SED2 VFD Electronic Bypass Option Operating Instructions
Parameter | Description |
|
| Action | Setting/ |
|
| Default | |||
|
|
|
|
| |
|
|
|
|
|
|
P1213 | Restart Time Increment | 1. | Press | to enter the SED2 | Minimum = 0 |
|
| Default = 30 | |||
|
|
| parameter mode and to display | ||
| Selects the amount (seconds) |
| Maximum = | ||
| that the restart time is |
| r0000. |
| 1000 |
| incremented for each restart of |
|
|
| Suggested = |
| the SED2 if P1210 automatic | 2. | Press | to advance to | |
| restart is activated. | 10 | |||
|
| parameter P1213. | |||
|
|
|
| ||
|
| 3. | Press | to access the |
|
|
|
| parameter values level. |
| |
|
| 4. | Press | to advance to |
|
|
|
| desired value. |
| |
|
| 5. | Press | to confirm and save |
|
|
|
| the setting. |
| |
|
|
|
|
|
|
Vdc Controller
Parameter | Description |
|
| Action | Setting/ |
|
| Default | |||
|
|
|
|
| |
|
|
|
|
|
|
P1240 | Configuration of Vdc | 1. | Press | to enter the SED2 | Minimum = 0 |
| Controller | Default = 1 | |||
|
|
| parameter mode and to display | Maximum = 3 | |
|
|
| r0000. |
| |
| Enables/disabled Vdc controller. |
|
|
| |
|
|
|
|
| |
| The Vdc controller dynamically | 2. | Press | to advance to |
|
| controls the DC link voltage to |
| parameter P1240. |
| |
| prevent overvoltage trips on high |
|
|
|
|
| inertia systems. | 3. | Press | to access the |
|
|
|
| |||
|
| parameter values level. |
| ||
|
|
|
|
| |
| link voltage (r0026) within limits. | 4. | Press | to advance to |
|
|
|
| |||
| 0 = Vdc controller disabled |
| desired value. |
| |
|
|
|
|
| |
| 1 = |
|
|
|
|
| 2 = Reserved | 5. | Press | to confirm and save |
|
| 3 = Reserved |
| |||
|
| the setting. |
| ||
|
|
|
| ||
|
|
|
|
|
|
36 | Siemens Building Technologies, Inc. |