Startup Procedures

9.If motor rotation is incorrect in either VFD, bypass, or both modes, have the appropriate site personnel take corrective action as follows:

Wrong Rotation in Bypass, Right in VFD Mode – Swap two input leads on the main input device of the Electronic Bypass Option.

Wrong Rotation in VFD, Right in Bypass Mode – Swap two input leads on the main input device of the Electronic Bypass Option and swap two motor leads at the motor overload in the Electronic Bypass Option.

Wrong Rotation in both VFD and Bypass Modes – Swap two motor leads at the motor overload in the Electronic Bypass Option.

Quick Commissioning

Parameter P0010 is the Commissioning Parameter Filter. It allows you to select a group of parameters that can be used for quick commissioning, including motor data, and motor ramp-up and ramp-down settings.

It is important to use parameter P0010 to commission the SED2, parameter P0003 to select the access level for using parameters, and parameter P0004 to filter the parameters according to their functionality. When Commissioning Parameter Filter P0010 = 1, it initiates the quick commissioning procedure.

It is recommended that you use the quick commissioning procedure. However, experienced users may commission the equipment without the P0004 filter functions.

At the end of the quick commissioning procedure, set parameter P3900 = 3. This setting performs the necessary motor calculations and sets all remaining parameters (those not included in P0010 = 1) to the factory default values. If 3900 is set to a value greater than 0, P0010 is automatically reset to 0. (If P0010 = 1, the SED2 cannot start.) The process of performing motor calculations and setting all parameters to factory default values is only possible via quick commissioning.

Siemens Building Technologies, Inc.

21

Image 29
Contents SED2 VFD Electronic Bypass Options Page SED2 VFD Electronic Bypass Option Operating Instructions Page Service Statement Page Table of Contents Technical Specifications Troubleshooting Application Feature SetupNotation Symbol Meaning How to Use this ManualManual Organization Manual NotationsReference Documents Where To Send CommentsSafety Instructions Fuses optional Electronic Bypass Option OverviewGeneral Description Controller Board Inputs and Outputs Controller BoardKeypad Functions ContactorsDescription Pushbutton/IndicatorOutput relay on the Controller board Pushbutton/Indicator DescriptionMechanical Installation Installation InstructionsDimensions and Weights Environmental ConditionsMounting Bypass Dimensions in Inches CentimetersFrame Sizes D and E Conduit Locations Viewed from Bottom Electrical Installation Bypass Power Circuit Routing of Power and Control Wiring For Frame Sizes a and B Disconnect Overload Ground Lug Switch Disconnect Overload Ground Lug Wire Max Safety Precautions Startup ProceduresInstallation Inspection Power-OnDIP Switch Settings for E-Bypass Features Switch Description PositionQuick Commissioning Quick Commissioning Parameter Description Action Setting DefaultUser Access Level Rated Motor Voltage Operation for Europe/NAmerica Rated Motor Current Rated Motor PowerRated Motor cosPhi P308, or Rated Motor Efficiency P0309Rated Motor Speed Rated Motor FrequencyMotor Overload Factor Selection of Command SourceStart Command Setpoint Speed Command SourceSelection of Frequency Minimum Motor Frequency Ramp-up Time Maximum Motor FrequencyEnd Quick Commissioning Ramp-down timeFlying Start Additional Parameter SettingsFlying Start R0000Search Rate Flying Start Motor Current Flying StartAutomatic Restart Automatic RestartSED2 VFD Electronic Bypass Option Operating Instructions Time to First Restart Number of Restart AttemptsRestart Time Increment Vdc ControllerPulse Frequency Motor Data Identification Motor Data IdentificationMotor Data Identification P0970 Reset to Factory DefaultsParameter Setting Required SED2 Parameter SettingsOverview Application Feature SetupAuto Bypass without Interlock DescriptionExample SED2 Settings SettingsInterlock Application Feature Setup Wiring Example for Interlock Essential ServicesWiring Example for Essential Services Wiring Example for Interlock and Auto Bypass on VFD Fault Interlock and Auto Bypass on VFD FaultSpecifications Description Technical SpecificationsDrive Specifications Description Electronic Bypass SpecificationsSED2 VFD Electronic Bypass Operating Instructons Drive Specifications DescriptionPower-on Initialization Failure Unit Fault Condition TroubleshootingBasic Sanity Description Test Fault Code/Flashes Basic Sanity Test Fault CodesFuses Override JumperFuse Replacement Information VFD0122R2 Troubleshooting Siemens Building Technologies, Inc