SED2 VFD Electronic Bypass Option Operating Instructions
Parameter | Description |
|
| Action | Setting/ |
|
| Default | |||
|
|
|
|
| |
|
|
|
|
|
|
P0640 | Motor Overload Factor | 1. | Press | to advance to | Setting = |
|
| As applicable | |||
|
|
| parameter P0640. | ||
| 10% to 400% |
|
| ||
|
|
|
| Default = 110 | |
|
|
|
|
| |
| Limited to the maximum SED2 | 2. | Press | to access the |
|
| output current rating, or to 400% |
| parameter values level. |
| |
| of the rated current (P0305), |
|
|
|
|
| whichever is lower. | 3. | Press | to advance to |
|
|
|
| |||
| NOTE: |
| desired value. |
| |
| This parameter is available when |
|
|
|
|
| P0003 = 3 and | 4. | Press | to confirm and save |
|
| P0010 = 1. |
| |||
|
|
| the setting. |
| |
|
|
|
|
|
|
P0700(0)** | Selection of Command Source | 1. | Press | to advance to | Setting = 2 |
| (Start Command) |
| |||
|
|
| parameter P0700. | Default = 2 | |
| Selects the command source as |
|
|
| |
|
|
|
|
| |
| follows: | 2. | Press | to access the |
|
|
|
| |||
| 0 = Factory default setting |
| parameter indexes. |
| |
|
|
|
|
| |
| 1 = BOP (keypad) | 3. | Press | to advance to index |
|
| 2 = Terminal digital input |
| [0], IN000, AUTO. |
| |
|
|
|
|
| |
| 4 = USS on BOP link (AOP) | 4. | Press | to confirm index |
|
|
| selection. |
|
| |
|
|
|
|
| |
| 5 = USS on COM link |
|
|
|
|
| 6 = CB (Communications board | 5. | Press | to advance to 2. |
|
|
|
|
|
| |
| or module) on COM link (P1/N2) | 6. | Press | to confirm and save |
|
|
|
| |||
|
|
| the setting. |
| |
|
|
|
|
|
|
NOTE:
Changing this parameter resets (to default) all settings on the selected item. For example, changing from 1 to 2 resets all digital inputs to default settings.
** Parameters have two index settings: IN000 = Auto and IN001 = Hand.
26 | Siemens Building Technologies, Inc. |