HP xw2x220c Blade System installation guidelines, Equipment grounding implementation details

Page 38

Add a grounding grid made of copper strips mounted to the subfloor. The strips should be 0.8 mm (0.032 in) thick and a minimum of 76 mm (3.0 in) wide. Connect each pedestal to four strips using 6-mm (0.25-in) bolts tightened to the manufacturer’s torque recommendation.

Equipment grounding implementation details

Connect all HP equipment cabinets to the site ground grid as follows:

1.Attach one end of each ground strap to the applicable cabinet ground lug.

2.Attach the other end to the nearest pedestal base (raised floor) or cable trough ground point (nonraised floor).

3.Check that the braid contact on each end of the ground strap consists of a terminal and connection hardware (a 6-mm [0.25-in] bolt, nuts, and washers).

4.Check that the braid contact connection points are free of paint or other insulating material and treated with a contact enhancement compound (similar to Burndy Penetrox).

System installation guidelines

In domestic installations, install the proper receptacles before the HP equipment arrives. For installation procedures, see the appropriate installation guide.

Wiring connections

Expansion and contraction rates vary among different metals. Therefore, the integrity of an electrical connection depends on the restraining force applied. Connections that are too tight can compress or deform the hardware and cause it to weaken. This deformation usually leads to high impedance, preventing circuit breakers from tripping when needed or contributing to a buildup of high frequency noise.

CAUTION: Connections that are too loose or too tight can have a high impedance that causes serious problems, such as erratic equipment operation. A high impedance connection overheats and sometimes causes fire or high temperatures that can destroy hard-to-replace components such as distribution panels or system bus bars.

Power requirements and considerations 38

Image 38
Contents HP BladeSystem c-Class Site Planning Guide Intended audience Contents Conversion factors and formulas Technical support Related documentation IntroductionAbout this document HP site planning assistance General site preparation guidelinesAshrae guidelines for site planning Site planning considerations Computer room preparationPage Air conditioning system specifications Basic air distribution systemsCabling requirements Air conditioning ductsAverage floor loading Floor loadingRaised floor loading Fire protection Computer room safetyInstallation and maintenance precautions Fire suppressionWorking space for component access Lighting requirements for equipment servicingHumidity level Environmental requirementsEnvironmental elements Dust and pollutionMetallic particulate contamination Acoustic noise specification Electrostatic discharge preventionRecommended operating environment AshraeBlanking panels Airflow requirementsSpace requirements HP Rack Airflow Optimization KitEquipment clearance and floor loading Delivery space requirementsOperational space requirements Floor plan grid Rack and accessory footprints HP BladeSystem enclosure environmental specificationsFront door clearance Environmental requirements Environmental requirements Best practices for deployment in rows Rack placement and arrangement for proper airflow Third-party racksRack tie-down option kit Electrical factors Power requirements and considerationsPower requirements Power consumption Electrical load requirements circuit breaker sizing Factors affecting power quality Power qualityPower considerations Power system protectionPower options Power redundancyDistribution hardware Non-redundant powerWire selection Line voltage selectionRaceway systems electrical conduits Lahj Grounding requirementsGrounding systems Building distributionComputer safety ground Power distribution safety grounding LahjPower panel ground Dual power source groundingCabinet performance grounding high frequency ground Raised floor high-frequency noise groundingEquipment grounding implementation details System installation guidelinesWiring connections HP BladeSystem enclosure single-phase power configuration Power configurationDynamic Power Capping Data communications cablesPower requirements and considerations Power requirements and considerations Power requirements and considerations PDU installation C7000 PDU exampleC3000 PDU example HP BladeSystem c7000 Enclosure three-phase AC configuration HP BladeSystem enclosure DC power configuration HP BladeSystem c7000 Enclosure DC configurationHP BladeSystem c3000 Enclosure DC configuation Power supply specificationsSingle-phase HP 2250W Power Supply specification Specification Value Specification Value DC power supply specification HP BladeSystem c7000 Enclosure specifications Hardware specifications and requirementsEnclosure specifications HP BladeSystem c3000 Enclosure specificationsHP 10000 G2 rack specifications Rack requirementsRack-free environment requirements Example minimum configuration Configuration scenariosExample configurations Example typical configurationExample maximum configuration Estimating power and cooling Estimating total weight Preparing for installation Preparing for installation General component placement guidelines Additional rack considerationsRack configuration software Sample installation schedule Sample checklistsIs there a completed floor plan? Delivery survey Page Formulas Conversion factors and formulasConversion factors HP contact information Technical supportBefore you contact HP Acronyms and abbreviations UPS Apparent power GlossaryKVA Index Site planning assistance from HP

xw2x220c Blade specifications

The HP xw2x220c Blade is designed for organizations that require a high-performance, space-efficient computing solution. This blade server epitomizes the commitment to enhancing data center efficiency and maximizing computing power without compromising on reliability.

One of the standout features of the HP xw2x220c Blade is its compact form factor, which enables organizations to fit a substantial amount of computing power in a small footprint. This is particularly beneficial for businesses with limited space, as they can host more servers within the same physical environment. The blade is optimized for virtualization, allowing it to handle multiple workloads simultaneously, which translates to cost savings and better resource utilization.

The server is powered by advanced Intel Xeon processors, ensuring efficient processing capabilities for demanding applications. The HP xw2x220c Blade supports multiple CPU options, allowing organizations to select the configuration that best meets their workload requirements. Leveraging Intel's latest technologies, it offers enhanced performance while maintaining energy efficiency, which is a critical consideration in today’s environmentally conscious technological landscape.

In terms of memory, the xw2x220c Blade supports high-capacity DDR4 RAM, which enhances data access speeds and ensures smooth operation even during heavy loads. The architecture of the blade also includes advanced cooling technology that optimizes airflow to maintain optimal temperatures, thereby prolonging hardware lifespan and reliability.

Network connectivity is a vital feature, and the HP xw2x220c Blade offers multiple Ethernet ports for flexible networking options, as well as support for fibre channel connections. This enables seamless integration into existing network configurations, ensuring high-speed data transfer rates that are crucial for real-time applications.

Security features are also integrated into the HP xw2x220c Blade, including options for secure boot, system integrity verification, and advanced encryption capabilities. These attributes protect sensitive data from unauthorized access and potential breaches, which is essential for organizations dealing with confidential information.

In conclusion, the HP xw2x220c Blade is a formidable choice for businesses seeking a compact, powerful, and efficient computing solution. Its combination of advanced processing capabilities, extensive memory support, flexible networking options, and robust security features makes it well-suited for a variety of applications, making it an essential component for modern data centers.