on, fault, OFF2, start in direction

 

desired setting.

 

 

of setpoint.

 

 

 

 

 

3

= Flying start is active if fault,

5.

Press

to confirm and save

 

 

OFF2, start in direction of

 

 

setpoint.

 

the setting.

 

 

4

= Flying start is always active,

 

 

 

 

 

only in direction of setpoint.

 

 

 

 

 

5

= Flying start is active if power

 

 

 

 

 

on, fault, OFF2, only in direction

 

 

 

 

 

of setpoint.

 

 

 

 

 

6

= Flying start is active if fault,

 

 

 

 

 

OFF2, only in direction of

 

 

 

 

 

setpoint.

 

 

 

 

 

 

 

 

 

 

 

NOTES:

1. Flying start is useful for motors with high inertia loads.

2. Settings 1 through 3 search in both directions. Settings 4 through 6 search only in the direction of the setpoint.

3. Flying start must be used in cases where the motor may still be turning (such as after a brief input power break) or can be driven by the load. Otherwise, overcurrent trips occur.

4. If the SED2 faults on F0002 (overvoltage) on a start command, flying start may have to be optimized by reducing the values in P1203 and P1202.

Siemens Building Technologies, Inc.

31

Image 39
Contents SED2 VFD Electronic Bypass Options Page SED2 VFD Electronic Bypass Option Operating Instructions Page Service Statement Page Table of Contents Technical Specifications Troubleshooting Application Feature SetupManual Notations How to Use this ManualNotation Symbol Meaning Manual OrganizationReference Documents Where To Send CommentsSafety Instructions Electronic Bypass Option Overview General DescriptionFuses optional Controller Board Inputs and Outputs Controller BoardKeypad Functions ContactorsDescription Pushbutton/IndicatorOutput relay on the Controller board Pushbutton/Indicator DescriptionEnvironmental Conditions Installation InstructionsMechanical Installation Dimensions and WeightsMounting Bypass Dimensions in Inches CentimetersFrame Sizes D and E Conduit Locations Viewed from Bottom Electrical Installation Bypass Power Circuit Routing of Power and Control Wiring For Frame Sizes a and B Disconnect Overload Ground Lug Switch Disconnect Overload Ground Lug Wire Max Power-On Startup ProceduresSafety Precautions Installation InspectionDIP Switch Settings for E-Bypass Features Switch Description PositionQuick Commissioning Parameter Description Action Setting Default User Access LevelQuick Commissioning Operation for Europe/N AmericaRated Motor Voltage Rated Motor Efficiency P0309 Rated Motor PowerRated Motor Current Rated Motor cosPhi P308, orRated Motor Speed Rated Motor FrequencySelection of Command Source Start CommandMotor Overload Factor Speed Command Source Selection of FrequencySetpoint Minimum Motor Frequency Ramp-up Time Maximum Motor FrequencyEnd Quick Commissioning Ramp-down timeR0000 Additional Parameter SettingsFlying Start Flying StartSearch Rate Flying Start Motor Current Flying StartAutomatic Restart Automatic RestartSED2 VFD Electronic Bypass Option Operating Instructions Time to First Restart Number of Restart AttemptsRestart Time Increment Vdc ControllerPulse Frequency Motor Data Identification Motor Data IdentificationMotor Data Identification P0970 Reset to Factory DefaultsParameter Setting Required SED2 Parameter SettingsDescription Application Feature SetupOverview Auto Bypass without InterlockExample SED2 Settings SettingsInterlock Application Feature Setup Wiring Example for Interlock Essential ServicesWiring Example for Essential Services Wiring Example for Interlock and Auto Bypass on VFD Fault Interlock and Auto Bypass on VFD FaultElectronic Bypass Specifications Technical SpecificationsSpecifications Description Drive Specifications DescriptionSED2 VFD Electronic Bypass Operating Instructons Drive Specifications DescriptionBasic Sanity Test Fault Codes TroubleshootingPower-on Initialization Failure Unit Fault Condition Basic Sanity Description Test Fault Code/FlashesFuses Override JumperFuse Replacement Information VFD0122R2 Troubleshooting Siemens Building Technologies, Inc