Siemens 125-3208 operating instructions Motor Data Identification

Page 46

SED2 VFD Electronic Bypass Option Operating Instructions

Motor Data Identification

Parameter

Description

 

 

Action

 

Setting/

 

 

 

 

 

 

Default

 

 

 

 

 

 

 

P1910

Motor Data Identification

1.

Press

to enter the SED2

Minimum = 0

 

 

 

 

Performs stator resistance

 

parameter mode and to display

Maximum = 20

 

measuring.

 

r0000.

 

 

 

 

 

 

 

 

 

 

0 = Disabled.

2.

Press

to advance to

 

 

1 = Identification of Rs with

 

parameter P1910.

 

 

 

 

 

 

 

 

 

parameter change.

3.

Press

to access the

 

 

2 = Identification of Rs without

 

 

 

parameter values level.

 

 

parameter change.

 

 

 

 

 

 

3 = Identification of the saturation

4.

Press

to advance to setting

 

 

characteristic with parameter

 

P1910=1. Press

to confirm

 

 

change.

 

 

 

 

 

and save the setting.

 

 

 

20 = Set voltage vector.

 

When P1910=1, Alarm A0541

 

 

 

 

 

 

 

 

(motor data identification active)

 

 

 

 

is output and internally P0340 is

 

 

 

 

set to 3.

 

 

 

 

 

 

Initiate the measuring operation

 

 

 

 

with a continuous (steady-state)

 

 

 

 

ON command.

 

 

 

 

 

The motor aligns itself and

 

 

 

 

current flows through it.

 

 

 

 

Diagnostics are possible using

 

 

 

 

r0069 (CO: phase current).

 

 

 

 

On completion of the motor

 

 

 

 

data identification routine,

 

 

 

 

P1910 resets (P1910=0, motor

 

 

 

 

data identification routine

 

 

 

 

inhibited) and Alarm A0541 is

 

 

 

 

cleared (deleted).

 

 

 

 

5. To set the SED2 into a defined

 

 

 

 

state, issue an OFF1 command.

 

 

 

 

 

 

 

 

38

Siemens Building Technologies, Inc.

Image 46
Contents SED2 VFD Electronic Bypass Options Page SED2 VFD Electronic Bypass Option Operating Instructions Page Service Statement Page Table of Contents Application Feature Setup Technical Specifications TroubleshootingManual Organization How to Use this ManualNotation Symbol Meaning Manual NotationsWhere To Send Comments Reference DocumentsSafety Instructions General Description Electronic Bypass Option OverviewFuses optional Controller Board Controller Board Inputs and OutputsContactors Keypad FunctionsPushbutton/Indicator DescriptionPushbutton/Indicator Description Output relay on the Controller boardDimensions and Weights Installation InstructionsMechanical Installation Environmental ConditionsBypass Dimensions in Inches Centimeters MountingFrame Sizes D and E Conduit Locations Viewed from Bottom Electrical Installation Bypass Power Circuit Routing of Power and Control Wiring For Frame Sizes a and B Disconnect Overload Ground Lug Switch Disconnect Overload Ground Lug Wire Max Installation Inspection Startup ProceduresSafety Precautions Power-OnSwitch Description Position DIP Switch Settings for E-Bypass FeaturesQuick Commissioning User Access Level Parameter Description Action Setting DefaultQuick Commissioning America Operation for Europe/NRated Motor Voltage Rated Motor cosPhi P308, or Rated Motor PowerRated Motor Current Rated Motor Efficiency P0309Rated Motor Frequency Rated Motor SpeedStart Command Selection of Command SourceMotor Overload Factor Selection of Frequency Speed Command SourceSetpoint Minimum Motor Frequency Maximum Motor Frequency Ramp-up TimeRamp-down time End Quick CommissioningFlying Start Additional Parameter SettingsFlying Start R0000Motor Current Flying Start Search Rate Flying StartAutomatic Restart Automatic RestartSED2 VFD Electronic Bypass Option Operating Instructions Number of Restart Attempts Time to First RestartVdc Controller Restart Time IncrementPulse Frequency Motor Data Identification Motor Data IdentificationMotor Data Identification Reset to Factory Defaults P0970Required SED2 Parameter Settings Parameter SettingAuto Bypass without Interlock Application Feature SetupOverview DescriptionSettings Example SED2 SettingsInterlock Application Feature Setup Essential Services Wiring Example for InterlockWiring Example for Essential Services Interlock and Auto Bypass on VFD Fault Wiring Example for Interlock and Auto Bypass on VFD FaultDrive Specifications Description Technical SpecificationsSpecifications Description Electronic Bypass SpecificationsDrive Specifications Description SED2 VFD Electronic Bypass Operating InstructonsBasic Sanity Description Test Fault Code/Flashes TroubleshootingPower-on Initialization Failure Unit Fault Condition Basic Sanity Test Fault CodesOverride Jumper FusesFuse Replacement Information VFD0122R2 Troubleshooting Siemens Building Technologies, Inc