Siemens 125-3208 operating instructions VFD0122R2

Page 62

SED2 VFD Electronic Bypass Option Operating Instructons

VFD0122R2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VFD DI#3

 

5

Remote Start/Stop

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VFD DI#2

 

8

Interlock Start Confirm

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Isolated 0V

 

28

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VFD

 

Bypass

 

 

 

 

 

 

 

 

VFD DI#1

 

6

OK to Run

 

 

 

 

 

 

 

 

 

 

 

 

Input

Input

Hand

 

 

 

 

 

 

 

 

 

COM

 

25

SED2 Relay

 

 

 

 

 

 

 

 

 

 

 

 

On/Off

Contactor

Start

 

 

 

 

VFD DO#2, NO

 

24

SED2

 

 

 

 

 

 

 

Bypass

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COM

 

 

22

SED2 Fault

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VFD Contactor

 

 

 

 

 

 

 

 

 

 

VFD DO#1, NO

 

 

21

VFD

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enable

Overload

Remote

VFD INTERFACE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Start

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Relay

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Output

 

VFD DO#1, NO

 

1

J4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Contactor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COM

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Motor

 

VFD DO#2, NO

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

STOP

AutoBypassEnabled

VFDFault

COM

 

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

RESET

 

SafetyFault

VFD DI#1

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

EssentialServices

OverloadFault

Isolated 0V

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VFD DI#2

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Enable Commanded Proofed

 

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INTERLOCKSTARTLOGIC

 

VFD DI#3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NOTE:

 

KEYPAD INTERFACE

 

6

J3

 

 

 

 

 

 

 

 

 

 

 

 

 

3-Contactor

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Keypad

 

Ribbon Cable for Keypad

 

 

 

 

 

 

 

 

 

 

MCU

 

 

 

 

Shown.

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Pushbuttons and Indicators

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Basic Sanity Test LED

 

J8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Factory Use Only

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

ON

OFF

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DIP Switch

SW1

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

J2

 

CONTROLLER

 

 

 

 

 

 

 

 

 

Remote Start Input

 

1

 

 

 

 

 

 

 

 

 

 

 

 

 

BOARD

 

 

 

 

 

 

 

 

 

 

 

Remote Safety #1

 

2

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

DIGITAL

Remote Safety #2

 

5

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

INPUTS

Interlock Start

 

6

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

7

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Essential Services

 

8

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

9

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Overload Trigger

 

10

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

11

 

 

 

 

 

 

 

 

 

 

 

 

HIGH VOLTAGE

 

DIGITAL

 

 

 

12

J1

 

 

 

 

 

 

 

 

 

 

 

 

 

Programmable Output, NO

 

13

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OUTPUTS

 

COM

 

14

 

 

 

 

 

 

 

 

 

 

 

 

FUSE

FUSE

 

 

 

NC

 

15

 

 

 

 

 

 

 

 

 

 

 

 

F3

F4

 

 

 

VFD Fault, NO

 

16

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

COM

 

17

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NC

 

18

 

 

 

 

 

 

TRANSFORMER

 

 

 

 

 

 

Drive Select, COM

 

19

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

NO

 

20

 

 

 

 

 

 

 

 

 

 

 

 

HIGH VOLTAGE/

 

 

 

Bypass Select, COM

 

21

 

 

 

 

 

 

 

 

 

 

 

 

 

120V

 

 

 

NO

 

22

 

 

 

 

 

 

 

 

 

 

F1

 

 

 

 

 

Bypass Running, COM

 

23

 

 

 

 

 

 

 

 

 

 

 

STEP-DOWN

 

 

 

NO

 

24

 

 

 

 

 

 

 

 

 

 

 

 

POWER

 

 

 

Overload Fault, COM

 

25

 

 

 

 

 

 

 

 

J7

 

 

 

 

 

NO

 

26

 

 

 

 

 

 

 

 

 

 

TRANSFORMER

 

 

 

Override Jumper

 

 

J6

 

9

10

11

12

13 14

 

J5

 

 

 

 

 

 

 

 

8

 

3 2 1

 

 

 

 

 

 

 

 

 

 

7

6

5

4

 

3

2

1

 

FUSE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTACTOR

 

 

 

 

Bypass Contactor COM

 

 

 

 

Earth Ground

F2

 

 

 

 

 

 

Bypass Contactor NO Not Used

 

 

 

 

 

 

 

 

 

 

 

Output Contactor NO ISO IN6B

Output Contactor NC 120V Neutral

 

 

 

 

120V Neutral

 

 

 

 

 

CONTROLS

 

 

 

 

 

 

120V Hot

 

 

 

 

 

 

 

 

Input Contactor

 

120V Neutral

120V Hot 120V Neutral

 

120V Neutral

 

 

INPUT

 

 

 

 

 

 

 

ISO IN6A

120V Hot

 

CONTACTOR

 

 

 

 

 

 

 

 

OUTPUT

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTACTOR

 

 

 

 

CUSTOMER

 

 

 

 

 

 

 

 

 

 

 

BYPASS

 

 

 

 

SUPPLIED

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3-PHASE

 

 

 

 

 

 

 

 

 

 

 

 

 

CONTACTOR

 

 

 

 

POWER

 

 

INPUT DEVICE

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

OF VFD WITH

ELECTRONIC BYPASS

MOTOR

Figure 15. Controller Board Inputs and Outputs.

54

Siemens Building Technologies, Inc.

Image 62
Contents SED2 VFD Electronic Bypass Options Page SED2 VFD Electronic Bypass Option Operating Instructions Page Service Statement Page Table of Contents Application Feature Setup Technical Specifications TroubleshootingManual Organization How to Use this ManualNotation Symbol Meaning Manual NotationsWhere To Send Comments Reference DocumentsSafety Instructions Fuses optional Electronic Bypass Option OverviewGeneral Description Controller Board Controller Board Inputs and OutputsContactors Keypad FunctionsPushbutton/Indicator DescriptionPushbutton/Indicator Description Output relay on the Controller boardDimensions and Weights Installation InstructionsMechanical Installation Environmental ConditionsBypass Dimensions in Inches Centimeters MountingFrame Sizes D and E Conduit Locations Viewed from Bottom Electrical Installation Bypass Power Circuit Routing of Power and Control Wiring For Frame Sizes a and B Disconnect Overload Ground Lug Switch Disconnect Overload Ground Lug Wire Max Installation Inspection Startup ProceduresSafety Precautions Power-OnSwitch Description Position DIP Switch Settings for E-Bypass FeaturesQuick Commissioning Quick Commissioning Parameter Description Action Setting DefaultUser Access Level Rated Motor Voltage Operation for Europe/NAmerica Rated Motor cosPhi P308, or Rated Motor PowerRated Motor Current Rated Motor Efficiency P0309Rated Motor Frequency Rated Motor SpeedMotor Overload Factor Selection of Command SourceStart Command Setpoint Speed Command SourceSelection of Frequency Minimum Motor Frequency Maximum Motor Frequency Ramp-up TimeRamp-down time End Quick CommissioningFlying Start Additional Parameter SettingsFlying Start R0000Motor Current Flying Start Search Rate Flying StartAutomatic Restart Automatic RestartSED2 VFD Electronic Bypass Option Operating Instructions Number of Restart Attempts Time to First RestartVdc Controller Restart Time IncrementPulse Frequency Motor Data Identification Motor Data IdentificationMotor Data Identification Reset to Factory Defaults P0970Required SED2 Parameter Settings Parameter SettingAuto Bypass without Interlock Application Feature SetupOverview DescriptionSettings Example SED2 SettingsInterlock Application Feature Setup Essential Services Wiring Example for InterlockWiring Example for Essential Services Interlock and Auto Bypass on VFD Fault Wiring Example for Interlock and Auto Bypass on VFD FaultDrive Specifications Description Technical SpecificationsSpecifications Description Electronic Bypass SpecificationsDrive Specifications Description SED2 VFD Electronic Bypass Operating InstructonsBasic Sanity Description Test Fault Code/Flashes TroubleshootingPower-on Initialization Failure Unit Fault Condition Basic Sanity Test Fault CodesOverride Jumper FusesFuse Replacement Information VFD0122R2 Troubleshooting Siemens Building Technologies, Inc