Siemens 125-3208 Troubleshooting, Power-on Initialization Failure Unit Fault Condition

Page 59

Troubleshooting

Troubleshooting

WARNING:

Always disconnect all power sources before opening the SED2 Electronic Bypass Option.

Power-on Initialization Failure

(Unit Fault Condition)

During power-on initialization, a unit fault condition occurs if the Electronic Bypass Option did not pass the basic sanity test. Rather than flash normally, the basic sanity test indicator pauses, flashes a fault code, and then repeats.

Table 7 shows the fault codes. For example, if the basic sanity test indicator flashes three times rapidly, pauses, and then repeats, this means that there is a keypad failure.

 

Table 7. Basic Sanity Test Fault Codes.

Basic Sanity

Description

Test Fault

Code/Flashes

 

1

Non-Volatile Memory Failure

 

 

2

Flash Memory Failure (CRC, cyclic redundancy check)

 

 

3

Keypad Failure

 

 

4

RAM Memory Failure (not used)

 

 

5

EEPROM Read error

 

 

6

EEPROM Write Failure

 

 

7

Runtime Flash Failure (CRC, cyclic redundancy check)

 

 

8

Main Program Failed (or hangs)

 

 

It may be possible to recover from the unit fault condition by simply attempting a power down/up of the Electronic Bypass Option. If the unit fault condition still exists, replace the Controller board.

CAUTION:

When powering down/up the Electronic Bypass Option, power down the unit, wait 5 minutes, and then power up the unit.

Siemens Building Technologies, Inc.

51

Image 59
Contents SED2 VFD Electronic Bypass Options Page SED2 VFD Electronic Bypass Option Operating Instructions Page Service Statement Page Table of Contents Technical Specifications Troubleshooting Application Feature SetupManual Notations How to Use this ManualNotation Symbol Meaning Manual OrganizationReference Documents Where To Send CommentsSafety Instructions Fuses optional Electronic Bypass Option OverviewGeneral Description Controller Board Inputs and Outputs Controller BoardKeypad Functions ContactorsDescription Pushbutton/IndicatorOutput relay on the Controller board Pushbutton/Indicator DescriptionEnvironmental Conditions Installation InstructionsMechanical Installation Dimensions and WeightsMounting Bypass Dimensions in Inches CentimetersFrame Sizes D and E Conduit Locations Viewed from Bottom Electrical Installation Bypass Power Circuit Routing of Power and Control Wiring For Frame Sizes a and B Disconnect Overload Ground Lug Switch Disconnect Overload Ground Lug Wire Max Power-On Startup ProceduresSafety Precautions Installation InspectionDIP Switch Settings for E-Bypass Features Switch Description PositionQuick Commissioning Quick Commissioning Parameter Description Action Setting DefaultUser Access Level Rated Motor Voltage Operation for Europe/NAmerica Rated Motor Efficiency P0309 Rated Motor PowerRated Motor Current Rated Motor cosPhi P308, orRated Motor Speed Rated Motor FrequencyMotor Overload Factor Selection of Command SourceStart Command Setpoint Speed Command SourceSelection of Frequency Minimum Motor Frequency Ramp-up Time Maximum Motor FrequencyEnd Quick Commissioning Ramp-down timeR0000 Additional Parameter SettingsFlying Start Flying StartSearch Rate Flying Start Motor Current Flying StartAutomatic Restart Automatic RestartSED2 VFD Electronic Bypass Option Operating Instructions Time to First Restart Number of Restart AttemptsRestart Time Increment Vdc ControllerPulse Frequency Motor Data Identification Motor Data IdentificationMotor Data Identification P0970 Reset to Factory DefaultsParameter Setting Required SED2 Parameter SettingsDescription Application Feature SetupOverview Auto Bypass without InterlockExample SED2 Settings SettingsInterlock Application Feature Setup Wiring Example for Interlock Essential ServicesWiring Example for Essential Services Wiring Example for Interlock and Auto Bypass on VFD Fault Interlock and Auto Bypass on VFD FaultElectronic Bypass Specifications Technical SpecificationsSpecifications Description Drive Specifications DescriptionSED2 VFD Electronic Bypass Operating Instructons Drive Specifications DescriptionBasic Sanity Test Fault Codes TroubleshootingPower-on Initialization Failure Unit Fault Condition Basic Sanity Description Test Fault Code/FlashesFuses Override JumperFuse Replacement Information VFD0122R2 Troubleshooting Siemens Building Technologies, Inc