Siemens 125-3208 operating instructions Interlock and Auto Bypass on VFD Fault

Page 56

SED2 VFD Electronic Bypass Option Operating Instructions

Interlock and Auto Bypass on VFD Fault

Description

Interlock and Auto Bypass features are both active. Auto bypass now becomes auto bypass on a VFD fault only (bypass is initiated by the SED2 Fault and this digital output must always be programmed to VFD fault).

All set-up is the same as with Interlock (see the Interlock section in Application Feature Setup).

Hand bypass is now initiated by SED2 Fault.

The Programmable Output is still used to initiate the proofing sequence.

Settings

Interlock and Auto Bypass requires that Controller board DIP Switches 2 and 3 are set ON.

NOTE: During operation, the Auto Bypass Enabled indicator is on steady. Also, the Interlock Start Logic Enabled indicator is on steady.

ON

1 2 3 4 5

VFD0120R1

 

 

 

 

5

 

 

 

 

 

 

 

4

 

 

 

 

 

 

 

 

3

 

 

 

 

 

2

 

 

ON

 

 

 

 

1

 

 

 

 

SW1

OFF

See the Auto Bypass without Interlock on VFD Relay Output and Interlock sections for parameter settings.

Wiring Example for Interlock and Auto Bypass on VFD Fault

Customer

Proof

DIGITAL INPUTS

Remote Start Input

Remote Safety #1

Remote Safety #2

Interlock Start

1

2

3

4

5

6

7

8

9

J2

Power to Customer Device

VFD0115R2

DIGITAL OUTPUTS

Programmable Output, NO COM NC

10

11

12

13J1

48

Siemens Building Technologies, Inc.

Image 56
Contents SED2 VFD Electronic Bypass Options Page SED2 VFD Electronic Bypass Option Operating Instructions Page Service Statement Page Table of Contents Application Feature Setup Technical Specifications TroubleshootingHow to Use this Manual Notation Symbol MeaningManual Organization Manual NotationsWhere To Send Comments Reference DocumentsSafety Instructions Fuses optional Electronic Bypass Option OverviewGeneral Description Controller Board Controller Board Inputs and OutputsContactors Keypad FunctionsPushbutton/Indicator DescriptionPushbutton/Indicator Description Output relay on the Controller boardInstallation Instructions Mechanical InstallationDimensions and Weights Environmental ConditionsBypass Dimensions in Inches Centimeters MountingFrame Sizes D and E Conduit Locations Viewed from Bottom Electrical Installation Bypass Power Circuit Routing of Power and Control Wiring For Frame Sizes a and B Disconnect Overload Ground Lug Switch Disconnect Overload Ground Lug Wire Max Startup Procedures Safety PrecautionsInstallation Inspection Power-OnSwitch Description Position DIP Switch Settings for E-Bypass FeaturesQuick Commissioning Quick Commissioning Parameter Description Action Setting DefaultUser Access Level Rated Motor Voltage Operation for Europe/NAmerica Rated Motor Power Rated Motor CurrentRated Motor cosPhi P308, or Rated Motor Efficiency P0309Rated Motor Frequency Rated Motor SpeedMotor Overload Factor Selection of Command SourceStart Command Setpoint Speed Command SourceSelection of Frequency Minimum Motor Frequency Maximum Motor Frequency Ramp-up TimeRamp-down time End Quick CommissioningAdditional Parameter Settings Flying StartFlying Start R0000Motor Current Flying Start Search Rate Flying StartAutomatic Restart Automatic RestartSED2 VFD Electronic Bypass Option Operating Instructions Number of Restart Attempts Time to First RestartVdc Controller Restart Time IncrementPulse Frequency Motor Data Identification Motor Data IdentificationMotor Data Identification Reset to Factory Defaults P0970Required SED2 Parameter Settings Parameter SettingApplication Feature Setup OverviewAuto Bypass without Interlock DescriptionSettings Example SED2 SettingsInterlock Application Feature Setup Essential Services Wiring Example for InterlockWiring Example for Essential Services Interlock and Auto Bypass on VFD Fault Wiring Example for Interlock and Auto Bypass on VFD FaultTechnical Specifications Specifications DescriptionDrive Specifications Description Electronic Bypass SpecificationsDrive Specifications Description SED2 VFD Electronic Bypass Operating InstructonsTroubleshooting Power-on Initialization Failure Unit Fault ConditionBasic Sanity Description Test Fault Code/Flashes Basic Sanity Test Fault CodesOverride Jumper FusesFuse Replacement Information VFD0122R2 Troubleshooting Siemens Building Technologies, Inc