SED2 VFD Electronic Bypass Option Operating Instructions
Parameter | Description |
|
| Action | Setting/ |
|
| Default | |||
|
|
|
|
| |
|
|
|
|
|
|
P1121 |
| 1. | Press | to advance to | Site Setting |
|
|
| |||
| 0s to 650s |
| parameter P1121. | Default = 30 | |
|
|
|
| ||
|
| 2. | Press | to access the | Typical fan = |
|
|
| parameter values level. | 120s | |
|
| 3. | Press | to advance it desired | Typical pump = |
|
| 30s | |||
|
|
| value. |
|
|
|
| 4. | Press | to confirm and save |
|
|
|
| the setting. |
| |
|
|
|
|
|
|
NOTES:
1. Setting the
2. If using an external frequency setpoint with set ramp rates (such as from a PLC), achieve optimum SED2 performance by setting ramp times (P1120 and P1121) slightly shorter than those of the PLC.
P3900 | End Quick Commissioning | 1. | Press | to advance to | Setting = 1 |
|
|
| |||
| 0 = End without motor calculation |
| parameter P3900. | Default = 0 | |
|
|
|
| ||
| or factory reset. |
|
|
|
|
| 1 = End with motor calculation | 2. | Press | to access the |
|
|
| parameter values level. |
| ||
| and factory reset (recommended |
|
|
|
|
| on SED2 without bypass option). | 3. | Press | to advance to 1. |
|
| 2 = End with motor calculation |
| |||
|
|
|
|
| |
| and with I/O reset. | 4. | Press | to confirm the |
|
|
|
| |||
| 3 = End with motor calculation |
| setting. |
|
|
| but without I/O reset |
|
|
|
|
| (recommended with SED2 with |
|
|
|
|
| bypass option). |
|
|
|
|
|
|
|
|
|
|
NOTES:
1. P0010 must always be set back to 0 before operating the motor.
2. If P3900 is greater than 0 on completion of commissioning, P0010 is automatically set back to 0.
3. If P0700 either indeed was changed during this process, programming of P0704 = 3 is required.
30 | Siemens Building Technologies, Inc. |