Siemens 125-3208 operating instructions Disconnect Overload Ground Lug Switch

Page 23

Installation Instructions

Table 1. Wire Sizes and Tightening Torques for E-Bypass with 208V Drive.

 

 

 

 

 

Circuit Breaker

Disconnect

 

 

Overload

 

Ground Lug

 

 

 

 

 

Switch

 

 

 

 

 

Bypass

 

 

 

 

 

 

 

 

 

 

 

 

 

Part

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

Max

 

 

Frame

HP

kW

Amps

 

Torque,

 

Torque,

 

Torque,

 

 

Torque,

Number

Wire

Wire

Wire

Range,

Wire

Size

 

 

 

Backup

 

 

 

 

 

Size *

lb-in

Size *

lb-in

Size *

lb-in

Amps

Fuse,

Size *

lb-in

 

 

 

 

 

(Nm)

(Nm)

(Nm)

(Nm)

 

 

 

 

 

 

 

 

 

Amps

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

VBE10.5----

A

0.5

0.37

2.3

14-10

32 (3.6)

18-10

13 -

18-14

7 - 10.3

1.8 - 2.5

10

14-2

35 (4)

Cu

(1.5

-

1.7)

(8 - 1.2)

 

 

 

 

 

 

 

 

 

 

 

 

VBE10.7----

A

0.7

0.55

3.0

14-10

32 (3.6)

18-10

13 -

18-14

7 - 10.3

2.2 - 3.2

12

14-2

35 (4)

Cu

(1.5

-

1.7)

(8 - 1.2)

 

 

 

 

 

 

 

 

 

 

 

 

VBE11.0----

A

1.0

0.75

3.9

14-10

32 (3.6)

18-10

13

-

17

18-14

7 - 10.3

2.8 - 4

16

14-2

35 (4)

Cu

(1.5

-

1.7)

(8 - 1.2)

 

 

 

 

 

 

 

 

 

 

 

 

VBE11.5----

B

1.5

1.1

5.5

14-10

32 (3.6)

18-10

13 -

18-14

7 - 10.3

4.5 - 6.3

25

14-2

35 (4)

Cu

(1.5

-

1.7)

(8 - 1.2)

 

 

 

 

 

 

 

 

 

 

 

 

VBE12.0----

B

2.0

1.5

7.4

14-10

32 (3.6)

18-10

13 -

18-14

7 - 10.3

5.5 - 8.0

30

14-2

35 (4)

Cu

(1.5

-

1.7)

(8 - 1.2)

 

 

 

 

 

 

 

 

 

 

 

 

VBE13.0----

B

3.0

2.2

10.4

14-10

32 (3.6)

18-10

13

-

17

18-14

7 - 10.3

7 - 10

40

14-2

35 (4)

Cu

(1.5

-

1.7)

(8 - 1.2)

 

 

 

 

 

 

 

 

 

 

 

 

VBE15.0----

C

5.0

4.0

16.7

14-10

32 (3.6)

14-8

17

-

22

14-10

18

- 22

14 - 20

80

14-2

35 (4)

Cu

(1.9

-

2.5)

(2 - 25)

 

 

 

 

 

 

 

 

 

 

 

 

VBE17.5----

C

7.5

5.5

22.0

14-10

20 - 60

14-8

17

-

22

14-10

18

- 22

20 - 25

100

14-2

35 (4)

Cu

(2.2 - 6.8)

(1.9

-

2.5)

(2 - 25)

 

 

 

 

 

 

 

 

 

 

 

VBE110.----

C

10

7.5

28

10-1/0

20 - 60

14-8

17

-

22

18-3

27

- 40

22 - 32

125

14-2

35 (4)

Cu

(2.2 - 6.8)

(1.9 -

2.5)

(3.1

- 4.5)

VBE115.----

D

15

11.0

42

10-1/0

20 - 60

14-6

22

-

27

18-3

27

- 40

40 - 50

200

14-2

35 (4)

Cu

(2.2 - 6.8)

(2.5 -

3.1)

(3.1

- 4.5)

VBE120.----

D

20

15.0

54

10-1/0

20 - 60

12-1

22

-

27

10-1/0

36

- 53

45 - 63

250

14-2

35 (4)

Cu

(2.2 - 6.8)

(2.5

-

3.1)

(4.1 - 6)

 

 

 

 

 

 

 

 

 

 

 

VBE125.----

D

25

18.5

68

3-3/0-3

80 (9)

12-1

22

-

27

10-1/0

36

- 53

57 - 75

300

14-2

35 (4)

Cu

(2.5

-

3.1)

(4.1 - 6)

 

 

 

 

 

 

 

 

 

 

 

 

VBE130.----

E

30

22.0

80

3-3/0-3

80 (9)

12-1

22

-

27

10-1/0

36

- 53

70 - 90

350

14-2

35 (4)

Cu

(2.5

-

3.1)

(4.1 - 6)

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6 - 350

120 - 275

 

22

-

27

 

124

- 210

 

 

 

 

VBE140.----

F

40

30.0

104

kcmil

(14 - 31.1)

12-1

(2.5 -

3.1)

6-3/0

(14 - 23.7)

50 - 200

800

14-2/0

50 (5.6)

 

 

 

 

 

Cu

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6 - 350

120 - 275

6 - 350

120 -

275

 

124

- 210

 

 

 

 

VBE150.----

F

50

37.0

130

kcmil

(14 - 31.1)

kcmil

(13.5 -

31.1)

6-3/0

(14 - 23.7)

50 - 200

800

14-2/0

50 (5.6)

 

 

 

 

 

Cu

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

6 - 350

120 - 275

6 - 350

120 -

275

 

124

- 210

 

 

 

 

VBE160.----

F

60

45.0

154

kcmil

(14 - 31.1)

kcmil

(13.5 -

31.1)

6-3/0

(14 - 23.7)

50 - 200

800

14-2/0

50 (5.6)

 

 

 

 

 

Cu

 

 

 

 

 

 

 

 

 

 

 

 

*Wire size is AWG unless noted otherwise. Use Copper (Cu) wire that is rated 167°F (75°C) minimum 600 Vac.

Siemens Building Technologies, Inc.

15

Image 23
Contents SED2 VFD Electronic Bypass Options Page SED2 VFD Electronic Bypass Option Operating Instructions Page Service Statement Page Table of Contents Technical Specifications Troubleshooting Application Feature SetupManual Notations How to Use this ManualNotation Symbol Meaning Manual OrganizationReference Documents Where To Send CommentsSafety Instructions Fuses optional Electronic Bypass Option OverviewGeneral Description Controller Board Inputs and Outputs Controller BoardKeypad Functions ContactorsDescription Pushbutton/IndicatorOutput relay on the Controller board Pushbutton/Indicator DescriptionEnvironmental Conditions Installation InstructionsMechanical Installation Dimensions and WeightsMounting Bypass Dimensions in Inches CentimetersFrame Sizes D and E Conduit Locations Viewed from Bottom Electrical Installation Bypass Power Circuit Routing of Power and Control Wiring For Frame Sizes a and B Disconnect Overload Ground Lug Switch Disconnect Overload Ground Lug Wire Max Power-On Startup ProceduresSafety Precautions Installation InspectionDIP Switch Settings for E-Bypass Features Switch Description PositionQuick Commissioning Quick Commissioning Parameter Description Action Setting DefaultUser Access Level Rated Motor Voltage Operation for Europe/NAmerica Rated Motor Efficiency P0309 Rated Motor PowerRated Motor Current Rated Motor cosPhi P308, orRated Motor Speed Rated Motor FrequencyMotor Overload Factor Selection of Command SourceStart Command Setpoint Speed Command SourceSelection of Frequency Minimum Motor Frequency Ramp-up Time Maximum Motor FrequencyEnd Quick Commissioning Ramp-down timeR0000 Additional Parameter SettingsFlying Start Flying StartSearch Rate Flying Start Motor Current Flying StartAutomatic Restart Automatic RestartSED2 VFD Electronic Bypass Option Operating Instructions Time to First Restart Number of Restart AttemptsRestart Time Increment Vdc ControllerPulse Frequency Motor Data Identification Motor Data IdentificationMotor Data Identification P0970 Reset to Factory DefaultsParameter Setting Required SED2 Parameter SettingsDescription Application Feature SetupOverview Auto Bypass without InterlockExample SED2 Settings SettingsInterlock Application Feature Setup Wiring Example for Interlock Essential ServicesWiring Example for Essential Services Wiring Example for Interlock and Auto Bypass on VFD Fault Interlock and Auto Bypass on VFD FaultElectronic Bypass Specifications Technical SpecificationsSpecifications Description Drive Specifications DescriptionSED2 VFD Electronic Bypass Operating Instructons Drive Specifications DescriptionBasic Sanity Test Fault Codes TroubleshootingPower-on Initialization Failure Unit Fault Condition Basic Sanity Description Test Fault Code/FlashesFuses Override JumperFuse Replacement Information VFD0122R2 Troubleshooting Siemens Building Technologies, Inc