For UPS products and PDUs that have permanently attached AC power cords or are directly wired to the building power, the total combined leakage current should not exceed 5 percent of the total input current required for the connected products.

For UPS products and PDUs that have detachable AC power cords, the total combined leakage current should not exceed 3.5 mA per PDU or UPS.

Power distribution safety grounding (LAHJ)

The power distribution safety grounding system consists of connecting various points in the power distribution system to earth ground using green (green/yellow) wire ground conductors. When tied to metal chassis parts that might be touched, these ground connections protect computer room personnel against shock hazard from current leakage and fault conditions.

Power distribution systems consist of several parts. HP recommends that these parts be solidly interconnected to provide an equipotential ground to all points.

Main building electrical ground

The main electrical service entrance equipment should have an earth ground connection, as required by applicable codes. Connections such as a grounding rod, building steel, or a conductive type cold water service pipe provide an earth ground.

Conduit bonding

Construct all electrical distribution systems of metallic conduit that is connected together securely or bonded to panels and electrical boxes to provide a continuous grounding system.

Power panel ground

Each power panel should be grounded to the electrical service entrance with green (green/yellow) wire ground conductors. The green (green/yellow) wire ground conductors should be sized per applicable codes (based on circuit overcurrent device ratings).

NOTE: The green wire ground conductor can be a black wire with green tape (LAHJ).

Computer safety ground

Ground all computer equipment with the green (green/yellow) wire included in the branch circuitry. The green (green/yellow) wire ground conductors should be connected to the appropriate power panel and should be sized per applicable codes (based on circuit overcurrent device ratings).

Dual power source grounding

With dual power sources, both sources must have the same ground reference. Otherwise, an electrical potential could exist that could be hazardous to personnel and might cause performance issues for the equipment.

Because the dual power sources often originate from two different transformers or two different UPS devices, use the same ground reference point to ground the secondary of each transformer or UPS device. Measure the voltage potentials from ground pin to ground pin of these sources. Voltage levels that are

Power requirements and considerations 36

Image 36
Contents HP BladeSystem c-Class Site Planning Guide Intended audience Contents Conversion factors and formulas Technical support Introduction About this documentRelated documentation General site preparation guidelines Ashrae guidelines for site planningHP site planning assistance Site planning considerations Computer room preparationPage Air conditioning system specifications Basic air distribution systemsCabling requirements Air conditioning ductsFloor loading Raised floor loadingAverage floor loading Computer room safety Installation and maintenance precautionsFire protection Fire suppressionWorking space for component access Lighting requirements for equipment servicingEnvironmental requirements Environmental elementsHumidity level Dust and pollutionMetallic particulate contamination Acoustic noise specification Electrostatic discharge preventionRecommended operating environment AshraeAirflow requirements Space requirementsBlanking panels HP Rack Airflow Optimization KitDelivery space requirements Operational space requirementsEquipment clearance and floor loading Floor plan grid Rack and accessory footprints HP BladeSystem enclosure environmental specificationsFront door clearance Environmental requirements Environmental requirements Best practices for deployment in rows Rack placement and arrangement for proper airflow Third-party racksRack tie-down option kit Power requirements and considerations Power requirementsElectrical factors Power consumption Electrical load requirements circuit breaker sizing Power quality Power considerationsFactors affecting power quality Power system protectionPower options Power redundancyNon-redundant power Wire selectionDistribution hardware Line voltage selectionGrounding requirements Grounding systemsRaceway systems electrical conduits Lahj Building distributionPower distribution safety grounding Lahj Power panel groundComputer safety ground Dual power source groundingCabinet performance grounding high frequency ground Raised floor high-frequency noise groundingSystem installation guidelines Wiring connectionsEquipment grounding implementation details Power configuration Dynamic Power CappingHP BladeSystem enclosure single-phase power configuration Data communications cablesPower requirements and considerations Power requirements and considerations Power requirements and considerations PDU installation C7000 PDU exampleC3000 PDU example HP BladeSystem c7000 Enclosure three-phase AC configuration HP BladeSystem enclosure DC power configuration HP BladeSystem c7000 Enclosure DC configurationPower supply specifications Single-phase HP 2250W Power Supply specificationHP BladeSystem c3000 Enclosure DC configuation Specification Value Specification Value DC power supply specification Hardware specifications and requirements Enclosure specificationsHP BladeSystem c7000 Enclosure specifications HP BladeSystem c3000 Enclosure specificationsHP 10000 G2 rack specifications Rack requirementsRack-free environment requirements Configuration scenarios Example configurationsExample minimum configuration Example typical configurationExample maximum configuration Estimating power and cooling Estimating total weight Preparing for installation Preparing for installation General component placement guidelines Additional rack considerationsRack configuration software Sample installation schedule Sample checklistsIs there a completed floor plan? Delivery survey Page Conversion factors and formulas Conversion factorsFormulas Technical support Before you contact HPHP contact information Acronyms and abbreviations UPS Apparent power GlossaryKVA Index Site planning assistance from HP

xw2x220c Blade specifications

The HP xw2x220c Blade is designed for organizations that require a high-performance, space-efficient computing solution. This blade server epitomizes the commitment to enhancing data center efficiency and maximizing computing power without compromising on reliability.

One of the standout features of the HP xw2x220c Blade is its compact form factor, which enables organizations to fit a substantial amount of computing power in a small footprint. This is particularly beneficial for businesses with limited space, as they can host more servers within the same physical environment. The blade is optimized for virtualization, allowing it to handle multiple workloads simultaneously, which translates to cost savings and better resource utilization.

The server is powered by advanced Intel Xeon processors, ensuring efficient processing capabilities for demanding applications. The HP xw2x220c Blade supports multiple CPU options, allowing organizations to select the configuration that best meets their workload requirements. Leveraging Intel's latest technologies, it offers enhanced performance while maintaining energy efficiency, which is a critical consideration in today’s environmentally conscious technological landscape.

In terms of memory, the xw2x220c Blade supports high-capacity DDR4 RAM, which enhances data access speeds and ensures smooth operation even during heavy loads. The architecture of the blade also includes advanced cooling technology that optimizes airflow to maintain optimal temperatures, thereby prolonging hardware lifespan and reliability.

Network connectivity is a vital feature, and the HP xw2x220c Blade offers multiple Ethernet ports for flexible networking options, as well as support for fibre channel connections. This enables seamless integration into existing network configurations, ensuring high-speed data transfer rates that are crucial for real-time applications.

Security features are also integrated into the HP xw2x220c Blade, including options for secure boot, system integrity verification, and advanced encryption capabilities. These attributes protect sensitive data from unauthorized access and potential breaches, which is essential for organizations dealing with confidential information.

In conclusion, the HP xw2x220c Blade is a formidable choice for businesses seeking a compact, powerful, and efficient computing solution. Its combination of advanced processing capabilities, extensive memory support, flexible networking options, and robust security features makes it well-suited for a variety of applications, making it an essential component for modern data centers.