Siemens 125-3208 operating instructions SED2 VFD Electronic Bypass Option Operating Instructions

Page 42

SED2 VFD Electronic Bypass Option Operating Instructions

Automatic Restart Continued

Parameter

Description

Action

Setting/

Default

 

 

 

 

 

 

 

P1210

P1210 = 4, Restart after supply power

 

 

(Continued)

brownout (P1211 disabled):

 

 

 

For these settings it is fundamental that

 

 

 

the drive only restarts if it has been in a

 

 

 

RUN state at the time of the fault

 

 

 

(F0003). The inverter will acknowledge

 

 

 

the fault and will restart the drive after a

 

 

 

blackout or brownwout. It is necessary

 

 

 

that the ON command is wired via

 

 

 

digital input (DIN).

 

 

 

P1210 = 5, Restart after blackout or fault

 

 

 

(P1211 disabled):

 

 

 

The inverter will acknowledge the faults

 

 

 

(F0003 etc.) at power on after blackout

 

 

 

and will restart the drive. It is necessary

 

 

 

that the ON command is wired via digital

 

 

 

input (DIN).

 

 

 

P1210 = 6, Restart after supply power

 

 

 

brown/blackout or fault (P1211 disabled):

 

 

 

The inverter will acknowledge the faults

 

 

 

(F0003 etc.) at power on after blackout or

 

 

 

brownout and will restart the drive. It is

 

 

 

necessary that the ON command is wired

 

 

 

via digital input (DIN). Setting 6 causes

 

 

 

the motor to restart immediately.

 

 

 

P1210 = 7, Restart after supply power

 

 

 

brown/blackout or fault (P1211

 

 

 

enabled):

 

 

 

This setting is for use where an external

 

 

 

bypass system or process is interlocked

 

 

 

with a relay that is set to

 

 

 

P0731/P0732=52.3 (fault). The inverter

 

 

 

functions the same as P1210=6 (trip on

 

 

 

brownout, blackout or fault) but uses

 

 

 

P1211 and only sets the fault bit

 

 

 

P0731/P0732=52.3 when the specified

 

 

 

number of restarts defined in P1211 has

 

 

 

expired. If no trip occurs after 2 hours,

 

 

 

the fault counter is reset.

 

 

 

 

 

 

NOTES:

1.Auto restart requires a constant ON command (such as via a digital input).

2.P1200 flying start must be used in cases where the motor may still be turning, such as after a brief input power break, or can be driven by the load.

3.A supply power brownout is when the power is interrupted and reapplied before the operator panel display has gone dark. It is a very short supply power break where the DC link has not fully collapsed.

4.A supply power blackout is when the operator panel display has gone dark before the power is reapplied. It is a long supply power break where the DC link has fully collapsed.

34

Siemens Building Technologies, Inc.

Image 42
Contents SED2 VFD Electronic Bypass Options Page SED2 VFD Electronic Bypass Option Operating Instructions Page Service Statement Page Table of Contents Application Feature Setup Technical Specifications TroubleshootingManual Organization How to Use this ManualNotation Symbol Meaning Manual NotationsWhere To Send Comments Reference DocumentsSafety Instructions Electronic Bypass Option Overview General DescriptionFuses optional Controller Board Controller Board Inputs and OutputsContactors Keypad FunctionsPushbutton/Indicator DescriptionPushbutton/Indicator Description Output relay on the Controller boardDimensions and Weights Installation InstructionsMechanical Installation Environmental ConditionsBypass Dimensions in Inches Centimeters MountingFrame Sizes D and E Conduit Locations Viewed from Bottom Electrical Installation Bypass Power Circuit Routing of Power and Control Wiring For Frame Sizes a and B Disconnect Overload Ground Lug Switch Disconnect Overload Ground Lug Wire Max Installation Inspection Startup ProceduresSafety Precautions Power-OnSwitch Description Position DIP Switch Settings for E-Bypass FeaturesQuick Commissioning Parameter Description Action Setting Default User Access LevelQuick Commissioning Operation for Europe/N AmericaRated Motor Voltage Rated Motor cosPhi P308, or Rated Motor PowerRated Motor Current Rated Motor Efficiency P0309Rated Motor Frequency Rated Motor SpeedSelection of Command Source Start CommandMotor Overload Factor Speed Command Source Selection of FrequencySetpoint Minimum Motor Frequency Maximum Motor Frequency Ramp-up TimeRamp-down time End Quick CommissioningFlying Start Additional Parameter SettingsFlying Start R0000Motor Current Flying Start Search Rate Flying StartAutomatic Restart Automatic RestartSED2 VFD Electronic Bypass Option Operating Instructions Number of Restart Attempts Time to First RestartVdc Controller Restart Time IncrementPulse Frequency Motor Data Identification Motor Data IdentificationMotor Data Identification Reset to Factory Defaults P0970Required SED2 Parameter Settings Parameter SettingAuto Bypass without Interlock Application Feature SetupOverview DescriptionSettings Example SED2 SettingsInterlock Application Feature Setup Essential Services Wiring Example for InterlockWiring Example for Essential Services Interlock and Auto Bypass on VFD Fault Wiring Example for Interlock and Auto Bypass on VFD FaultDrive Specifications Description Technical SpecificationsSpecifications Description Electronic Bypass SpecificationsDrive Specifications Description SED2 VFD Electronic Bypass Operating InstructonsBasic Sanity Description Test Fault Code/Flashes TroubleshootingPower-on Initialization Failure Unit Fault Condition Basic Sanity Test Fault CodesOverride Jumper FusesFuse Replacement Information VFD0122R2 Troubleshooting Siemens Building Technologies, Inc