Siemens 125-3208 operating instructions Number of Restart Attempts, Time to First Restart

Page 43

Startup Procedures

Parameter

Description

 

 

Action

Setting/

 

 

Default

 

 

 

 

 

 

 

 

 

 

 

P1211

Number of Restart Attempts

1.

Press

to enter the SED2

Minimum = 0

 

 

Default = 3

 

 

 

parameter mode and to display

 

Specifies the number of times

 

Maximum = 10

 

SED2 will attempt to restart after

 

r0000.

 

 

 

supply power brownout or fault, if

 

 

 

Suggested =

 

P1210 automatic restart is

2.

Press

to advance to

10

 

activated.

 

 

 

parameter P1211.

 

 

 

 

 

 

 

3.

Press

to access the

 

 

 

 

parameter values level.

 

 

 

4.

Press

to advance to

 

 

 

 

desired value.

 

 

 

5.

Press

to confirm and save

 

 

 

 

the setting.

 

 

 

 

 

 

 

P1212

Time to First Restart

1.

Press

to enter the SED2

Minimum = 0

 

 

Default = 3

 

 

 

parameter mode and to display

 

Selects the time (seconds)

 

Maximum = 10

 

before the SED2 is restarted for

 

r0000.

 

 

 

 

 

 

 

 

the first time if P1210 automatic

 

 

 

Suggested =

 

restart is activated.

2.

Press

to advance to

10

 

 

 

 

 

 

parameter P1212.

 

 

 

3.

Press

to access the

 

 

 

 

parameter values level.

 

 

 

4.

Press

to advance to

 

 

 

 

desired value.

 

 

 

5.

Press

to confirm and save

 

 

 

 

the setting.

 

 

 

 

 

 

 

Siemens Building Technologies, Inc.

35

Image 43
Contents SED2 VFD Electronic Bypass Options Page SED2 VFD Electronic Bypass Option Operating Instructions Page Service Statement Page Table of Contents Technical Specifications Troubleshooting Application Feature SetupManual Notations How to Use this ManualNotation Symbol Meaning Manual OrganizationReference Documents Where To Send CommentsSafety Instructions General Description Electronic Bypass Option OverviewFuses optional Controller Board Inputs and Outputs Controller BoardKeypad Functions ContactorsDescription Pushbutton/IndicatorOutput relay on the Controller board Pushbutton/Indicator DescriptionEnvironmental Conditions Installation InstructionsMechanical Installation Dimensions and WeightsMounting Bypass Dimensions in Inches CentimetersFrame Sizes D and E Conduit Locations Viewed from Bottom Electrical Installation Bypass Power Circuit Routing of Power and Control Wiring For Frame Sizes a and B Disconnect Overload Ground Lug Switch Disconnect Overload Ground Lug Wire Max Power-On Startup ProceduresSafety Precautions Installation InspectionDIP Switch Settings for E-Bypass Features Switch Description PositionQuick Commissioning User Access Level Parameter Description Action Setting DefaultQuick Commissioning America Operation for Europe/NRated Motor Voltage Rated Motor Efficiency P0309 Rated Motor PowerRated Motor Current Rated Motor cosPhi P308, orRated Motor Speed Rated Motor FrequencyStart Command Selection of Command SourceMotor Overload Factor Selection of Frequency Speed Command SourceSetpoint Minimum Motor Frequency Ramp-up Time Maximum Motor FrequencyEnd Quick Commissioning Ramp-down timeR0000 Additional Parameter SettingsFlying Start Flying StartSearch Rate Flying Start Motor Current Flying StartAutomatic Restart Automatic RestartSED2 VFD Electronic Bypass Option Operating Instructions Time to First Restart Number of Restart AttemptsRestart Time Increment Vdc ControllerPulse Frequency Motor Data Identification Motor Data IdentificationMotor Data Identification P0970 Reset to Factory DefaultsParameter Setting Required SED2 Parameter SettingsDescription Application Feature SetupOverview Auto Bypass without InterlockExample SED2 Settings SettingsInterlock Application Feature Setup Wiring Example for Interlock Essential ServicesWiring Example for Essential Services Wiring Example for Interlock and Auto Bypass on VFD Fault Interlock and Auto Bypass on VFD FaultElectronic Bypass Specifications Technical SpecificationsSpecifications Description Drive Specifications DescriptionSED2 VFD Electronic Bypass Operating Instructons Drive Specifications DescriptionBasic Sanity Test Fault Codes TroubleshootingPower-on Initialization Failure Unit Fault Condition Basic Sanity Description Test Fault Code/FlashesFuses Override JumperFuse Replacement Information VFD0122R2 Troubleshooting Siemens Building Technologies, Inc