Siemens 125-3208 operating instructions Automatic Restart

Page 41

Startup Procedures

Automatic Restart

CAUTION:

Settings 2 through 7 can cause the motor to restart unexpectedly.

Parameter

Description

 

 

Action

Setting/

 

 

Default

 

 

 

 

 

 

 

 

 

 

 

P1210

Automatic Restart

1.

Press

to enter the SED2

Minimum = 0

 

 

Default = 1

 

Enables SED2 restart after a

 

parameter mode and to display

 

 

Maximum:

 

 

r0000.

 

 

supply power break or after a

 

 

 

 

 

 

5=Control Board

 

fault.

 

 

 

 

 

 

 

Version 1.20

 

 

 

 

 

 

P1210 = 0, Disabled:

2.

Press

to advance to

or earlier

 

 

parameter P1210.

6=Control Board

 

Automatic restart is disabled.

 

 

 

 

 

Version 1.30

 

 

 

 

 

 

P1210 = 1, Trip reset after power on

3.

Press

to access the

7=Control Board

 

(P1211 disabled:

Version 1.40

 

The inverter will acknowledge

 

parameter values level.

Suggested:

 

(reset) faults; that is, it will reset a

 

 

 

 

 

 

 

3=Control Board

 

fault when it is re-applied. This

 

 

 

 

means the inverter must be fully

4.

Press

to advance to

Version 1.20

 

powered down, a brownout is not

 

desired setting.

or earlier

 

sufficient. The inverter will not run

 

6=Control Board

 

 

 

 

 

until the ON command has been

 

 

 

Version 1.30

 

toggled.

5.

Press

to confirm and save

7=Control Board

 

P1210 = 2, Restart after supply

Version 1.40

 

 

the setting.

 

power blackout (P1211 disabled):

 

 

 

 

 

The inverter will acknowledge the

 

 

 

 

 

fault F0003 at power on after

 

 

 

 

 

blackout and will restart the drive.

 

 

 

 

 

It is necessary that the ON

 

 

 

 

 

command is wired via digital input

 

 

 

 

 

(DIN).

 

 

 

 

 

P1210 = 3, Restart after brownout or

 

 

 

 

 

fault (P1211 enabled):

 

 

 

 

 

For these settings it is

 

 

 

 

 

fundamental that the drive only

 

 

 

 

 

restarts if it has been in a RUN

 

 

 

 

 

state at the time of the faults

 

 

 

 

 

(F0003, etc.). The inverter will

 

 

 

 

 

acknowledge the fault and will

 

 

 

 

 

restart the drive after a blackout

 

 

 

 

 

or brownwout. It is necessary that

 

 

 

 

 

the ON command is wired via

 

 

 

 

 

digital input (DIN).

 

 

 

 

 

 

 

 

 

 

Siemens Building Technologies, Inc.

33

Image 41
Contents SED2 VFD Electronic Bypass Options Page SED2 VFD Electronic Bypass Option Operating Instructions Page Service Statement Page Table of Contents Technical Specifications Troubleshooting Application Feature SetupNotation Symbol Meaning How to Use this ManualManual Organization Manual NotationsReference Documents Where To Send CommentsSafety Instructions Fuses optional Electronic Bypass Option OverviewGeneral Description Controller Board Inputs and Outputs Controller BoardKeypad Functions ContactorsDescription Pushbutton/IndicatorOutput relay on the Controller board Pushbutton/Indicator DescriptionMechanical Installation Installation InstructionsDimensions and Weights Environmental ConditionsMounting Bypass Dimensions in Inches CentimetersFrame Sizes D and E Conduit Locations Viewed from Bottom Electrical Installation Bypass Power Circuit Routing of Power and Control Wiring For Frame Sizes a and B Disconnect Overload Ground Lug Switch Disconnect Overload Ground Lug Wire Max Safety Precautions Startup ProceduresInstallation Inspection Power-OnDIP Switch Settings for E-Bypass Features Switch Description PositionQuick Commissioning Quick Commissioning Parameter Description Action Setting DefaultUser Access Level Rated Motor Voltage Operation for Europe/NAmerica Rated Motor Current Rated Motor PowerRated Motor cosPhi P308, or Rated Motor Efficiency P0309Rated Motor Speed Rated Motor FrequencyMotor Overload Factor Selection of Command SourceStart Command Setpoint Speed Command SourceSelection of Frequency Minimum Motor Frequency Ramp-up Time Maximum Motor FrequencyEnd Quick Commissioning Ramp-down timeFlying Start Additional Parameter SettingsFlying Start R0000Search Rate Flying Start Motor Current Flying StartAutomatic Restart Automatic RestartSED2 VFD Electronic Bypass Option Operating Instructions Time to First Restart Number of Restart AttemptsRestart Time Increment Vdc ControllerPulse Frequency Motor Data Identification Motor Data IdentificationMotor Data Identification P0970 Reset to Factory DefaultsParameter Setting Required SED2 Parameter SettingsOverview Application Feature SetupAuto Bypass without Interlock DescriptionExample SED2 Settings SettingsInterlock Application Feature Setup Wiring Example for Interlock Essential ServicesWiring Example for Essential Services Wiring Example for Interlock and Auto Bypass on VFD Fault Interlock and Auto Bypass on VFD FaultSpecifications Description Technical SpecificationsDrive Specifications Description Electronic Bypass SpecificationsSED2 VFD Electronic Bypass Operating Instructons Drive Specifications DescriptionPower-on Initialization Failure Unit Fault Condition TroubleshootingBasic Sanity Description Test Fault Code/Flashes Basic Sanity Test Fault CodesFuses Override JumperFuse Replacement Information VFD0122R2 Troubleshooting Siemens Building Technologies, Inc