Siemens 125-3208 operating instructions Bypass Power Circuit

Page 21

Installation Instructions

VFD0160R1

 

 

OPTIONAL SUPPLEMENTARY

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER FUSES - MAIN SHORT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CIRCUIT PROTECTION BY OTHERS

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DISC1

(SEE NOTE 1)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

FU1

 

 

 

 

 

 

 

 

 

M1

 

 

 

 

L1

1L1

 

2L1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

POWER

(T1)

(L1)

 

 

 

 

 

 

 

 

 

 

(5)

(6)

 

 

 

L2

1L2

 

 

2L2

 

 

 

 

 

 

 

 

 

 

 

SUPPLY

 

 

 

 

 

 

 

 

(3)

(4)

 

 

 

3 PHASE

(T2)

(L2)

 

 

 

 

 

 

 

 

 

 

 

 

 

60 Hz

L3

1L3

 

 

2L3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

(T3)

(L3)

OPTIONAL

 

OPTIONAL

 

 

 

OPTIONAL

(1)

(2)

 

 

 

GND

 

 

 

 

 

 

 

 

 

 

 

DRIVE INPUT

INPUT LINE

 

VFD

 

OUTPUT LOAD

 

 

 

 

 

 

GND

GND

CONTACTOR

REACTOR

 

 

 

REACTOR

 

 

 

 

 

 

M3 3L1

 

 

 

 

 

 

 

 

M2

OL1 1T1

 

 

 

LUG

 

 

 

R

L1

U

U1

U

 

 

 

 

 

(2)

(1)

 

A1

A2

 

A1

A2

(1)

(2)

(T1)

 

 

 

 

 

 

 

 

 

 

AC MOTOR

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3L2

 

 

 

S

 

 

V1

V

 

 

1T2

 

 

 

 

 

 

 

 

L2

V

 

 

M

(CUSTOMER

 

 

 

(4)

(3)

 

B1

B2

 

B1

B2

(3)

(4)

(T2)

 

 

 

 

 

 

 

 

SUPPLIED)

 

 

 

 

3L3

 

 

 

T

L3

W

W1

W

 

 

1T3

 

 

 

 

 

(6)

(5)

 

C1

C2

 

C1

C2

(5)

(6)

(T3)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

 

 

 

 

 

 

1L1

1L2

 

 

 

 

 

 

 

 

 

 

 

GND

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

LUG

TO

STEP-DOWN

CONTROL

TRANSFORMER

NOTES:

1.Branch circuit protection to be provided by installer, per UL508A, if not provided with drive.

2.For bypass operation, modify these drive parameters: P0702[0] and P0702[1] = 3,

P0748 = Digital Out 1 Reverse ().

3.Control and communication wiring should be 300V UL minimum.

4.Communication wiring should be run with maximum separation possible from all other wiring.

5.Essential service mode operates the motor full speed (bypass) with no protection for the motor or system.

6.Ensure that automatic bypass will not damage the system before activating.

7.See Table 8 for proper fuse and wire sizes.

8.See Siemens Publication No. 125-3201for SED2 input/output control signal wiring details.

Figure 9. E-Bypass Power Circuit.

Siemens Building Technologies, Inc.

13

Image 21
Contents SED2 VFD Electronic Bypass Options Page SED2 VFD Electronic Bypass Option Operating Instructions Page Service Statement Page Table of Contents Technical Specifications Troubleshooting Application Feature SetupNotation Symbol Meaning How to Use this ManualManual Organization Manual NotationsReference Documents Where To Send CommentsSafety Instructions Electronic Bypass Option Overview General DescriptionFuses optional Controller Board Inputs and Outputs Controller BoardKeypad Functions ContactorsDescription Pushbutton/IndicatorOutput relay on the Controller board Pushbutton/Indicator DescriptionMechanical Installation Installation InstructionsDimensions and Weights Environmental ConditionsMounting Bypass Dimensions in Inches CentimetersFrame Sizes D and E Conduit Locations Viewed from Bottom Electrical Installation Bypass Power Circuit Routing of Power and Control Wiring For Frame Sizes a and B Disconnect Overload Ground Lug Switch Disconnect Overload Ground Lug Wire Max Safety Precautions Startup ProceduresInstallation Inspection Power-OnDIP Switch Settings for E-Bypass Features Switch Description PositionQuick Commissioning Parameter Description Action Setting Default User Access LevelQuick Commissioning Operation for Europe/N AmericaRated Motor Voltage Rated Motor Current Rated Motor PowerRated Motor cosPhi P308, or Rated Motor Efficiency P0309Rated Motor Speed Rated Motor FrequencySelection of Command Source Start CommandMotor Overload Factor Speed Command Source Selection of FrequencySetpoint Minimum Motor Frequency Ramp-up Time Maximum Motor FrequencyEnd Quick Commissioning Ramp-down timeFlying Start Additional Parameter SettingsFlying Start R0000Search Rate Flying Start Motor Current Flying StartAutomatic Restart Automatic RestartSED2 VFD Electronic Bypass Option Operating Instructions Time to First Restart Number of Restart AttemptsRestart Time Increment Vdc ControllerPulse Frequency Motor Data Identification Motor Data IdentificationMotor Data Identification P0970 Reset to Factory DefaultsParameter Setting Required SED2 Parameter SettingsOverview Application Feature SetupAuto Bypass without Interlock DescriptionExample SED2 Settings SettingsInterlock Application Feature Setup Wiring Example for Interlock Essential ServicesWiring Example for Essential Services Wiring Example for Interlock and Auto Bypass on VFD Fault Interlock and Auto Bypass on VFD FaultSpecifications Description Technical SpecificationsDrive Specifications Description Electronic Bypass SpecificationsSED2 VFD Electronic Bypass Operating Instructons Drive Specifications DescriptionPower-on Initialization Failure Unit Fault Condition TroubleshootingBasic Sanity Description Test Fault Code/Flashes Basic Sanity Test Fault CodesFuses Override JumperFuse Replacement Information VFD0122R2 Troubleshooting Siemens Building Technologies, Inc