Siemens 125-3208 operating instructions Vdc Controller, Restart Time Increment

Page 44

SED2 VFD Electronic Bypass Option Operating Instructions

Parameter

Description

 

 

Action

Setting/

 

 

Default

 

 

 

 

 

 

 

 

 

 

 

P1213

Restart Time Increment

1.

Press

to enter the SED2

Minimum = 0

 

 

Default = 30

 

 

 

parameter mode and to display

 

Selects the amount (seconds)

 

Maximum =

 

that the restart time is

 

r0000.

 

1000

 

incremented for each restart of

 

 

 

Suggested =

 

the SED2 if P1210 automatic

2.

Press

to advance to

 

restart is activated.

10

 

 

parameter P1213.

 

 

 

 

 

 

3.

Press

to access the

 

 

 

 

parameter values level.

 

 

 

4.

Press

to advance to

 

 

 

 

desired value.

 

 

 

5.

Press

to confirm and save

 

 

 

 

the setting.

 

 

 

 

 

 

 

Vdc Controller

Parameter

Description

 

 

Action

Setting/

 

 

Default

 

 

 

 

 

 

 

 

 

 

 

P1240

Configuration of Vdc

1.

Press

to enter the SED2

Minimum = 0

 

Controller

Default = 1

 

 

 

parameter mode and to display

Maximum = 3

 

 

 

r0000.

 

 

Enables/disabled Vdc controller.

 

 

 

 

 

 

 

 

 

The Vdc controller dynamically

2.

Press

to advance to

 

 

controls the DC link voltage to

 

parameter P1240.

 

 

prevent overvoltage trips on high

 

 

 

 

 

inertia systems.

3.

Press

to access the

 

 

 

 

 

Vdc-max automatically increases

 

parameter values level.

 

 

ramp-down times to keep the DC

 

 

 

 

 

link voltage (r0026) within limits.

4.

Press

to advance to

 

 

 

 

 

0 = Vdc controller disabled

 

desired value.

 

 

 

 

 

 

 

1 = Vdc-max controller enabled

 

 

 

 

 

2 = Reserved

5.

Press

to confirm and save

 

 

3 = Reserved

 

 

 

the setting.

 

 

 

 

 

 

 

 

 

 

 

36

Siemens Building Technologies, Inc.

Image 44
Contents SED2 VFD Electronic Bypass Options Page SED2 VFD Electronic Bypass Option Operating Instructions Page Service Statement Page Table of Contents Application Feature Setup Technical Specifications TroubleshootingHow to Use this Manual Notation Symbol MeaningManual Organization Manual NotationsWhere To Send Comments Reference DocumentsSafety Instructions Fuses optional Electronic Bypass Option OverviewGeneral Description Controller Board Controller Board Inputs and OutputsContactors Keypad FunctionsPushbutton/Indicator DescriptionPushbutton/Indicator Description Output relay on the Controller boardInstallation Instructions Mechanical InstallationDimensions and Weights Environmental ConditionsBypass Dimensions in Inches Centimeters MountingFrame Sizes D and E Conduit Locations Viewed from Bottom Electrical Installation Bypass Power Circuit Routing of Power and Control Wiring For Frame Sizes a and B Disconnect Overload Ground Lug Switch Disconnect Overload Ground Lug Wire Max Startup Procedures Safety PrecautionsInstallation Inspection Power-OnSwitch Description Position DIP Switch Settings for E-Bypass FeaturesQuick Commissioning Quick Commissioning Parameter Description Action Setting DefaultUser Access Level Rated Motor Voltage Operation for Europe/NAmerica Rated Motor Power Rated Motor CurrentRated Motor cosPhi P308, or Rated Motor Efficiency P0309Rated Motor Frequency Rated Motor SpeedMotor Overload Factor Selection of Command SourceStart Command Setpoint Speed Command SourceSelection of Frequency Minimum Motor Frequency Maximum Motor Frequency Ramp-up TimeRamp-down time End Quick CommissioningAdditional Parameter Settings Flying StartFlying Start R0000Motor Current Flying Start Search Rate Flying StartAutomatic Restart Automatic RestartSED2 VFD Electronic Bypass Option Operating Instructions Number of Restart Attempts Time to First RestartVdc Controller Restart Time IncrementPulse Frequency Motor Data Identification Motor Data IdentificationMotor Data Identification Reset to Factory Defaults P0970Required SED2 Parameter Settings Parameter SettingApplication Feature Setup OverviewAuto Bypass without Interlock DescriptionSettings Example SED2 SettingsInterlock Application Feature Setup Essential Services Wiring Example for InterlockWiring Example for Essential Services Interlock and Auto Bypass on VFD Fault Wiring Example for Interlock and Auto Bypass on VFD FaultTechnical Specifications Specifications DescriptionDrive Specifications Description Electronic Bypass SpecificationsDrive Specifications Description SED2 VFD Electronic Bypass Operating InstructonsTroubleshooting Power-on Initialization Failure Unit Fault ConditionBasic Sanity Description Test Fault Code/Flashes Basic Sanity Test Fault CodesOverride Jumper FusesFuse Replacement Information VFD0122R2 Troubleshooting Siemens Building Technologies, Inc