SED2 VFD Electronic Bypass Option Operating Instructions
Electrical Installation
See Figure 9 for all Electronic Bypass Option wiring.
1.Route shielded twisted pair (recommended wire type) cable, 24 gauge minimum control wiring in conduit through knockout and into housing (Figures 10 through 12). Connect control wiring per
NOTES:
•Terminate shield at control device.
•Control wiring is 12 to 26 AWG and tightening torque is 5
2.If applicable, route communications wiring (P1) in conduit through knockout and into housing (Figures 10 through 12). Continue to route communications wiring to SED2 and terminate per SED2 VFD Startup, Operation, and Maintenance Manual
3.Route motor wiring in conduit through knockout and into housing (Figures 10 through 12). Connect motor wiring to motor overload and ground lug. See Tables 1 through 4 for wire sizes and tightening torques.
4.Route input power wiring in conduit through knockout and into housing (Figures 10 through 12). Connect input power wiring to disconnect switch and ground lug or to circuit breaker and ground lug. See Tables 1 through 4 for wire sizes and tightening torques.
12 | Siemens Building Technologies, Inc. |