HP xw2x220c Blade manual Grounding requirements, Grounding systems, Building distribution

Page 35

Raceway systems (electrical conduits) (LAHJ)

Raceways (electrical conduits) form part of the protective ground path for personnel and equipment. Raceways protect the wiring from accidental damage and also provide a heatsink for the wires.

Any of the following types may be used:

EMT thin-wall tubing

Rigid (metal) conduit

Liquidtight with RFI shield grounded (most commonly used under raised floors)

Armored cable

Building distribution

All building feeders and branch circuitry should be in rigid metallic conduit with proper connectors (to provide ground continuity). Conduit that is exposed and subject to damage should be constructed of rigid galvanized steel.

Grounding requirements

This equipment must be grounded properly for proper operation and safety. In the United States, you must install the equipment in accordance with NFPA 70 (National Electric Code), Article 250, as well as any local and regional building codes.

In Canada, you must install the equipment in accordance with Canadian Standards Association, CSA C22.1, Canadian Electrical Code.

In all other countries, you must install the equipment in accordance with any regional or national electrical wiring codes, such as the International Electrotechnical Commission (IEC) Code 364, parts 1 through 7. Furthermore, you must be sure that all power distribution devices used in the installation, such as branch wiring and receptacles, are listed or certified grounding-type devices.

Because of the high ground-leakage currents associated with this equipment, HP recommends the use of a PDU that is either permanently wired to the building’s branch circuit or includes a nondetachable cord that is wired to an industrial-style plug. NEMA locking-style plugs or those complying with IEC 60309 are considered suitable for this purpose. Using common power outlet strips to supply power to this equipment is not recommended.

Grounding systems

HP systems are tested and certified only with grounding systems in which a neutral return path and a protective earth are separate conductors without any inserted impedances. Additionally, the protective earth and return neutral wires are shorted together at the XO bonding junction on the secondary side of the newly derived power source.

Grounding and earth leakage current

For proper operation and safety, rack components must be properly grounded in accordance with any local and regional building codes. Furthermore, be sure that all power distribution devices used in the installation, such as branch wiring and receptacles, are Listed or Certified grounding-type devices.

Observe the following limits when connecting products to AC power distribution devices:

Power requirements and considerations 35

Image 35
Contents HP BladeSystem c-Class Site Planning Guide Intended audience Contents Conversion factors and formulas Technical support Related documentation IntroductionAbout this document HP site planning assistance General site preparation guidelinesAshrae guidelines for site planning Computer room preparation Site planning considerationsPage Basic air distribution systems Air conditioning system specificationsAir conditioning ducts Cabling requirementsAverage floor loading Floor loadingRaised floor loading Fire suppression Computer room safetyInstallation and maintenance precautions Fire protectionLighting requirements for equipment servicing Working space for component accessDust and pollution Environmental requirementsEnvironmental elements Humidity levelMetallic particulate contamination Electrostatic discharge prevention Acoustic noise specificationAshrae Recommended operating environmentHP Rack Airflow Optimization Kit Airflow requirementsSpace requirements Blanking panelsEquipment clearance and floor loading Delivery space requirementsOperational space requirements Floor plan grid HP BladeSystem enclosure environmental specifications Rack and accessory footprintsFront door clearance Environmental requirements Environmental requirements Best practices for deployment in rows Third-party racks Rack placement and arrangement for proper airflowRack tie-down option kit Electrical factors Power requirements and considerationsPower requirements Power consumption Electrical load requirements circuit breaker sizing Power system protection Power qualityPower considerations Factors affecting power qualityPower redundancy Power optionsLine voltage selection Non-redundant powerWire selection Distribution hardwareBuilding distribution Grounding requirementsGrounding systems Raceway systems electrical conduits LahjDual power source grounding Power distribution safety grounding LahjPower panel ground Computer safety groundRaised floor high-frequency noise grounding Cabinet performance grounding high frequency groundEquipment grounding implementation details System installation guidelinesWiring connections Data communications cables Power configurationDynamic Power Capping HP BladeSystem enclosure single-phase power configurationPower requirements and considerations Power requirements and considerations Power requirements and considerations C7000 PDU example PDU installationC3000 PDU example HP BladeSystem c7000 Enclosure three-phase AC configuration HP BladeSystem c7000 Enclosure DC configuration HP BladeSystem enclosure DC power configurationHP BladeSystem c3000 Enclosure DC configuation Power supply specificationsSingle-phase HP 2250W Power Supply specification Specification Value Specification Value DC power supply specification HP BladeSystem c3000 Enclosure specifications Hardware specifications and requirementsEnclosure specifications HP BladeSystem c7000 Enclosure specificationsRack requirements HP 10000 G2 rack specificationsRack-free environment requirements Example typical configuration Configuration scenariosExample configurations Example minimum configurationExample maximum configuration Estimating power and cooling Estimating total weight Preparing for installation Preparing for installation Additional rack considerations General component placement guidelinesRack configuration software Sample checklists Sample installation scheduleIs there a completed floor plan? Delivery survey Page Formulas Conversion factors and formulasConversion factors HP contact information Technical supportBefore you contact HP Acronyms and abbreviations UPS Glossary Apparent powerKVA Index Site planning assistance from HP

xw2x220c Blade specifications

The HP xw2x220c Blade is designed for organizations that require a high-performance, space-efficient computing solution. This blade server epitomizes the commitment to enhancing data center efficiency and maximizing computing power without compromising on reliability.

One of the standout features of the HP xw2x220c Blade is its compact form factor, which enables organizations to fit a substantial amount of computing power in a small footprint. This is particularly beneficial for businesses with limited space, as they can host more servers within the same physical environment. The blade is optimized for virtualization, allowing it to handle multiple workloads simultaneously, which translates to cost savings and better resource utilization.

The server is powered by advanced Intel Xeon processors, ensuring efficient processing capabilities for demanding applications. The HP xw2x220c Blade supports multiple CPU options, allowing organizations to select the configuration that best meets their workload requirements. Leveraging Intel's latest technologies, it offers enhanced performance while maintaining energy efficiency, which is a critical consideration in today’s environmentally conscious technological landscape.

In terms of memory, the xw2x220c Blade supports high-capacity DDR4 RAM, which enhances data access speeds and ensures smooth operation even during heavy loads. The architecture of the blade also includes advanced cooling technology that optimizes airflow to maintain optimal temperatures, thereby prolonging hardware lifespan and reliability.

Network connectivity is a vital feature, and the HP xw2x220c Blade offers multiple Ethernet ports for flexible networking options, as well as support for fibre channel connections. This enables seamless integration into existing network configurations, ensuring high-speed data transfer rates that are crucial for real-time applications.

Security features are also integrated into the HP xw2x220c Blade, including options for secure boot, system integrity verification, and advanced encryption capabilities. These attributes protect sensitive data from unauthorized access and potential breaches, which is essential for organizations dealing with confidential information.

In conclusion, the HP xw2x220c Blade is a formidable choice for businesses seeking a compact, powerful, and efficient computing solution. Its combination of advanced processing capabilities, extensive memory support, flexible networking options, and robust security features makes it well-suited for a variety of applications, making it an essential component for modern data centers.