Rear door: The clearance between the rear of the enclosure and the rear rack door must be a minimum of 175 mm (6.9 in) to accommodate system cabling.

Side: The clearance between the installed rack component and the side panels of the rack must be a minimum of 70 mm (2.75 in).

Width: 483 mm (19 in)

Depth: Maximum clearance between front and rear RETMA rails is 864 mm (34 in). Minimum clearance for round-hole racks is 627 mm (24.7 in). Minimum clearance for square-hole racks is 635 mm (25 in).

The rack must be able to accept the adjustable rack rails that are shipped with each enclosure: o Minimum rail length: 635 mm (25 in)

o Maximum rail length: 864 mm (34 in)

Rack tie-down option kit

The HP 10000 G2 Series Rack Tie-Down Option Kit enables you to secure HP 10000 G2 Series Racks to the floor.

The following table indicates where the holes are to be drilled to secure the rack to the floor. The distances are measured from the holes on the tie-downs. To drill your holes, contact your building structural engineer. After your holes have been drilled, insert a bolt with a washer into each hole, securing the rack to the floor.

Callout

600W distance

 

 

A

470 mm (18.0 in)

 

 

B

235 mm (9.3 in)

 

 

C

987.1 mm (38.9 in)

 

 

D

231 mm (9.1 in)

 

 

E

462 mm (18.2 in)

 

 

For more information, see the HP 10000 G2 Series Rack Tie-Down Option Kit Installation Instructions.

Environmental requirements 28

Image 28
Contents HP BladeSystem c-Class Site Planning Guide Intended audience Contents Conversion factors and formulas Technical support About this document IntroductionRelated documentation Ashrae guidelines for site planning General site preparation guidelinesHP site planning assistance Site planning considerations Computer room preparationPage Air conditioning system specifications Basic air distribution systemsCabling requirements Air conditioning ductsRaised floor loading Floor loadingAverage floor loading Computer room safety Installation and maintenance precautionsFire protection Fire suppressionWorking space for component access Lighting requirements for equipment servicingEnvironmental requirements Environmental elementsHumidity level Dust and pollutionMetallic particulate contamination Acoustic noise specification Electrostatic discharge preventionRecommended operating environment AshraeAirflow requirements Space requirementsBlanking panels HP Rack Airflow Optimization KitOperational space requirements Delivery space requirementsEquipment clearance and floor loading Floor plan grid Rack and accessory footprints HP BladeSystem enclosure environmental specificationsFront door clearance Environmental requirements Environmental requirements Best practices for deployment in rows Rack placement and arrangement for proper airflow Third-party racksRack tie-down option kit Power requirements Power requirements and considerationsElectrical factors Power consumption Electrical load requirements circuit breaker sizing Power quality Power considerationsFactors affecting power quality Power system protectionPower options Power redundancyNon-redundant power Wire selectionDistribution hardware Line voltage selectionGrounding requirements Grounding systemsRaceway systems electrical conduits Lahj Building distributionPower distribution safety grounding Lahj Power panel groundComputer safety ground Dual power source groundingCabinet performance grounding high frequency ground Raised floor high-frequency noise groundingWiring connections System installation guidelinesEquipment grounding implementation details Power configuration Dynamic Power CappingHP BladeSystem enclosure single-phase power configuration Data communications cablesPower requirements and considerations Power requirements and considerations Power requirements and considerations PDU installation C7000 PDU exampleC3000 PDU example HP BladeSystem c7000 Enclosure three-phase AC configuration HP BladeSystem enclosure DC power configuration HP BladeSystem c7000 Enclosure DC configurationSingle-phase HP 2250W Power Supply specification Power supply specificationsHP BladeSystem c3000 Enclosure DC configuation Specification Value Specification Value DC power supply specification Hardware specifications and requirements Enclosure specificationsHP BladeSystem c7000 Enclosure specifications HP BladeSystem c3000 Enclosure specificationsHP 10000 G2 rack specifications Rack requirementsRack-free environment requirements Configuration scenarios Example configurationsExample minimum configuration Example typical configurationExample maximum configuration Estimating power and cooling Estimating total weight Preparing for installation Preparing for installation General component placement guidelines Additional rack considerationsRack configuration software Sample installation schedule Sample checklistsIs there a completed floor plan? Delivery survey Page Conversion factors Conversion factors and formulasFormulas Before you contact HP Technical supportHP contact information Acronyms and abbreviations UPS Apparent power GlossaryKVA Index Site planning assistance from HP

xw2x220c Blade specifications

The HP xw2x220c Blade is designed for organizations that require a high-performance, space-efficient computing solution. This blade server epitomizes the commitment to enhancing data center efficiency and maximizing computing power without compromising on reliability.

One of the standout features of the HP xw2x220c Blade is its compact form factor, which enables organizations to fit a substantial amount of computing power in a small footprint. This is particularly beneficial for businesses with limited space, as they can host more servers within the same physical environment. The blade is optimized for virtualization, allowing it to handle multiple workloads simultaneously, which translates to cost savings and better resource utilization.

The server is powered by advanced Intel Xeon processors, ensuring efficient processing capabilities for demanding applications. The HP xw2x220c Blade supports multiple CPU options, allowing organizations to select the configuration that best meets their workload requirements. Leveraging Intel's latest technologies, it offers enhanced performance while maintaining energy efficiency, which is a critical consideration in today’s environmentally conscious technological landscape.

In terms of memory, the xw2x220c Blade supports high-capacity DDR4 RAM, which enhances data access speeds and ensures smooth operation even during heavy loads. The architecture of the blade also includes advanced cooling technology that optimizes airflow to maintain optimal temperatures, thereby prolonging hardware lifespan and reliability.

Network connectivity is a vital feature, and the HP xw2x220c Blade offers multiple Ethernet ports for flexible networking options, as well as support for fibre channel connections. This enables seamless integration into existing network configurations, ensuring high-speed data transfer rates that are crucial for real-time applications.

Security features are also integrated into the HP xw2x220c Blade, including options for secure boot, system integrity verification, and advanced encryption capabilities. These attributes protect sensitive data from unauthorized access and potential breaches, which is essential for organizations dealing with confidential information.

In conclusion, the HP xw2x220c Blade is a formidable choice for businesses seeking a compact, powerful, and efficient computing solution. Its combination of advanced processing capabilities, extensive memory support, flexible networking options, and robust security features makes it well-suited for a variety of applications, making it an essential component for modern data centers.