SED2 VFD Electronic Bypass Option Operating Instructions
Reset to Factory Defaults
Parameter | Description |
|
| Action | Setting/ |
|
| Default | |||
|
|
|
|
| |
|
|
|
|
|
|
P0010 | Reset to Factory Default | 1. | Press | to enter the SED2 | P0010: |
P0970 |
| Setting = 30 | |||
|
| parameter mode and to display | |||
| Resets SED2 parameters to the |
| Default = 0 | ||
| factory defaults. |
| r0000. |
|
|
|
|
|
| P0970: | |
|
|
|
|
| |
|
| 2. | Press | to advance to | Setting = 1 |
|
| Default = 0 | |||
|
|
| parameter P0010. | ||
|
|
|
| ||
|
| 3. | Press | to access the |
|
|
|
| parameter values level. |
| |
|
| 4. | Press | to advance to 30. |
|
|
| 5. | Press | to confirm and save |
|
|
|
| the setting. |
| |
|
| 6. | Press | to go to parameter |
|
|
|
| P0970. |
|
|
|
| 7. | Press | to access the |
|
|
|
| parameter values level. |
| |
|
| 8. | Press | to advance to 1. |
|
|
| 9. | Press | to confirm and save |
|
|
|
| the setting. |
| |
|
|
|
|
|
|
NOTES:
1. First set P0010 = 30.
2. Stop SED2 (that is, disable all pulses) before you reset parameters to factory default values.
3. The following parameters retain their values after a factory reset:
• P0918 (address of CB, communications board or module)
• P2010 (USS baud rate)
• P2011 (USS address)
4. The reset process takes about 10 seconds.
40 | Siemens Building Technologies, Inc. |